A reactance relay is

(A) Voltage restrained directional relay

(B) Directional restrained over-current relay

(C) Voltage restrained over current relay

(D) Directional restrained over voltage relay

1 Answer

Answer :

A reactance relay is Directional restrained over-current relay

Related questions

Description : Reactance relay is normally preferred for protection against

Last Answer : Reactance relay is normally preferred for protection against earth faults

Description : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he

Last Answer : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he 0.52

Description : Consider the following statements. Which of these statements are correct ?  (1) Reactance relays are preferred for ground fault relaying  (2) Impedance relays are most suitable for:protecting long transmission lines  (3) Mho relays are best ... (1) and (3) (C) (2) and (4) (D) (1), (2) and (4)

Last Answer : Consider the following statements. Which of these statements are correct ?  (1) Reactance relays are preferred for ground fault relaying  (2) Impedance relays are most suitable for:protecting long transmission lines  (3) Mho relays are ... (1) and (3) (C) (2) and (4) (D) (1), (2) and (4)

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : Define impedance diagram and reactance diagram.

Last Answer : Impedance diagram: Impedance diagram is the simplified equivalent circuits of single line or one line diagrams of power system in which all components are represented by their equivalent circuit.  ... machines are neglected and is used only for fault current calculation is called reactance diagram.

Description : What do you mean by exciting resistance and exciting reactance?

Last Answer : At no-load, a transformer behaves as a highly inductive load connected to the system which contains some resistance and inductance in parallel. The resistance is called exciting resistance R0 = V1/I w and reactance is called exciting reactance, X0 = V1/I mag

Description : Capacitive reactance

Last Answer : Capacitive reactance formula

Description : Parallel Reactance and Resistance Example 1

Last Answer : Parallel Reactance and Resistance Example 1

Description : AC Circuits with Resistance but No Reactance

Last Answer : AC Circuits with Resistance but No Reactance AC Circuits with Resistance but No Reactance Series resistances let two resistances R 1 and R 2 are connected in series as shows in figure and there ... voltage. Voltage V A is common to both the branch hence voltage V A is common reference.

Description : If the % reactance upto the fault point is 20%, then the short circuit current will be

Last Answer : If the % reactance upto the fault point is 20%, then the short circuit current will be 5 times the full load current

Description : Ratio of the rotor reactance X to the rotor resistance R for a two-phase servo motor (A) is equal to that of a normal induction motor (B) is less than that of a normal induction motor (C) ... than that of a normal induction motor (D) may be less or greater than that of a normal induction motor

Last Answer : C

Description : Capacitive reactance is more when?

Last Answer : Capacitive reactance is more when capacitance is less and frequency of supply is less.

Description : What is the unit of reactance?

Last Answer : Unit of reactance is Ohms ( Ω ) .Reactance is denoted by X .

Description : What is the inverse of reactance?

Last Answer : Inverse of reactance is Susceptance .Unit of Susceptance is Siemens.

Description : what is the reciprocal of reactance?

Last Answer : reciprocal of reactance is susceptance.

Description : Fuel Pump Relay

Last Answer : Some car owners immediately suspect a fuel pump failure when their cars stall. However, there are many other engine problems that may resemble a fuel pump failure, such as restricted fuel filters, smashed ... advisable to bring your car to the repair shop so that the whole engine can be checked.

Description : main parts of Relay

Last Answer : Coil, plunger, contacts, springs, connecting terminals and enclosure.

Description : The purpose of the restraining coil in a biased differential relay is  (A) To reduce CT saturation during fault.  (B) To increase the sensitivity of the relay.  (C) To match the transformation ratio.  (D) To limit the spill current through the relay during heavy external fault.

Last Answer : d

Description : A relay used for protection of motors against overload is :  (A) Impedance relay (B) Electromagnetic attraction type (C) Thermal relay (D) Buchholz's relay

Last Answer : D

Description : A relay has a rating of 5 A, 2.2 sec IDMT and a relay setting of 125% TMS = 0.6. It is connected to a supply circuit through a C.T. 400/5 ratio. The fault current is 4000 A. The operating current of the relay is

Last Answer : A relay has a rating of 5 A, 2.2 sec IDMT and a relay setting of 125% TMS = 0.6. It is connected to a supply circuit through a C.T. 400/5 ratio. The fault current is 4000 A. The operating current of the relay is 6.25A

Description : The operating time of instantaneous relay is

Last Answer : The operating time of instantaneous relay is 0.1 sec

Description : What is the difference between relay and contactor?

Last Answer : Relay have smaller ratings. Contactor is a high rating relay.

Description : A negative sequence relay is used for protection of  (1) Generator (3) Motor (2) Transformer (4) Long Transmission lines

Last Answer : A negative sequence relay is used for protection of Generator 

Description : Buchholz relay is  (1) located in the conservator tank  (2) located in the transformer tank itself  (3) connected in the pipe connecting main tank of transformer and conservator  (4) installed in the circuit breaker

Last Answer : Buchholz relay is connected in the pipe connecting main tank of transformer and conservator 

Description : To prevent mal-operation of differentially connected relay while energizing a transformer, the relay restraining coil is based with  (1) second harmonic current  (2) third harmonic current  (3) fifth harmonic current  (4) seventh harmonic current

Last Answer : To prevent mal-operation of differentially connected relay while energizing a transformer, the relay restraining coil is based with  second harmonic current 

Description : Buchholz relay is used as a safety device with respect to which of the following? A) Audio transformers B) Oil filled power transformers C) Air core transformer D) None of these

Last Answer : Buchholz relay is used as a safety device with respect to which of the following? A) Audio transformers B) Oil filled power transformers C) Air core transformer D) None of these

Description : In the induction type directional over current relay, when a short-circuit occurs in the circuit (A) power flows in reverse direction (B) power flows in normal direction (C) directional power element does not operate (D) over current element is not energized

Last Answer : In the induction type directional over current relay, when a short-circuit occurs in the circuit power flows in reverse direction

Description : A solid state relay (A) withstands voltage transients (B) does not require auxiliary dc supply (C) provide low burden on CT and P (D) does not provide earth fault protection

Last Answer : A solid state relay provide low burden on CT and P

Last Answer : The torque produced in induction type relay (shaded pole structure) is inversely proportional to the square of the current.

Last Answer : Admittance relay is directional relay.

Last Answer : The relay with inverse time characteristic will operate within 5 to 10 sec.

Last Answer : The under voltage relay can be used for generators, busbars, transformers, motors.

Last Answer : Reactance relay is preferred for phase fault on short transmission line.

Last Answer : Induction cup relay is operated due to changes in current, voltage, impedance.

Last Answer : Interruption of large currents by relay requires arc suppressing blow out coils, wide separation of the opened contacts, high speed opening of contacts.

Last Answer : Overheating of relay contacts or contact born out is due to slow making and breaking of load circuit contacts, foreign matter on the contact surface, too low contact pressure.

Last Answer : A differential relay measures the vector difference between two or more similar electrical quantities.

Last Answer : Burden of a protective relay is the power absorbed by the circuit of relay.

Last Answer : In order that current should flow without causing excessive heating or voltage drop, the relay contacts should have low contact resistance, be clean and smooth, be of sufficient size and proper shape.

Last Answer : The relay operating speed depends upon the spring tension, the rate of flux built up, armature core air gap.

Last Answer : A Buchholz relay can be installed on oil cooled transformers.

Last Answer : Buchholz's relay gives warning and protection against electrical fault inside the transformer itself.

Description : How do relay works ?

Last Answer : Relay working like contact it is noise less 

Description : What is the use of Buchholz relay in transformer?

Last Answer : This is a transformer that is used to step up and down current. 

Description : What is the difference between a switch and a relay?

Last Answer : Switch is simply a mechanical contact mechanism and relay is a electromagnetic switch . Switch can be direct mechanically turn on and off but relay can be operated by energising coil .

Description : what is reverse power relay?

Last Answer : Thereverse powerrelay is a directional protective relay that prevents power from flowing in the reverse direction. Read our article going back ... it all to be up to date. And if you do, read it anyway just to check if youreallydo!

Description : Circuits with XL Alone

Last Answer : Circuits with XL Alone X L values in series let two inductive reactances X L 1 and X L 2 are connected in series and has value 50 ohm and 50 ohm respectively. 100 volts A C ... phasor. And it is taken horizontal. Phase angle between inductive current and voltage is same 90 degree.

Description : A capacitor-start single phase induction motor is switched on to supply with its capacitor replaced by an inductor of equivalent reactance value. It will?

Last Answer : A capacitor-start single phase induction motor is switched on to supply with its capacitor replaced by an inductor of equivalent reactance value. It will not start at all.

Description : The p.u. parameter for a 500 MVA machine on its own base are: inertia, M = 20 p.u. ; reactance, X = 2 p.u. The p.u. values of inertia and reactance on 100 MVA common base, respectively, are (A) 4, 0.4 (B) 100, 10 (C) 4, 10 (D) 100, 0.4

Last Answer : The p.u. parameter for a 500 MVA machine on its own base are: inertia, M = 20 p.u. ; reactance, X = 2 p.u. The p.u. values of inertia and reactance on 100 MVA common base, respectively, are 100, 0.4

Description : relay is preferred for phase fault on short transmission line. (a) Induction type (b) Reactance (c) Impedance (d) None of the above

Last Answer : (b) Reactance