A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is

(A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

1 Answer

Answer :

A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Related questions

Description : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he

Last Answer : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he 0.52

Description : Consider the following statements. Which of these statements are correct ?  (1) Reactance relays are preferred for ground fault relaying  (2) Impedance relays are most suitable for:protecting long transmission lines  (3) Mho relays are best ... (1) and (3) (C) (2) and (4) (D) (1), (2) and (4)

Last Answer : Consider the following statements. Which of these statements are correct ?  (1) Reactance relays are preferred for ground fault relaying  (2) Impedance relays are most suitable for:protecting long transmission lines  (3) Mho relays are ... (1) and (3) (C) (2) and (4) (D) (1), (2) and (4)

Description : A reactance relay is (A) Voltage restrained directional relay (B) Directional restrained over-current relay (C) Voltage restrained over current relay (D) Directional restrained over voltage relay

Last Answer : A reactance relay is Directional restrained over-current relay

Description : Ratio of the rotor reactance X to the rotor resistance R for a two-phase servo motor (A) is equal to that of a normal induction motor (B) is less than that of a normal induction motor (C) ... than that of a normal induction motor (D) may be less or greater than that of a normal induction motor

Last Answer : C

Description : A 1100 kVA, 11 kV/1.1 kV conventional two-winding transformer is connected as a 12.1 kV/11 kV step-down auto-transformer. The rating of the auto-transformer is (A) 1000 kVA (B) 1100 kVA (C) 11000 kVA (D) 12100 kVA

Last Answer : A 1100 kVA, 11 kV/1.1 kV conventional two-winding transformer is connected as a 12.1 kV/11 kV step-down auto-transformer. The rating of the auto-transformer is 12100 kVA

Description : Define impedance diagram and reactance diagram.

Last Answer : Impedance diagram: Impedance diagram is the simplified equivalent circuits of single line or one line diagrams of power system in which all components are represented by their equivalent circuit.  ... machines are neglected and is used only for fault current calculation is called reactance diagram.

Description : What do you mean by exciting resistance and exciting reactance?

Last Answer : At no-load, a transformer behaves as a highly inductive load connected to the system which contains some resistance and inductance in parallel. The resistance is called exciting resistance R0 = V1/I w and reactance is called exciting reactance, X0 = V1/I mag

Description : Capacitive reactance

Last Answer : Capacitive reactance formula

Description : Parallel Reactance and Resistance Example 1

Last Answer : Parallel Reactance and Resistance Example 1

Description : AC Circuits with Resistance but No Reactance

Last Answer : AC Circuits with Resistance but No Reactance AC Circuits with Resistance but No Reactance Series resistances let two resistances R 1 and R 2 are connected in series as shows in figure and there ... voltage. Voltage V A is common to both the branch hence voltage V A is common reference.

Description : If the % reactance upto the fault point is 20%, then the short circuit current will be

Last Answer : If the % reactance upto the fault point is 20%, then the short circuit current will be 5 times the full load current

Description : Reactance relay is normally preferred for protection against

Last Answer : Reactance relay is normally preferred for protection against earth faults

Description : Capacitive reactance is more when?

Last Answer : Capacitive reactance is more when capacitance is less and frequency of supply is less.

Description : What is the unit of reactance?

Last Answer : Unit of reactance is Ohms ( Ω ) .Reactance is denoted by X .

Description : What is the inverse of reactance?

Last Answer : Inverse of reactance is Susceptance .Unit of Susceptance is Siemens.

Description : what is the reciprocal of reactance?

Last Answer : reciprocal of reactance is susceptance.

Description : If an unsymmetrical line to ground fault occurs at the secondary terminals of a delta/star, ungrounded transformer, then  (A) zero sequence currents are present on both sides of the transformer  (B) ... side  (D) zero sequence currents are present on the primary side but not on the secondary side

Last Answer : If an unsymmetrical line to ground fault occurs at the secondary terminals of a delta/star, ungrounded transformer, then zero sequence currents are absent on both sides of the transformer 

Description : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be :  (A) 34.64 kVA (B) 75 kVA (C) 20 kVA (D) None of the above

Last Answer : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be : 34.64 kVA

Description : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is (A) 2/15 p.u. (B) 5/6 p.u. (C) 1.0 p.u. (D) 1.2 p.u.

Last Answer : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is 5/6 p.u.

Description : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

Last Answer : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is 0.01

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer : A. As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : What is the difference between delta-delta, delta-star transformer?

Last Answer : A. Delta-delta transformer is used at generating station or a receiving station for Change of Voltage (i,e) generally it is used where the Voltage is high & Current is low whereas Delta-star ... star neutral is taken as a return path and this configuration is used for Step down voltage phenomena.

Last Answer : Delta/star transformer works satisfactorily when on balanced as well as unbalanced loads.

Description : A capacitor-start single phase induction motor is switched on to supply with its capacitor replaced by an inductor of equivalent reactance value. It will?

Last Answer : A capacitor-start single phase induction motor is switched on to supply with its capacitor replaced by an inductor of equivalent reactance value. It will not start at all.

Description : A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

Last Answer : 543A

Description : 55 When a 400Hz transformer is operated at 50Hz its KVA rating is A. Reduced to 1/8 B. Increased 8 times C. Unaffected D. Increased 64 times

Last Answer : A. Reduced to 1/8

Description : 4] In operating a 400hz transformer at 50Hz A. Only voltage is reduced in the same proportion as the frequency B. Only KVA rating is reduced in the same proportion as the frequency C. Both voltage and KVA rating are reduced in the same proportion as frequency D. None of the above

Last Answer : B. Only KVA rating is reduced in the same proportion as the frequency

Description : The transformer ratings are usually expressed in terms of A. Volts B. Amperes C. kW D. kVA

Last Answer : D) KVA

Description : Why Transformer rating is given in kVA?

Last Answer : Because of core losses and iron losses as core losses are measured in amps and cu losses in voltage ....this is definatly reason for the rating Or kVA is the unit for apparent power. Apparent ... shift between voltage and current). So a transformer has to be rated (and selected) by apparent power.

Description : Define kVA rating of transformer.

Last Answer : kVA rating of transformer is defined as the product of voltage (V) and current (I) on primary side of transformer or secondary side of transformer divided by 1000. On both side the VA rating remains ... Mathematically kVA rating is given by, kVA rating of transformer = V1I1/1000 =V2I2/1000

Description : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is

Last Answer : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is 0.707

Description : Transformer generally rated in KVA

Last Answer : The power of transformer is apparent power because it has no power factor and it is the product of voltage and current.

Description : The voltage at the two ends of a transmission line are 132 KV and its reactance is 40 ohm. The Capacity of the line is (A) 435.6 MW (B) 217.8 MW (C) 251.5 MW (D) 500 MW

Last Answer : (A) 435.6 MW

Description : If voltage at the two ends of a transmission line is 132 kV and its reactance is 40 Ohms, the capacity of the line will be: (A) 435.6 MW (B) 217.8 MW(C) 251.5 MW (D) 500 MW

Last Answer : If voltage at the two ends of a transmission line is 132 kV and its reactance is 40 Ohms, the capacity of the line will be: 435.6 MW

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Last Answer : D. Loading of the transformers not in proportion to their kVA ratings

Description : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of   (a) 250A (b) 50 A (c) 150 A (d) 350 A 

Last Answer : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of 250A

Description : A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be   (a) 240 (b) 132 (c) 416 (d) 720

Last Answer : A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be 240 

Description : At full -load of a transformer, the iron loss and copper loss are 3000 W and 4000 W respectively. Then total loss at maximum efficiency is :  (A) 7000 W (B) 6000 W (C) 8000 W (D) 4000 W

Last Answer : At full -load of a transformer, the iron loss and copper loss are 3000 W and 4000 W respectively. Then total loss at maximum efficiency is : 6000 W

Description : The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

Last Answer : 3500

Description : How the leakage reactance of the transformer is reduced?

Last Answer : In transformers the leakage reactance is reduced by interleaving the high voltage and low voltage winding.

Description : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 ... load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

Last Answer : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/ ... MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be 36 

Description : 63 The dielectric strength of transformer oil is expected to be A. 1kV B. 33kV C. 100kV D. 330 kV

Last Answer : B. 33kv

Description : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

Last Answer : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is 1.316.

Description : The maximum possible power of a 3-phase synchronous motor with synchronous reactance 0.8 p.u. connected to a bus-bar of 1.0 p.u. and excitation adjusted to 1.2 p.u. is (A) 0.5 p.u. (B) 0.96 p.u. (C) 1.5 p.u. (D) 1.8 p.u.

Last Answer : The maximum possible power of a 3-phase synchronous motor with synchronous reactance 0.8 p.u. connected to a bus-bar of 1.0 p.u. and excitation adjusted to 1.2 p.u. is 1.5 p.u.

Description : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is: A) 300 kVA B) 75 kVA C) 259 kVA D) 249 kVA

Last Answer : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is:  259 kVA

Description : A transformer has negative voltage regulation when its load power factor is   (1) Zero (2) Unity (3) Leading (4) Lagging

Last Answer : 0

Description : If a 5-bus test system contains 6 transmission lines and one transformer, how many non-zero elements are there in the system Y-bus ? (A) 25 (B) 12 (C) 11 (D) 19

Last Answer : If a 5-bus test system contains 6 transmission lines and one transformer, 19 non-zero elements are there in the system Y-bus.

Description : Circuits with XL Alone

Last Answer : Circuits with XL Alone X L values in series let two inductive reactances X L 1 and X L 2 are connected in series and has value 50 ohm and 50 ohm respectively. 100 volts A C ... phasor. And it is taken horizontal. Phase angle between inductive current and voltage is same 90 degree.

Description : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of ... the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

Last Answer : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, ... line. The voltage of the alternator neutral with respect to ground during the fault is 642.2 V

Description : In a three phase transformer, if the primary side is connected in star and secondary side is connected in delta, what is the angle difference between phase voltage in the two cases. (A) delta side lags by -30°. (B) star side lags by -30°. (C) delta side leads by 30°. (D) star side leads by -30°.

Last Answer : Ans: C This is vector group and has +30° displacement. Therefore, delta side leads by +30°.