The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be : 

(A) 34.64 kVA (B) 75 kVA (C) 20 kVA (D) None of the above

1 Answer

Answer :

The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be : 34.64 kVA

How to solve this problem

Related questions

Description : Why Transformer rating is given in kVA?

Last Answer : Because of core losses and iron losses as core losses are measured in amps and cu losses in voltage ....this is definatly reason for the rating Or kVA is the unit for apparent power. Apparent ... shift between voltage and current). So a transformer has to be rated (and selected) by apparent power.

Description : Define kVA rating of transformer.

Last Answer : kVA rating of transformer is defined as the product of voltage (V) and current (I) on primary side of transformer or secondary side of transformer divided by 1000. On both side the VA rating remains ... Mathematically kVA rating is given by, kVA rating of transformer = V1I1/1000 =V2I2/1000

Description : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is

Last Answer : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is 0.707

Description : The rating of transformer may be expressed in ____________.  (A) kVAR (B) kW (C) kVA (D) Horse power

Last Answer : The rating of transformer may be expressed in kVA . 

Description : The speed of a three-phase induction motor is controlled by variable voltage variable frequency control (i.e. keeping V/f constant). As the frequency is reduced, the slip at maximum torque  (1) Decreases (2) Increases (3) Remains constant (4) None of the above

Last Answer : The speed of a three-phase induction motor is controlled by variable voltage variable frequency control (i.e. keeping V/f constant). As the frequency is reduced, the slip at maximum torque Increases 

Last Answer : The transformer ratings are usually expressed in terms of kVA.

Description : Why are generators rated in kVA not in kW ?

Last Answer : Because It's rating of generator kva is apparent power. Kw is active power which we use. And one is kvar reactive power.

Description : The apparent power drawn by an A.C. circuit is 10 kVA and active power is 8 kW. The reactive power in the circuit is?

Last Answer : The apparent power drawn by an A.C. circuit is 10 kVA and active power is 8 kW. The reactive power in the circuit is 6 kVAR.

Description : Step-down transformer converts high voltage and low current into:  (A) How voltage and high current (B) High voltage and low current (C) Low voltage and high current (D) None of the above

Last Answer : Step-down transformer converts high voltage and low current into: Low voltage and high current

Description : What is difference between KW and KVA?

Last Answer : kW is kilowatt and kVA is kilovolt ampere. kW is unit of real power and kVA is unit of Apparent power.

Description : What is meant by KVA?

Last Answer : KVA - kilo volt ampere  Used to specify the transformer details

Description : 4] In operating a 400hz transformer at 50Hz A. Only voltage is reduced in the same proportion as the frequency B. Only KVA rating is reduced in the same proportion as the frequency C. Both voltage and KVA rating are reduced in the same proportion as frequency D. None of the above

Last Answer : B. Only KVA rating is reduced in the same proportion as the frequency

Description : What is a capacitor voltage transformer? A) It is a transformer used in power systems to step up low voltage signals and provide extra high voltage B) It is a transformer used in power systems ... in power systems to step down extra high voltage signals and provide low voltage D) None of these

Last Answer : What is a capacitor voltage transformer? A) It is a transformer used in power systems to step up low voltage signals and provide extra high voltage B) It is a transformer used in power systems ... power systems to step down extra high voltage signals and provide low voltage D) None of these

Last Answer : yes High Voltage side of Transformer winding have more number of turns. and low voltage side of Transformer winding have less number of turns.

Description : Torque developed by a three-phase, 400V, induction motor is 100 N -m. If the applied voltage is reduced to 200-V, the d'veloped torque will be

Last Answer : Torque developed by a three-phase, 400V, induction motor is 100 N -m. If the applied voltage is reduced to 200-V, the d'veloped torque will be 25 N -m

Description : Transformer generally rated in KVA

Last Answer : The power of transformer is apparent power because it has no power factor and it is the product of voltage and current.

Description : A transformer has negative voltage regulation when its load power factor is   (1) Zero (2) Unity (3) Leading (4) Lagging

Last Answer : 0

Description : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are?

Last Answer : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are hysteresis and eddy current losses.

Description : A good voltage regulation of a transformer means?

Last Answer : A good voltage regulation of a transformer means output voltage fluctuation from no load to full load is least.

Description : The voltage transformation ratio of a transformer is equal to the ratio of?

Last Answer : The voltage transformation ratio of a transformer is equal to the ratio of secondary induced e.m.f. to primary induced e.m.f.

Description : If a transformer is switched on to a voltage more than the rated voltage?

Last Answer : If a transformer is switched on to a voltage more than the rated voltage its power factor will deteriorate.

Description : 47 Cross over windings are used in A. Low voltage side of high kVA rating transformers B. Current transformers C. High voltage side of high kVA rating transformers D. High voltage side of low kVA rating transformers

Last Answer : D. High voltage side of low kVA rating transformers

Description : 55 When a 400Hz transformer is operated at 50Hz its KVA rating is A. Reduced to 1/8 B. Increased 8 times C. Unaffected D. Increased 64 times

Last Answer : A. Reduced to 1/8

Description : How rating of main switch and cable is selected for Industrial Installation.

Last Answer : 1. Rating of Main Switch or Fuse Rating is decided in industrial installation: Rating of main switch or fuse is based up the starting current of motor. For calculating starting current is considered 2 ... take 1.5 times the rated current or full load current. & thus cable rating is decided.

Description : Boiler rating is usually defined in terms of  (1) Maximum temperature of steam in Kelvin (2) Heat transfer rate in KJ/hr (3) Heat transfer area in metre2 (4) Steam output in kg/hr

Last Answer : Boiler rating is usually defined in terms of Steam output in kg/hr

Last Answer : For the same H.P. rating and full load speed, following motor has poor starting torque differentially compounded.

Last Answer : The wattage rating for a ceiling fan motor will be in the range 50 to 150 W .

Last Answer : The fuse rating is expressed in terms of current.

Description : A 400 V, 50 Hz three-phase induction motor rotates at 1440 rpm on full -load. The motor is wound for

Last Answer : A 400 V, 50 Hz three-phase induction motor rotates at 1440 rpm on full -load. The motor is wound for 4 poles

Description : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that

Last Answer : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that the transformers should belong to the same vector group

Description : The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is (A) 0.745 lagging (B) 0.775 lagging (C) 0.8 lagging (D) 0.85 lagging

Last Answer : Vscos¢s-Vrcos¢r=IR

Last Answer : In case one phase of a three-phase synchronous motor is short-circuited the motor will not start.

Description : 4 Helical coils can be used on A. Low voltage side of high kVA transformers B. High frequency transformers C. High voltage side of small capacity transformers D. High voltage side of high kVA rating transformers

Last Answer : A) low voltage side of high KVA transformer

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : Can Transformers be Reconnected as Autotransformers to Increase Their KVA Rating?

Last Answer : ANSWER: Several of standard single phase transformers can be connected as autotransformers. The KVA capacity will be greatly increased when used as an Autotransformer, in comparison to the ... This voltage is normally used for operating fluorescent lamps or similar devices requiring 277 volts

Description : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Last Answer : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Description : The transformer ratings are usually expressed in terms of A. Volts B. Amperes C. kW D. kVA

Last Answer : D) KVA

Description : Where would you rate Ronald Reagan among US Presidents?

Last Answer : I think the “fat little dutchman” did good, made me laugh on numerous occasions.

Description : On a scale from 0 to 10, how do you rate the numbers in that scale?

Last Answer : 1: 1 2: 2 3: 3 4: 4 5: 7 6: 5 7: 6 8: 10 9: 8 10: 9

Description : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: A. 4 kVA B. 0.25 kVA C. 16 kVA D. 8 kVA

Last Answer : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: 16 kVA

Description : Define: 1) voltage ratio, 2) current ratio, 3) transformation ratio of transformer.

Last Answer : 1) Voltage ratio: The voltages in primary and secondary winding is proportional to number of turns in primary and secondary respectively. So, the voltage ratio is same as transformation ratio. V2/V1 = N2 ... as transformation ratio of transformer. It is denoted by K. K = N2/N1

Description : About trnsformer

Last Answer : Acc to Ohms law V=IR but it is only applicable when our resistance R is constant, as in case of transformer we take impedence which is equivalent to resistance is not constant it varies with system parameters that why Ohms law not applicable in case of transformer

Description : A transformer at 25 Hz develops 20 W hysteresis loss and 50 W eddy current loss. If the applied voltage and frequency are doubled, the new core losses are (A) 140 W (B) 180 W (C) 240 W (D) 480 W

Last Answer : A transformer at 25 Hz develops 20 W hysteresis loss and 50 W eddy current loss. If the applied voltage and frequency are doubled, the new core losses are 240 W

Description : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he

Last Answer : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he 0.52

Description : Write the relation between phase and line current, phase and line voltage for Star connection.

Last Answer : Line voltage is equal to root three times of phase voltage and line and phase currents are equal in star connection

Description : If 1-phase voltage is 220V, why is 3-phase 440V and not 660V ?

Last Answer : Phase voltage =220v /( phase to neutral) Line voltage = 380 v ( phase to phase) Phase angle difference 120° So when two phases reach vmax +ve I.e. (+220v) + (+220v) = 440v that time due ... these event happen very fast. Hence we have 440 v only in three phase motor. √3.phase voltage= 380 v.

Description : A 3-phase voltage source inverter operates in 180° conduction mode with a star connected resistive load. If input dc voltage is 100 V, then the peak to peak output line voltage is :

Last Answer : A 3-phase voltage source inverter operates in 180° conduction mode with a star connected resistive load. If input dc voltage is 100 V, then the peak to peak output line voltage is : 200 V

Description : A single core cable is designed to work for a single phase system with a peak voltage of 220 kV. The maximum permissible stress in the dielectric is not to exceed 20 kV/mm. For economical size, the overall core diameter of the cable is (A) 28.2 mm (B) 26.4 mm (C) 24.4 mm (D) 22.0 mm

Last Answer : A single core cable is designed to work for a single phase system with a peak voltage of 220 kV. The maximum permissible stress in the dielectric is not to exceed 20 kV/mm. For economical size, the overall core diameter of the cable is 22.0 mm

Description : At a particular instant, the R-phase voltage of a balanced 3-phase system is + 30 V, and the Y-phase voltage is – 90 V. The voltage of B-phase at that instant is (A) + 120 V (B) – 120 V (C) – 60 V (D) + 60 V

Last Answer : At a particular instant, the R-phase voltage of a balanced 3-phase system is + 30 V, and the Y-phase voltage is – 90 V. The voltage of B-phase at that instant is + 60 V

Description : In a tap changing transformer, the tappings are provided on (a) primary winding (b) secondary winding (c) high voltage winding (d) any of the above

Last Answer : (b) secondary winding