The voltage appearing across the contacts after opening of the circuit breaker is called______voltage. (a) recovery (b) surge (c) operating (d) arc (e) none of the above

1 Answer

Answer :

(a) recovery

Related questions

Last Answer : The voltage appearing across the contacts after opening of the circuit breaker is called recovery voltage.

Description : Arc in a circuit breaker is interrupted at (a) zero current (b) maximum current (c) minimum voltage (d) maximum voltage

Last Answer : (a) zero current

Description : The arc voltage produced in A.C. circuit breaker is always (a) in phase with the arc current (b) lagging the arc current by 90" (c) leading the arc current by 90° (d) none of the above

Last Answer : (a) in phase with the arc current

Description : Interruption of large currents by relay requires (a) arc suppressing blow out coils (b) wide separation of the opened contacts (c) high speed opening of contacts (d) all of the above

Last Answer : (d) all of the above

Description : What is recovery voltage in circuit breaker?

Last Answer : Recovery voltage in circuit breakers is defined as the power frequency rms voltage which appears across the breaker contacts after the transient oscillations die out and the final extinction of the arc ... poles of the circuit breaker. It is the voltage developed after the arc extinction is competed

Description : Arc in a circuit behaves as (a) a capackive reactance (b) an inductive reactance (c) a resistance increasing with voltage rise across the arc (d) a resistance decreasing with voltage rise across the arc

Last Answer : (d) a resistance decreasing with voltage rise across the arc

Description : The contacts of high voltage switches used in power system are submerged in oil. The main purpose of the oil is to (a) lubricate the contacts (b) insulate the contacts from switch body (c) extinguish the arc (d) all of the above (e) none of the above

Last Answer : (c) extinguish the arc

Description : Circuit breakers are essentially (a) current carrying contacts called electrodes (b) arc extinguishers (c) circuits to break the system (d) transformers to isolate the two systems (e) any of the above

Last Answer : (a) current carrying contacts called electrodes

Description : In a circuit breaker the basic problem is to (a) maintain the arc (b) extinguish the arc (c) transmit large power (d) emit the ionizing electrons

Last Answer : (c) transmit large power

Description : Which of the following medium is employed for extinction of arc in air circuit breaker ? (a) Water (b) Oil (c) Air (d) SF6

Last Answer : (c) Air

Description : The arcing contacts in a circuit breaker are made of (a) copper tungsten alloy (b) porcelain (c) electrolytic copper (d) aluminium alloy

Last Answer : (a) copper tungsten alloy

Description : Which of the following is the least expensive protection for overcurrent is low voltage system ? (a) Rewireable fuse (b) Isolator (c) Oil circuit breaker (d) Air break circuit breaker (e) None of the above

Last Answer : (a) Rewireable fuse

Description : Which of the following devices will receive voltage surge first travelling on the transmission line ? (a) Lightning arresters (b) Relays (c) Step-down transformer (d) Switchgear

Last Answer : (a) Lightning arresters

Description : With which of the following, a circuit breaker must be equipped for remote operation ? (a) Inverse time trip (b) Time-delay trip (c) Shunt trip (d) None of the above (e) All of the above

Last Answer : (c) Shunt trip

Description : In order that current should flow without causing excessive heating or voltage drop, the relay contacts should (a) have low contact resistance (b) be clean and smooth (c) be of sufficient size and proper shape (d) have all above properties

Last Answer : (d) have all above properties

Description : For an Resistive Load and Inductive load considered for switching operation of circuit breaker, Switching of which load is difficult and Why?

Last Answer : In case of switching resistive load, current and voltage will be in phase i.e,when during current zero voltage also will be zero in case of resistive load. Hence the voltage at the ... maximum. This results in re-striking of arc once again. Therefore switching inductive load will be difficult

Description : Why asymmetrical breaking current is higher than the symmetrical breaking current in a circuit breaker?

Last Answer : Asymmetrical breaking current is the rms value of the combined sum of the dc and ac components of the short circuit current at the instant of separation of the breaker contacts while ... the ac component alone. Thus asymmetrical breaking current is higher than the symmetrical breaking current.

Description : Which of the following circuit breakers has high reliability and minimum maintenance ? (a) Air blast circuit breakers (b) Circuit breaker with SF6 gas (c) Vacuum circuit breakers (d) Oil circuit breakers

Last Answer : (b) Circuit breaker with SF6 gas

Description : Ionization in circuit breaker is facilitated by (a) high temperature (b) increase of mean free path (c) increasing field strength (d) all of the above

Last Answer : (d) all of the above

Description : Burden of a protective relay is the power (a) required to operate the circuit breaker (b) absorbed by the circuit of relay (c) developed by the relay circuit (d) none of the above

Last Answer : (b) absorbed by the circuit of relay

Description : Air blast circuit breaker is used for (a) over currents (b) short duty (c) intermittant duty (d) repeated duty

Last Answer : (d) repeated duty

Description : Magnetic circuit breaker has ______ trip action. (a) delayed (b) instantaneous (c) both of the above (d) none of the above

Last Answer : (b) instantaneous

Description : Thermal circuit breaker has (a) delayed trip action (b) instantaneous trip action (c) both of the above (d) none of the above

Last Answer : (a) delayed trip action

Description : Overheating of relay contacts or contact born out is due to (a) slow making and breaking of load circuit contacts (b) foreign matter on the contact surface (c) too low contact pressure (d) all of the above

Last Answer : (d) all of the above

Description : What will be the reflection coefficient of the wave of load connected to transmission line if surge impedance of the line is equal to load ? (a) Zero (b) Unity (c) Infinity (d) None of the above

Last Answer : (a) Zero

Description : Which of the following statements is incorrect? (a) Station batteries are used to operate relay only (b) The lightning arresters are basically surge diverters (c) An impedance relay has maximum fault current when fault occurs near the relay (d) A high speed relay has an operation of 1 to 2 cycles

Last Answer : (a) Station batteries are used to operate relay only

Description : When does an arc extincts?

Last Answer : If the rate of rise of re-striking voltage (RRRV) is less than rate of rise of dielectric strength between the breaker contacts arc will not sustain and extincts

Description : Bus coupler is very essential in arrangement (a) single bus (b) double bus, double breaker (c) main and transfer bus (d) all of the above

Last Answer : (c) main and transfer bus

Description : The arc resulting from the tripping of a circuit breaker is prevented from damaging the contacts by _____________. A. designing the contacts to open slowly B. directing the arc into an ... an inverse timed thermal trip for short circuit currents D. instantaneous magnetic trip for overload currents

Last Answer : Answer: B

Description : The short circuit in any winding of the transformer is the result of (a) mechanical vibration (b) insulation failure (c) loose connection (d) impulse voltage

Last Answer : (d) impulse voltage

Description : Insulation resistance of high voltage circuit breakers is more than (a) 1 mega ohms (b) 10 mega ohms (c) 100 mega ohms (d) 500 mega ohms

Last Answer : (c) 100 mega ohms

Description : A thermal protection switch can protect against (a) short-circuit (b) temperature (c) overload (d) over voltage

Last Answer : (c) overload

Description : The relay operating speed depends upon (a) the spring tension (b) the rate of flux built up (c) armature core air gap (d) all of the above

Last Answer : (d) all of the above

Description : Circuit breakers usually operate under (a) transient state of short-circuit current (b) sub-transient state of short-circuit current (c) steady state of short-circuit current (d) after D.C. component has ceased

Last Answer : (a) transient state of short-circuit current

Description : Over voltage protection is recommended for (a) hydro-electric generators (b) steam turbine generators (c) gas turbine generators (d) all of the above (e) none of the above

Last Answer : (d) all of the above

Description : The under voltage relay can be used for (a) generators (b) busbars (c) transformers (d) motors (e) all of the above

Last Answer : (e) all of the above

Description : Relays can be designed to respond to changes in (a) resistance, reactance or impedance (b) voltage and current (c) light intensity (d) temperature (e) all above

Last Answer : (e) all above

Description : In the illustration, the purpose of part B is to _________. EL-0033 A. increase resistance in series with the contacts as they close to prevent arcing B. create a magnetic field in the steel ... event of an overload D. provide ventilation to the contact when the breaker is close to rated capacity

Last Answer : Answer: B

Description : transmission line has reflection coefficient as one. (a) Open circuit (b) Short-circuit (e) Long (d) None of the above

Last Answer : (a) Open circuit

Description : Short-circuit currents are due to (a) single phase to ground faults (b) phase to phase faults (c) two phase to ground faults (d) three phase faults (e) any of these

Last Answer : (e) any of these

Description : A.C. network analyser is used to solve problems of (a) load flow (b) load flow and short-circuit (c) load flow and stability (d) load flow, short-circuit and stability (e) none of the above

Last Answer : (d) load flow, short-circuit and stability

Description : The time of closing the cycle, in modern circuit breakers is (a) 0.003 sec (b) 0.001 sec (c) 0.01 sec (d) 0.10 sec (e) none of the above

Last Answer : (a) 0.003 sec

Description : The current zero interruption, in oil and air blast circuit breakers, is achieved by (a) lengthening of the gap (b) cooling and blast effect (c) both (a) and (b) (d) deionizing the oil with forced air (e) none of the above

Last Answer : (c) both (a) and (b)

Description : The main function of a fuse is to (a) protect the line (b) open the circuit (c) protect the appliance (d) prevent excessive currents (e) none of the above

Last Answer : (d) prevent excessive currents

Description : The arc voltage in a circuit breaker is :

Last Answer : The arc voltage in a circuit breaker is : in phase with the arc current

Last Answer : The arc voltage produced in A.C. circuit breaker is always in phase with the arc current.

Description : What is re-striking voltage?

Last Answer : The Re-striking voltage may be defined as the resultant transient voltage which appears across the breaker contacts at the instant of arc extinction

Description : Series capacitors are used to (a) compensate for line inductive reactance (b) compensate for line capacitive reactance (c) improve line voltage (d) none of the above

Last Answer : (a) compensate for line inductive reactance

Description : Induction cup relay is operated due to changes in (a) current (b) voltage (c) impedance (d) all of the above

Last Answer : (d) all of the above

Description : Resistance grounding is used for voltage between (a) 33kVto66kV (b) HkVto33kV (c) 3.3kVandllkV (d) none of the above

Last Answer : (c) 3.3kVandllkV