A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is 

(A) 50.0% (B) 70.7% (C) 141.4% (D) 200.0%

1 Answer

Answer :

A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is 70.7%

Related questions

Description : A single-phase, 50 kVA, 250 V/500 V two winding transformer has an efficiency of 95% at full load, unity power factor. If it is re-configured as a 500 V/750 V auto-transformer, its efficiency at its new rated load at unity power factor will be  (A) 95.752% (B) 97.851% (C) 98.276% (D) 99.241%

Last Answer : A

Description : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is

Last Answer : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is 0.707

Description : When two transformer of different kVA rating are connected in parallel they share the load in proportion to their respective kVA rating only when their:

Last Answer : When two transformer of different kVA rating are connected in parallel they share the load in proportion to their respective kVA rating only when their: P u impedance are equal

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Last Answer : D. Loading of the transformers not in proportion to their kVA ratings

Description : A 3-phase 50HZ SCIM takes a power input of 30 KW at its full load speed of 1440 rpm. Total stator losses are 1 KW. The slip and rotor ohmic losses at full load are a) 0.02, 600 W b) 0.04, 580 W c) 0.04, 1160 W d) 0.04, 1200 W

Last Answer : Ans: 0.04, 1160 W

Last Answer : The full-load copper loss of a trans¬former is 1600 W. At half-load, the copper loss will be 400 W.

Description : A 220/440 V, 50 Hz, 5 KVA, single phase transformer operates on 220V, 40Hz supply with secondary winding open circuited. Then (A) Both eddy current and hysteresis losses decreases. (B) Both ... same but hysteresis loss increases. (D) Eddy current loss increases but hysteresis loss remains the same.

Last Answer : (A) Both eddy current and hysteresis losses decreases.

Description :  A transformer has maximum efficiency at 3/4 full load. The ratio of its iron losses and full load copper loss is : -  a) 16/9 b) 4 / 3 c) 3/4 d) 9 /16

Last Answer :  A transformer has maximum efficiency at 3/4 full load. The ratio of its iron losses and full load copper loss is : -  9 /16

Description : Auto-transformer makes effective saving on copper and copper losses, when its transformation ratio is?

Last Answer : Auto-transformer makes effective saving on copper and copper losses, when its transformation ratio is approximately equal to 1.

Description : Which losses in a transformer varies significantly with load  a. Hysteresis losses b. Eddy current losses c. Copper losses d. Core losses 

Last Answer : Which losses in a transformer varies significantly with load Copper losses

Description : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are?

Last Answer : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are hysteresis and eddy current losses.

Description : The hysteresis and eddy current losses of a single phase transformer working on 200 V, 50 Hz supply are Ph and Pe respectively. The percentage decrease in these when operated on a 160 V, 40 Hz supply are   (a) 32, 36 (b) 20, 36 (c) 25, 50 (d) 40, 80 

Last Answer : The hysteresis and eddy current losses of a single phase transformer working on 200 V, 50 Hz supply are Ph and Pe respectively. The percentage decrease in these when operated on a 160 V, 40 Hz supply are 20, 36

Description : A single-phase transformer has no-load loss of 64 W, as obtained from an open circuit test. When a short-circuit test is performed on it with 90% of the rated currents flowing in its both LV and HV windings, ... .0% of the rated current (C) 80.0% of the rated current (D) 88.8% of the rated current

Last Answer : A single-phase transformer has no-load loss of 64 W, as obtained from an open circuit test. When a short-circuit test is performed on it with 90% of the rated currents flowing in its both ... measured loss is 81 W. The transformer has maximum efficiency when operated at 80.0% of the rated current

Description : A 50 KVA transformer has iron loss 2 kW on full load. Calculate its iron loss at 75% of full load.

Last Answer : Iron loss is dependent on voltage and independent of load. Hence iron loss at 75% of Load = Iron loss at full load = 2 kW

Description : One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

Last Answer : 100

Description : Full load copper loss in a transformer is 1600 watts. At half load the copper loss will be: A) 6400 watt B) 1600 watt C) 800 watt D) 400 watt

Last Answer :  Full load cupper loss in a transformer is 1600 watts. At half load the cupper loss will be: 400 watt

Description : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Last Answer : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Description : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is 500 kVA and its pu ... its pu leakage impedance is  (A) 0.20 (B) 0.10 (C) 0.05 (D) 0.025

Last Answer : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is ... .05 pu. If the rating of second transformer is 250 kVA, its pu leakage impedance is 0.10

Description : A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is  (A) 86.7% (B) 88.26% (C) 88.9% (D) 87.8%

Last Answer : A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is 87.8%

Description : In an actual transformer the iron loss remains practically constant from no load to full load because?

Last Answer : In an actual transformer the iron loss remains practically constant from no load to full load because core flux remains practically constant.

Description : At full -load of a transformer, the iron loss and copper loss are 3000 W and 4000 W respectively. Then total loss at maximum efficiency is :  (A) 7000 W (B) 6000 W (C) 8000 W (D) 4000 W

Last Answer : At full -load of a transformer, the iron loss and copper loss are 3000 W and 4000 W respectively. Then total loss at maximum efficiency is : 6000 W

Description : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is: A) 300 kVA B) 75 kVA C) 259 kVA D) 249 kVA

Last Answer : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is:  259 kVA

Description : A single-phase transformer has a turns ratio of 1 :2 and is connected to a purely resistive load as shown in the figure. The magnetizing current drawn is 1A, and the secondary current is 1A. Ifcore losses and ... reactances are neglected, the primary current is  A)1.41A B)2A C) 2.24A D)3A

Last Answer : A single-phase transformer has a turns ratio of 1 :2 and is connected to a purely resistive load as shown in the figure. The magnetizing current drawn is 1A, and the secondary current is 1A. Ifcore losses and leakage reactances are neglected, the primary current is 2.24A

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : Reduction in core losses and increase in permeability are obtained with transformer employing?

Last Answer : Reduction in core losses and increase in permeability are obtained with transformer employing core built-up of laminations of cold rolled grain oriented steel.

Description : 42 The efficiency of a transformer will be maximum when A. copper losses = hysteresis losses B. Hysteresis losses = eddy current losses C. Eddy current losses = copper losses D. Copper losses = iron losses

Last Answer : D. Copper losses = iron losses

Description : To pump water from a water reservoir 3 m deep and maximum water level at 135 m, a pump is  installed to lift water up to R.L. 175 m at a constant rate of 36,00,000 litres per hour. If the length  of the ... the water horse power of the pump is  (A) 400  (B) 450  (C) 500 (D) 600

Last Answer : (D) 600

Description : [23] Transformers are rated in KVA instead of KW because A. load power factor is often not known B. KVA is fixed whereas KW depends on load power factor C. Total transformer loss depends on volt ampere D. It has become customary

Last Answer : C. Total transformer loss depends on volt ampere

Description : KVA of an Auto-transformer of V1/V2 = 220/150 for a load of 100KVA is: a. 100KVA b. 50KVA c. 33.3KVA d. 20KVA 

Last Answer : KVA of an Auto-transformer of V1/V2 = 220/150 for a load of 100KVA is: a. 100KVA b. 50KVA c. 33.3KVA d. 20KVA 

Description : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: A. 4 kVA B. 0.25 kVA C. 16 kVA D. 8 kVA

Last Answer : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: 16 kVA

Description : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be :  (A) 34.64 kVA (B) 75 kVA (C) 20 kVA (D) None of the above

Last Answer : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be : 34.64 kVA

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: (A) both the eddy current and the hysteresis losses will decrease ... losses will increase (D) eddy current losses will increase but the hysteresis losses will remain the same

Last Answer : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: both the eddy current and the hysteresis losses will decrease

Description : A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

Last Answer : 543A

Description : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of   (a) 250A (b) 50 A (c) 150 A (d) 350 A 

Last Answer : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of 250A

Description : During short circuit test iron losses are negligible because?

Last Answer : During short circuit test iron losses are negligible because the voltage applied on primary side is low.

Description : In a transformer, zero voltage regulation at full load is   (a)Not possible   (b) Possible at unity power factor load   (c) Possible at leading power factor load   (d) Possible at lagging power factor load

Last Answer : In a transformer, zero voltage regulation at full load is Possible at leading power factor load 

Description :  The no-load current drawn by transformer is usually what per cent of the full-load current ?

Last Answer : 5 to 8 percentage of full load current

Description : The rotor power output of a 3-phase induction motor is 15 KW and corresponding slip is 4%. The rotor copper loss will be (A) 600 W. (B) 625 W (C) 650 W (D) 700 W

Last Answer : Ans: B Rotor copper losses = rotor input- rotor output and output = (1-s) input ∴ Input = output/(1-s) = 15000 /1-0.04 = 15625 ∴ loss = 15625 -1500 = 625 watt

Description : Minimum excretory urinary volume for waste products elimination during 24 hrs is (A) 200–300 ml (B) 200–400 ml (C) 500–600 ml (D) 800 ml

Last Answer : Answer : C

Description : Insensible loss of body water of normal adult is about (A) 50–100 ml (B) 100–200 ml (C) 300–500 ml (D) 600–1000 ml

Last Answer : Answer : D

Description : In glycinuria daily urinary excretion of glycine ranges from (A) 100–200 mg (B) 300–500 mg (C) 600–1000 mg (D) 1100–1400 mg

Last Answer : Answer : C

Description : In glycoproteins the carbohydrate is in the form of disaccharide units, the number of units are (A) 50–100 (B) 200–300 (C) 400–500 (D) 600–700

Last Answer : Answer : D

Description : Amylose contains glucose units (A) 100–200 (B) 200–300 (C) 300–400 (D) 500–600

Last Answer : C

Description : The round-trip propagation delay between two earth stations through a geosynchronous satellite is A. 500 to 600 ms B. 300 to 400 ms C. 600 to 700 ms D. 400 to 500 ms

Last Answer : A. 500 to 600 ms

Description : Total capacitance of 300 mF capacitor and a 600 mF in series isA. 300 mF B. 500 mF C. 200 mF D. 1000 mF

Last Answer : 200 mF

Description : How much cloves of garlic is required for one hectare (a) 400 kg (b) 500 kg (c) 600 kg (d) 300 kg

Last Answer : (a) 400 kg

Description : Maximum root zone depth for Maize (a) 200-300 mm (b) 400-600 mm (c) 500-600 mm (d) 350- 450 mm

Last Answer : (b) 400-600 mm

Description : Number of meiotic divisions required to produce 200/400 seeds of pea would be (a) 200/400 (b) 400/800 (c) 300/600 (d) 250/500

Last Answer : (d) 250/500.