The driving power from the prime-mover driving the alternator is lost but the alternator remains connected to the supply network; the field supply also remains on. The alternator will:

A) get burnt B) behave as an induction motor but will rotate in the opposite direction C) behave as a synchronous motor and will rotate in the same direction D) behave as a synchronous motor but will rotate in a reverse direction to that corresponding to generator action 

1 Answer

Answer :

The driving power from the prime-mover driving the alternator is lost but the alternator remains connected to the supply network; the field supply also remains on. The alternator will: behave as a synchronous motor and will rotate in the same direction

Related questions

Description : In the illustration, the signal from the device connected to terminals 18 and 19 is __________. EL-0046 A. prime mover speed feedback B. loss of control alarm when comparing with the input signal ... slip between the prime mover and the alternator D. to shut down the prime mover if overspeeding

Last Answer : Answer: A

Description : If the energy input is significantly reduced to the prime mover of one shipboard alternator operating in parallel with others, that alternator will _____________. A. continue to operate at no load B. lose ... overspeed C. begin to motorize and then trip out D. slow down and operate at reduced load

Last Answer : Answer: C

Description : The standard method of controlling the output voltage of a 440 volt, 60 Hz, AC generator is accomplished by adjusting the ____________. A. prime mover speed droop B. number of poles C. alternator field excitation D. load on the alternator

Last Answer : Answer: C

Description : The frequency of an AC generator is adjusted by means of the ____________. A. main alternator field rheostat B. exciter field rheostat C. prime mover governor control D. equalizing reactor

Last Answer : Answer: C

Description : The output voltage of a 440 volt, 60 Hz AC generator is controlled by the ______________. A. load on the alternator B. load on the prime mover C. speed of the prime mover D. exciter output voltage

Last Answer : Answer: D

Description : The output voltage of a 440 volt, 60 hertz, AC generator is controlled by the _____________. A. prime mover speed B. exciter output voltage C. load on the alternator D. number of poles

Last Answer : Answer: B

Description : What happens if speed of prime mover is changed keeping excitation of alternator constant?

Last Answer : If speed of prime mover is changed, the speed of alternator also changes hence frequency also changes. The frequency increase with increase in steam input and hence speed and vise versa.

Description : What happens if excitation of alternator is changed keeping speed of prime mover constant?

Last Answer : The emf induced will be changed and hence terminal voltage will also change. The terminal voltage will increase with increase in excitation and vise versa.

Description : What type of prime mover requires a specially designed high-speed alternator?

Last Answer : Steam turbine.

Description : In the illustrated electronic governor, the circuit card connected to the potential and current transformers is for ________. EL-0046 A. increasing the signal strength to the governor to ... from motorization D. conditioning the load through the use of a magnetic amplifier current transformer

Last Answer : Answer: A

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description :  An 8-pole alternator runs at 750 rpm and supplies power to a 6-pole induction motor which has a full load slip of 3 percent. The full load speed of the induction motor will be: A) 1000 rpm B) 920 rpm C) 950 rpm D) 970 rpm

Last Answer : An 8-pole alternator runs at 750 rpm and supplies power to a 6-pole induction motor which has a full load slip of 3 percent. The full load speed of the induction motor will be: 970 rpm

Description : At which power factor alternator is said to be overexcited?

Last Answer : At leading power factor alternator is said to be overexcited.

Description : The power factor of an alternator depends on?

Last Answer : The power factor of an alternator depends on load.

Description : In an alternator at lagging power factor the generated voltage per phase as compared to that at unity power factor?

Last Answer : In an alternator, at lagging power factor the generated voltage per phase as compared to that at unity power factor must be more than terminal voltage.

Description : State working principle of alternator. State the meaning self and separate excitation. 

Last Answer : Working principle of alternator: When a conductor is moved in magnetic field or a magnetic field moved with respect to conductor, according to Faraday's law of electromagnetic induction, the conductor ... like battery or shaft-mounted exciter, then the excitation is said to be separate excitation.

Description : Explain the construction of alternator with neat diagram.

Last Answer : Diagram: Construction of three phase alternator: Construction wise, an alternator generally consists of field poles placed on the rotating fixture of the machine i.e. rotor as shown in the ... of rotor used in construction of alternator, 1. Salient pole type. 2. Cylindrical rotor type. 

Description :  In an alternator if the winding is short pitched by 60 electrical degrees, its pitch factor will be: A) 1.0 B) 0.866 C) 0.75 D) 0.50

Last Answer :  In an alternator if the winding is short pitched by 60 electrical degrees, its pitch factor will be: A) 1.0 B) 0.866 C) 0.75 D) 0.50

Description : Which alternator will have more number of poles ? (a) coupled to steam turbine (b) coupled to gas turbine (c) coupled to hydraulic turbine (d) None of the above 

Last Answer : b

Description : If the excitation of an alternator operating in parallel with other alternators decreased, its: (1) Power factor becomes more leading (2) Output Kw will change (3) Power factor becomes more lagging (4) Power factor becomes unity

Last Answer : If the excitation of an alternator operating in parallel with other alternators decreased, its: Power factor becomes more leading

Description : Drop in alternator frequency is corrected by: (1) Damper winding (2) Increased prime mover output (3) Automatic voltage regulator (4) None of these

Last Answer : Drop in alternator frequency is corrected by: Increased prime mover output

Description : A field excitation of 20 A in a certain alternator results in an armature current of 400 A in short circuit and a terminal voltage of 2000 V on open circuit. The magnitude of the internal voltage drop within the machine at a load current of 200 A is  (A) 1 V (B) 10 V (C) 100 V (D) 1000 V

Last Answer : 800

Description : A 8 pole alternator rotates at 750 r.p.m. Its frequency is

Last Answer : A 8 pole alternator rotates at 750 r.p.m. Its frequency is 50 Hz

Description : A 60 Hz, 2 pole alternator should run at • a. 3000 r.p.m. c. 1500 r.p.m. • b. 3600 r.p.m. d. 1800 r.p.m.

Last Answer : A 60 Hz, 2 pole alternator should run at 3600 r.p.m.

Description : Is the speed of alternator is directly proportional to frequency?

Last Answer : Yes, speed of alternator is directly proportional to frequency.

Description : The magnitude of various voltage drops that occur in an alternator depends on?

Last Answer : The magnitude of various voltage drops that occur in an alternator depends on load current.

Description : In alternator where the voltage drop occurs?

Last Answer : In alternator voltage drop occurs in armature resistance, leakage reactance, and armature reactance.

Description : The division of the kilowatt load between two AC generators operating in parallel is controlled by the settings and characteristics of the _____________. A. voltage regulators B. field rheostats C. reverse power relays D. prime mover governors

Last Answer : Answer: D

Description : A constant output voltage from an AC generator is maintained by the _____________. A. prime mover governor B. exciter generator C. voltage regulator D. reverse power relay

Last Answer : Answer: C

Description : The power developed in prime mover of power operated sprayer is a) 1 to 5 HP b) 5 to 10 HP c) 10 to 20 HP d) None of the above

Last Answer : 1 to 5 HP

Description : is the prime mover in which the direction of travel and its control for field operation is performed by the operator walking behind it. A. Power tiller C. Tillage B. Disc plough D. Rotary tiller

Last Answer : Power tiller

Description : Two 3-phase, Y-connected alternators are to be paralleled to a set of common busbars. The armature has a per phase synchronous reactance of 1.7 Ohm and negligible armature resistance. The line voltage of the first machine is adjusted to ... will be  (A) 16.98 A (B) 29.41 A (C) 33.96 A (D) 58.82 A

Last Answer : Two 3-phase, Y-connected alternators are to be paralleled to a set of common busbars. The armature has a per phase synchronous reactance of 1.7 Ohm and negligible armature resistance. The ... instant they are paralleled. Under this condition, the synchronizing current per phase will be 16.98 A

Description : The division of the reactive KVA load between paralleled AC generators is initiated by the ______________. A. prime mover governors B. voltage regulators C. phase balance relay D. proportioner

Last Answer : Answer: B

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : The prime mover of an AC two pole main propulsion generator drives the generator at 3600 RPM. If the main propulsion motor has 80 poles, what will be the propeller speed? A. 45 RPM B. 80 RPM C. 90 RPM D. 180 RPM

Last Answer : Answer: C

Description : Which of the methods listed is used to start a AC generator turning? A. Residual magnetism remaining in the field poles. B. Residual magnetism remaining in the field coils. C. Residual magnetism remaining in the armature. D. Rotation by a mechanical prime mover.

Last Answer : Answer: D

Description : On electrical generators one of the bearings is isolated from the bedplate. This insulating block should not be painted and must be kept clean to ___________. A. protect operating personnel from shock ... the prime mover as it warms up D. eliminate shaft currents to prevent damaging the bearings

Last Answer : Answer: D

Description : If the bearings of an electrical generator are failing more frequently than expected and the lubricating oil is sludging then you should ______________. A. check the connections to the output leads B. ... replace the bearing with a sealed roller type D. replace the thrust bearing of the prime mover

Last Answer : Answer: B

Description : If air gap readings for an electical generating machine have changed significantly from the last reading, you should check _________. A. the bearings B. insulation readings and machine cleanliness C. the prime mover thrust bearing D. the field coil bolts for the proper torque values

Last Answer : Answer: A

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : The voltage developed by an AC generator is controlled by varying the ____________. A. speed of the prime mover B. AC excitation to the field C. DC excitation to the field D. DC excitation of the voltage regulator

Last Answer : Answer: C

Description : Automatic voltage regulators provided on switchboards function to _____________. A. regulate the AC load on the generator B. protect the switchboard from high voltage C. govern prime mover speed to control voltage D. vary the field excitation to the generators

Last Answer : Answer: D

Description : The voltage output of an AC generator is accurately controlled by _____________. A. changing the sensitivity of the prime mover to large changes in voltage B. varying the reluctance of the air gap C. varying the DC exciter voltage D. shorting out part of the armature windings

Last Answer : Answer: C

Description : To increase the frequency of an operating AC generator, you should ____________. A. increase the field excitation B. decrease the field excitation C. increase the number of magnetic poles D. increase the speed of the prime mover

Last Answer : Answer: D

Description : Prior to starting an AC generator prime mover, the voltage regulator cutout switch should be placed in the __________. A. manual position B. bus neutral position C. raise voltage position D. transfer position

Last Answer : Answer: A

Description : As load is added to an AC generator provided with constant field excitation, the prime mover slows down with the effect of ____________. A. lowering frequency and lowering generated ... C. increasing frequency and lowering generated voltage D. lowering frequency and increasing generated voltage

Last Answer : Answer: A