Which type of protection is provided on a generator to protect against stator insulation failure? A) Differential protection B) Overcurrent relay C) Thermocouple actuated alarm D) Reverse power relay

1 Answer

Answer :

Which type of protection is provided on a generator to protect against stator insulation failure? A) Differential protection B) Overcurrent relay C) Thermocouple actuated alarm D) Reverse power relay 

Related questions

Last Answer : A thermal protection switch can protect against overload.

Description : Why 100% winding protection is felt essential for main generator stator E/F protection? (Used in NAPS onwards?)  

Last Answer : At MAPS 4% of winding is not protected. Earlier felt that the Electro magnetic stress due high external fault currents near 4% of neutral may not be high to cause E/F here. But now felt that the mechanical stress can leads to E/F. 

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Last Answer : Discrimination between main and back up protection is provided by the use of relays which are slow.

Description : Unnecessary and frequent applications of varnish to the generator windings to repair defective insulation will result in ____________. A. heavy coatings of varnish interfering with heat dissipation B. ... of the rectifier assembly D. a built-up of varnish without changing generator operation

Last Answer : Answer: A

Description : To protect the power transformer (Y-Y with neutral grounded) against fault, what type of connection do the CTs have ?

Last Answer : To protect the power transformer (Y-Y with neutral grounded) against fault, what type of connection do the CTs have ? Δ-Δ connection

Description : What type of insulation is done for stator bars?

Last Answer : Bar insulation is done with epoxy mica thermosetting insulation. This insulation is void free and possesses better mechanical properties. This insulation is more reliable for higher voltages. Conductors are ... After curing the insulation the epoxy resin (glue) fill all voids in the insulation. 

Description : IDMT relays are used to protect the transformer against :  (A) Internal short -circuits (B) Open circuits (C) External short circuits (D) Oil leakage

Last Answer : IDMT relays are used to protect the transformer against : External short circuits

Last Answer : Thermal overload relays are used to protect the motor against overcurrent due to heavy loads.

Description : A relay used for protection of motors against overload is :  (A) Impedance relay (B) Electromagnetic attraction type (C) Thermal relay (D) Buchholz's relay

Last Answer : D

Description : For protection of rotating machines against lightning surges _______ is used.  (1) lightning arrester (2) capacitor (3) combination of lightning arrester and capacitor (4) lightning conductor and arrester

Last Answer : For protection of rotating machines against lightning surges combination of lightning arrester and capacitor is used. 

Description : Reactance relay is normally preferred for protection against

Last Answer : Reactance relay is normally preferred for protection against earth faults

Description : Surge absorbers are used for protection against

Last Answer : Surge absorbers are used for protection against low voltage high frequency oscillations

Last Answer : A fuse in a motor circuit provides protection against short-circuit and overload.

Last Answer : The inverse definite mean time relays are used for over current and earth fault protection of transformer against internal short-circuits.

Last Answer : For the protection of power station buildings against direct strokes the requirements are interception, conduction and dissipation.

Last Answer : H.R.C. fuses provide best protection against short-circuits.

Description : Ungrounded neutral transmission system is not recommended because of system (a) insulation being overstressed due to over voltages (b) insulation overstress may lead to failure and subsequent phase to phase faults (c) being inadequately protected against ground fault (d) all of the above

Last Answer : (d) all of the above

Description : Where automatic restart does not present a hazard after a power failure, Coast Guard Regulations (46 CFR) require motor controllers for auxiliaries vital to the propelling equipment to be provided ... overload protection B. low voltage protection C. low voltage release D. reverse current protection

Last Answer : Answer: C

Description : Automatic voltage regulators provided on switchboards function to _____________. A. regulate the AC load on the generator B. protect the switchboard from high voltage C. govern prime mover speed to control voltage D. vary the field excitation to the generators

Last Answer : Answer: D

Description : Why main generator/UT is not provided with separate overfluxing protection?

Last Answer : Since GT is provided with overfluxing protection, it is adequate to protect main generator / UT also. Main generator can withstand higher degree of overfluxing. If a generator CB is used, separate overfluxing protection is essential for main generator. 

Description : Why inter-turn protection is provided along with differential protection in generator?

Last Answer : Inter-turn protects two separate windings from the fault of the generator.  

Description : What types of threats can virus protection protect against?

Last Answer : Virus protection software can protect against viruses that are known. New viruses that haven't been updated in the system yet may still slip through the software. To prevent this update your protection frequently and get software that can eliminate viruses as well.

Description : A thermal protection switch can protect against (a) short-circuit (b) temperature (c) overload (d) over voltage

Last Answer : (c) overload

Description : Angiotensin converting enzyme inhibitors afford maximum protection against progression of heart failure when used: A. At the higher therapeutic dose range over long term B. At the maximum tolerated dose only till ... restored C. At low doses over long term D. At low doses along with diuretics/digoxi

Last Answer : A. At the higher therapeutic dose range over long term

Description : Define the term “Insulation co-ordination”.

Last Answer : Insulation Co-ordination : It is the correlation of the insulation of electrical equipment and the lines with the characteristics of protective devices such that the insulation of the whole power system is protected from the excessive over voltages.

Last Answer : Insulation resistance of high voltage circuit breakers is more than 100 mega ohms.

Description : What causes stator failure?

Last Answer : Stator faliur due to moistur. Due to priodically heatup of winding.

Description : Biological shield in a nuclear reactor is generally provided to protect against the (A) α-rays (B) β-rays (C) Gamma rays & neutrons (D) Electrons

Last Answer : Option C

Description : Earth wire on EHV overhead transmission line is provided to protect the line against:

Last Answer : Earth wire on EHV overhead transmission line is provided to protect the line against: lightening surge

Description : Voltage build up in an isolated induction generator depends on A. Capacitor bank value B. Residual magnetism of the rotor iron C. Residual magnetism of the stator iron a) A, B b) A, B, C c) B d) A, C

Last Answer : Ans: A

Description : A DC generator is used to supply direct current in order to maintain an AC generator field and is known as a/an _____________. A. rotor B. stator C. exciter D. armature

Last Answer : Answer: C

Description : The amount of voltage induced in the windings of an AC generator depends mainly on _____________. A. the number of field poles energized B. the speed at which the stator windings rotate through the magnetic field C. the strength of the magnetic field D. all of the above

Last Answer : Answer: C

Description : Which of the listed devices may be installed on a large diesel-electric alternating current propulsion generator? A. Temperature detector coils inserted in the stator slots for measuring stator temperature. B. ... . C. Electric space heaters to prevent condensation of moisture. D. All of the above.

Last Answer : Answer: D

Description : Which of the listed devices may be installed on a large turbo-electric alternating current propulsion generator? A. Temperature detector coils inserted in the stator slots for measuring stator temperature. B. A ... . C. Electric space heaters to prevent condensation of moisture. D. All of the above.

Last Answer : Answer: D

Description : What is the generator IR value when generator is filled with stator water and hydrogen?  

Last Answer : Generator IR when filled with stator water and hydrogen is about 100 kΩ only. That is because most of the gases and liquids are self-restoring insulators. As we are measuring insulation with 1 kV or 5 kV ... region moderate voltage (1 kV to 70 kV), and breakdown region is above 70 kV voltage.  

Description : Why generator stator having alternate arrangements of hollow and solid conductor?  

Last Answer : It ensures an optimum solution for increasing current and to reduce losses.  

Description : Why oil cannot be used instead of water in generator stator?

Last Answer : Oil has high thermal capacity than gas, but low thermal capacity than water. Ability to absorb heat is also less than waters. High viscosity of oil causes linear flow and poor surface heat transfer in small ducts. Large pumping power required. 

Description : How are the generator rotor and stator cooled?  

Last Answer : Passing highly DM water through the hollow conductor of the generator cools generator stator and rotor is cooled by hydrogen. 

Description : A _______ is used to measure the stator % winding temperature of the generator. (a) thermocouple (b) pyrometer (c) resistance thermometer (d) thermometer

Last Answer : (c) resistance thermometer

Description : A _________ is used to measure the stator % winding temperature of the generator.  (A) Thermocouple (B) Pyrometer (C) Resistance thermometer (D) Thermometer

Last Answer : A Resistance thermometer is used to measure the stator % winding temperature of the generator. 

Description : The type of backup protection scheme widely used in the field is (A) Relay backup (B) Breaker backup (C) Remote backup (D) Auxiliary backup

Last Answer : The type of backup protection scheme widely used in the field is Remote backup 

Description : Protection against sustained overloads occurring in molded-case circuit breakers is provided by a/an __________. A. overvoltage release B. thermal acting trip C. thermal overload relay D. current overload relay

Last Answer : Answer: B

Description : A harbour is a place where (A) Ships get shelter and protection against destructive forces due to sea waves (B) Facilities are provided for receiving cargo and passengers (C) Port buildings are constructed for commercial purposes (D) All the above

Last Answer : (D) All the above

Description : Routine maintenance of dry-type transformers should include ____________. A. cleaning the windings, if accessible, with a vacuum cleaner or very low pressure air B. measuring and recording the winding ... . making sure that the units are close to bulkheads or corners to protect them from damage

Last Answer : Answer: A

Description : Why and where the magnetic filter is provided in stator water circuit?

Last Answer : Magnetic filter is provided to catch the metal particles in stator water circuit, which are produced in the pipelines. This is mounted at the end of the circuit nearer to the inlet of the generator. 

Description : A circuit breaker is designed to protect an electrical circuit from damage caused by :  (A) Over load (B) Short circuit (C) Over current (D) All of the above

Last Answer : A circuit breaker is designed to protect an electrical circuit from damage caused by :  (A) Over load (B) Short circuit (C) Over current (D) All of the above

Last Answer : To protect most of the electrical equipment handling low power, the types of relays used are thermocouple, electronic and bimetallic.

Description : Explain the “Differential Protection Scheme” used for alternators with neat labeled diagram.

Last Answer : Differential Protection Scheme for Alternator: Figure shows the differential protection provided to 3 phase alternator. Here identical CTs are placed on both sides of 3 phase alternator and ... causing its operation. Relay sends trip signal to the CB, thereby alternator circuit is tripped.

Description : Explain with neat sketch, the Pilot wire protection scheme applied to transmission line.

Last Answer : Pilot Wire Protection scheme of Transmission Line : Figure shows the single line diagram of Merz price voltage balance system for pilot wire protection of three phase transmission line. ... through the relay, which gives trip signal to the circuit breaker for protection of transmission line.