If we have 30kva, 250 kva, 300kva d.g set than how many earthing we do? 

2 Answers

Answer :

According to Indian Std. DG Set Should have four Earthing 

Pits Each Should have Separate Copper Plate Accoring to Std.

-Run two properly sized Copper or GI Earthing Conductors 

from the Neutral Bushing/Terminal of the DG Set's 

Alternator and connect one each to the two neutral earth 

pits. Similarly, the alternator will have two earthing 

terminal on its body (at diagonally opposite ends); Run two 

properly sized Copper or GI Earthing Conductors from these 

body earthing terminals of the DG Set's Alternator and 

connect one each to the two body earth pits. But, you MUST 

inter-connect all these four (two neutral and the two body) 

earth pits by properly sized Copper or GI Earthing 

Conductor.

Answer :

We should have two distinct earthing for neautral earthing and two for Body earthing.To achieve minimal resistance neautral earthpit should be connected in parallel.similarly body earthing too.

Related questions

Description : A 8-pole, DC generator has a simplex wave-wound armature containing 32 coils of 6 turns each. Its flux per pole is 0.06 Wb. The machine is running at 250 rpm. The induced armature voltage is  (A) 96 V (B) 192 V (C) 384 V (D) 768 V

Last Answer : A 8-pole, DC generator has a simplex wave-wound armature containing 32 coils of 6 turns each. Its flux per pole is 0.06 Wb. The machine is running at 250 rpm. The induced armature voltage is 384 V

Description : The voltage built-up process of a d.c. generator is  1. difficult 2. delayed 3. cumulative 4. Infinite 

Last Answer : The voltage built-up process of a d.c. generator is cumulative 

Description : for the voltage built-up a self-excited D.C. generator, which of the following is not an essential condition.  1.there must be some residual flux  2.field winding mmf must aid the residual ... 3.total field circuit resistance must be less than t critical value  4.armature speed must be very high

Last Answer : for the voltage built-up a self-excited D.C. generator, which of the following is not an essential condition.  1.there must be some residual flux  2.field winding mmf must aid the ... .total field circuit resistance must be less than t critical value  4.armature speed must be very high

Description : The slight curvature at the lower end of the O.C.C. of a self-excited dc generator is due to  1. residual pole flux 2. high armature speed 3.magnetic inertia 4. high field circuit resistance

Last Answer : The slight curvature at the lower end of the O.C.C. of a self-excited dc generator is due to magnetic inertia

Description : In a DC shunt generator working on load, the brushes are moved forward in the direction of rotation, as a result of this, commutation will   (a) Improve but terminal voltage will fall   (b) ... will fall   (c) Improve and terminal voltage will rise   (d) worsen and terminal voltage will rise 

Last Answer : In a DC shunt generator working on load, the brushes are moved forward in the direction of rotation, as a result of this, commutation will Improve but terminal voltage will fall 

Description : The terminal voltage of a DC shunt generator drops on load because of all of the following except : (A) Armature reaction (B) Armature resistance drop (C) Commutation (D) Field weakening due to armature reaction and armature resistance drop

Last Answer : (D) Field weakening due to armature reaction and armature resistance drop

Last Answer : The critical resistance of the D.C. generator is the resistance of field.

Last Answer : Armature reaction in a generator results in demagnetisation of leading pole tip and magnetisation of trailing pole tip.

Description : If residual magnetism is present in a D.C. generator, the induced e.m.f. at zero speed will be?

Last Answer : If residual magnetism is present in a D.C. generator, the induced e.m.f. at zero speed will be zero.

Last Answer : In a separately excited generator supplying rated load the armature reaction is always present.

Last Answer : A 220 V D.C. generator is run at full speed without any excitation. The open circuit voltage will be about 2 V.

Description : A sinusoidal voltage of 5 Hz is applied to the field of a shunt generator. The armature voltage wave?

Last Answer : A sinusoidal voltage of 5 Hz is applied to the field of a shunt generator. The armature voltage wave will be of 5 Hz.

Last Answer : In a level compounded D.C. generator, full load terminal voltage is equal to no-load terminal voltage.

Last Answer : In over compounded generator, full load terminal voltage is more than no load terminal voltage.

Last Answer : In case of a flat compounded generator voltage remains constant irrespective of the load.

Last Answer : An exciter for a turbo generator is a shunt generator.

Last Answer : In a D.C. generator in case the resistance of the field winding is increased, then output voltage will decrease.

Last Answer : A D.C. generator can be considered as rotating amplifier.

Last Answer : A cumulatively compounded long shunt generator when operating as a motor would be differentially compounded long shunt.

Last Answer : In a D.C. generator, the critical resistance refers to the resistance of field.

Description : The e.m.f. induced in the armature of a shunt generator is 600 V. The armature resistance is 0.1 ohm. If the armature current is 200 A, the terminal voltage will be?

Last Answer : The e.m.f. induced in the armature of a shunt generator is 600 V. The armature resistance is 0.1 ohm. If the armature current is 200 A, the terminal voltage will be 580 V.

Last Answer : Flashing the field of D.C. generator means creating residual magnetism by a D.C. source.

Last Answer : If a D.C. generator fails to build up the probable cause could not be field resistance less than the critical resistance.

Description : The purpose of providing dummy coils in a generator is?

Last Answer : The purpose of providing dummy coils in a generator is to provide mechanical balance for the rotor.

Description : A shunt generator running at 1000 r.p.m. has generated e.m.f. as 200 V. If the speed increases to 1200 r.p.m., the generated e.m.f. will be nearly?

Last Answer : 200V/E2 = 1000/1200 E2= 240 V

Last Answer : In a D.C. generator the magnetic neutral axis coincides with the geometrical neutral axis, when there is no load on|he generator.

Last Answer : The e.m.f. generated in a D.C. generator is directly proportional to speed of armature.

Last Answer : In a D.C. generator the number of mechanical degrees and electrical degrees will be the same when number of poles is 2.

Last Answer : D.C. generator generally preferred for charging automobile batteries is long shunt compound generator.

Last Answer : The armature core of a D.C. generator is usually made of silicon steel.

Last Answer : In a D.C. generator the ripples in the direct e.m.f. generated are reduced by using carbon brushes of superior quality.

Last Answer : The demagnetising component of armature reaction in a D.C. generator reduces generator e.m.f.

Last Answer : Welding generator will have lap winding.

Last Answer : If brushes of a D.C. generator are moved in order to bring these brushes in magnetic neutral axis, there will be crossmagnetisation as well as demagnetising.

Last Answer : In case of a 4-pole D.C. generator provided with a two layer lap winding with sixteen coils, the pole pitch will be 8.

Last Answer : A separately excited generator as compared to a self-excited generator is amenable to better voltage control, more stable, has exciting current independent of load current.

Description : For a D.C. generator when the number of poles and the number of armature conductors is fixed, then which winding will give the higher e.m.f. ?

Last Answer : Wave winding

Last Answer : In a D.C. generator, the iron losses mainly take place in armature rotor.

Last Answer : The condition for maximum efficiency for a D.C. generator is variable losses equal to constant losses.

Last Answer : The total losses in a well designed D.C. generator of 10 kW will be nearly 500 W.

Description : What size generator is needed for a three bedroom house?

Last Answer : A generator for a three bedroom house would be medium sized. Try a small to medium sized generator that can be found online or at any hardware store in your neighborhood.

Description : What is the minimum wind speed needed for a wind power generator to produce electricity?

Last Answer : You will need at least 10 miles per hour wind speeds to generate power with a turbine. Look for an open spot in your garden that is away from other structures or above the roof line.

Description : The 'function generator' of the control circuit illustrated _______________. EL-0095 A. can be programmed to produce a non-linear output for a linear input depending on operating conditions B. is used for ... which or how many engines are needed for a required vessel speed D. all of the above

Last Answer : Answer: A

Last Answer : If  equalising bar is connected to the 2 DC generators  the current will be equal in 2 generators irrespective of parallel connection so that we connect equaliser bar

Last Answer : Wave winding is composed of that even number which is exact multiple of poles + 2.

Last Answer : Lap winding is composed of any even number of conductors.

Last Answer : In a D.C. machine stray loss is the sum of iron loss and mechanical loss.

Last Answer : In any rotating machine that part which houses the conductors and in which e.m.f. induced is to be utilised is called armature.

Last Answer : Number of tappings for each equilizer ring is equal to number of pole pairs.