Explain negative phase sequence protection of alternator.

1 Answer

Answer :

Negative phase sequence protection of alternator: Unbalanced loading on alternator mainly causes the negative sequence currents which generate the negative sequence components of magnetic fields. These fields rotate in opposite direction of the main field and induce emfs of double frequency in rotor winding causing overheating. Figure shows a scheme for protection against negative phase sequence currents. Three CT’s are connected in star and the secondaries are connected to negative sequence filter. The relay is connected to sequence filter. The negative sequence filters consists of number of inductors and resistors. This negative sequence filter detects the presence of negative sequence components due to unbalance and operates the relay which further operates CB.

image

Related questions

Description : A negative sequence relay is used for protection of  (1) Generator (3) Motor (2) Transformer (4) Long Transmission lines

Last Answer : A negative sequence relay is used for protection of Generator 

Description : For complete protection of a three-phase line: A) three Phase relays and three Earth fault relays are required B) three Phase relays and two Earth fault relays are required C) two Phase relays and two Earth fault relays are required D) two Phase relays and one Earth fault relay are required

Last Answer : For complete protection of a three-phase line: two Phase relays and one Earth fault relay are required

Description : For complete protection ofa 3— phase line: (1) Three phase and three—earth fault relays are required (2) Three phase and two—earth fault relays are required (3) Two phase and two—earth fault relays are required (4) Two phase and one-earth fault relays are required

Last Answer : For complete protection ofa 3— phase line: Two phase and one-earth fault relays are required

Description : The phase sequence of a three-phase alternator will reverse if  A) The field current is reversed keeping the direction of rotation same. B) The field current remains the same but the direction of ... The field current is reversed and also the direction of rotation is reversed D) None of the above

Last Answer : The phase sequence of a three-phase alternator will reverse if The field current remains the same but the direction of rotation is reversed 

Description : An alternator has a phase sequence of RYB for its phase voltage. In case the direction of rotation of alternator is reversed, the phase sequence will become?

Last Answer : An alternator has a phase sequence of RYB for its phase voltage. In case the direction of rotation of alternator is reversed, the phase sequence will become RBY.

Description : How the alternator can be protected from inter-turn fault?

Last Answer : Inter-turn fault Protection: Figure shows scheme for one phase only. It is identical for other phases. Under normal working condition, the two currents in the stator winding sections (S1 and S2) are ... relay coil to operate it, leading to isolation of the alternator from the power system.

Description : For which of the following protection from negative sequence currents is provided ? (a) Generators (b) Motors (c) Transmission line (d) Transformers

Last Answer : (a) Generators

Description : Systems for Protection from negative sequence current is provided normally for (a) Transformers (c) Transmission lines (b) Generators (d) Motors

Last Answer : Systems for Protection from negative sequence current is provided normally for Transmission lines

Description : Explain the “Differential Protection Scheme” used for alternators with neat labeled diagram.

Last Answer : Differential Protection Scheme for Alternator: Figure shows the differential protection provided to 3 phase alternator. Here identical CTs are placed on both sides of 3 phase alternator and ... causing its operation. Relay sends trip signal to the CB, thereby alternator circuit is tripped.

Description : Explain with neat sketch, the Pilot wire protection scheme applied to transmission line.

Last Answer : Pilot Wire Protection scheme of Transmission Line : Figure shows the single line diagram of Merz price voltage balance system for pilot wire protection of three phase transmission line. ... through the relay, which gives trip signal to the circuit breaker for protection of transmission line.

Description : Explain differential protection scheme for busbars with neat sketch.

Last Answer : Differential Protection Scheme for Bus bar:  Under normal conditions, the sum of the currents entering the bus bar zone is equal to those leaving it and no current flows through the relay ... of these currents will flow through the relay coil causing opening of circuit breaker of bus-bar.

Description : Explain differential protection of busbar.

Last Answer : Differential protection Scheme for bus bar: Under normal conditions the sum of the currents entering the bus bar zone is equal to those leaving it and no current flows through the relay ... . The difference of these currents will flow through the relay coil causing opening of circuit breaker.

Description : Explain over-current protection of transformer.

Last Answer : Over-Current Protection of Transformer: Simple over-current & earth fault protection of transformer against external shortcircuit and excessive overloads is shown in the above figure. The ... trip command to the circuit breaker and the transformer is disconnected from load or fault.

Description : Explain fault bus protection scheme.

Last Answer : Fault bus protection of busbar: In this scheme, the substation is so designed that every fault on the bus bar is converted to earth fault. Under normal operating conditions, there is no current flowing ... This results in operation of relay to actuate trip coil of CB to trip the circuit.

Description : Explain distance protection of transmission line with neat sketch diagram.

Last Answer : Distance protection of Transmission line: Distance protection scheme uses impedance relay. The relay operation is based on the impedance (or distance) between the relay and point of fault. Figure shows ... than ZL and impedance relay operates which operates the CB and line is protected.

Description : RC time constant characteristics, as shown in the illustration, are important in _____________. EL-0086 A. bridge rectifiers for alternator excitation B. timing and pulse shaping circuits C. transistor power amplifier biasing D. motor controller overload protection

Last Answer : Answer: B

Description : The purpose of an impressed current cathodic protection system aboard ship is to _______________. A. prevent corrosion of the hull, propeller, rudder and line shafting B. neutralize the vessel's ... the presence of salt air D. maintain a minimum constant alternator load to prevent overheating

Last Answer : Answer: A

Description : What is the backup protection available for an alternator?

Last Answer : Overcurrent and earth fault protection is the backup protections.

Description : Discuss in brief the principle of distance protection and state four advantages of distance protection scheme.

Last Answer : Advantages: 1. System is economical 2. High speed of interruption 3. Suitable for very long and high voltage transmission lines. 4. No problem of pilot wires.

Description : State two requirements of transmission line protection. 

Last Answer : Requirements of Transmission Line Protection: 1) Faults on lines should be quickly detected to initiate actions to maintain system stability. 2) For very long lines the protection system must be capable ... backup protection in the event of failure of circuit breaker (nearest to fault) to operate.

Description : List two limitations of Differential-Protection scheme for transformer.

Last Answer : Limitations of Differential Protection Scheme of Transformer:  1) Due to the magnetization characteristics of the CTs used, the ratio errors change with respect to the circulating currents.  2) ... & improper operation.  5) Inrush of magnetizing current may lead to inadvertent operation.

Description : Write down limitation of differential protection of transformer.

Last Answer : Limitations of differential protection of transformer: 1) Due to the magnetization characteristics of the CTs used, the ratio errors change with respect to the circulating currents. 2) The pilot wires ... current (higher imbalance) due to which accuracy of sensing & operation is decreased. 

Description : How can we use CT and PT for protection purpose?

Last Answer : CT and PT for Protection purpose: Current transformer (CT) and Potential transformer (PT) are instrument transformers, which are used in conjunction with protective relays for protection purpose. The CT ... from the healthy part. In this way the CT and PT can be used for protection purpose.

Description : Which type of protection is provided on a generator to protect against stator insulation failure? A) Differential protection B) Overcurrent relay C) Thermocouple actuated alarm D) Reverse power relay

Last Answer : Which type of protection is provided on a generator to protect against stator insulation failure? A) Differential protection B) Overcurrent relay C) Thermocouple actuated alarm D) Reverse power relay 

Description :  For the protection of parallel feeders fed from one end, the relays used are: A) non-directional relays at the source-end and directional relays at the load-end B) non-directional relays at both the ... at the source-end and non-directional at the load-end D) directional relays at both the ends

Last Answer : For the protection of parallel feeders fed from one end, the relays used are: non-directional relays at the source-end and directional relays at the load-end

Description : A loss of excitation protection scheme for large generating unit employs A) under frequency relays B) offset Mho relay C) reactance relay D) percentage differential relay

Last Answer : A loss of excitation protection scheme for large generating unit employs offset Mho relay

Description : The type of backup protection scheme widely used in the field is (A) Relay backup (B) Breaker backup (C) Remote backup (D) Auxiliary backup

Last Answer : The type of backup protection scheme widely used in the field is Remote backup 

Description : Blind spot is a point in the zones of protection where

Last Answer : Blind spot is a point in the zones of protection where No protection is available.

Description : A relay used for protection of motors against overload is :  (A) Impedance relay (B) Electromagnetic attraction type (C) Thermal relay (D) Buchholz's relay

Last Answer : D

Description : For protection of rotating machines against lightning surges _______ is used.  (1) lightning arrester (2) capacitor (3) combination of lightning arrester and capacitor (4) lightning conductor and arrester

Last Answer : For protection of rotating machines against lightning surges combination of lightning arrester and capacitor is used. 

Description : Reactance relay is normally preferred for protection against

Last Answer : Reactance relay is normally preferred for protection against earth faults

Description : Surge absorbers are used for protection against

Last Answer : Surge absorbers are used for protection against low voltage high frequency oscillations

Last Answer : Protection by fuses is generally not used beyond 100 A .

Last Answer : A fuse in a motor circuit provides protection against short-circuit and overload.

Last Answer : Overfluxing protection is recommended for generator transformer of the power plant.

Last Answer : Over voltage protection is recommended for hydro-electric generators, steam turbine generators, gas turbine generators.

Last Answer : The inverse definite mean time relays are used for over current and earth fault protection of transformer against internal short-circuits.

Last Answer : The single phasing relays are used for the protection of three phase motors.

Last Answer : Discrimination between main and back up protection is provided by the use of relays which are slow.

Last Answer : For the protection of power station buildings against direct strokes the requirements are interception, conduction and dissipation.

Last Answer : The delay fuses are used for the protection of motors.

Last Answer : H.R.C. fuses provide best protection against short-circuits.

Last Answer : A thermal protection switch can protect against overload.

Description : Primary and Backup Protection

Last Answer : Primary and Backup Protection  B,D,G,I are the primary protection. A,C,H,J are the backup protection. About 90% of faults are clear by Primary Protection. So ... ordinated backup (primary is at various station  and backup is at control room with computer)

Description : Zero-sequence current is used for relaying purpose only in the case of   (a) Phase over current relay (b) Phase impedance relay (c) Ground over current relay (d) Ground impedance relay

Last Answer : Zero-sequence current is used for relaying purpose only in the case of Ground impedance relay

Description : An open occurring within the field rheostat of an AC generator can be detected by short circuiting its terminals and observing a ____________. A. negative deflection of the wattmeter pointer B. ... of the wattmeter pointer C. buildup of alternator voltage D. low, but constant alternator voltage

Last Answer : Answer: C

Description : Which of the following problems will occur if the circuit breaker of the incoming alternator is closed and it is 180° out of phase with the loaded alternator when paralleling? A. The rotor of the ... The rotor of the incoming alternator will stop. D. Both alternators will parallel 180° out of phase.

Last Answer : Answer: B

Description : A three-phase alternator is operating at 450 volts, 250 amps at 0.6 power factor. If the power factor increases to 0.8, the kw load potential will increase by _____________. A. 38.525 kw B. 116.91 kw C. 155.88 kw D. 194.85 kw

Last Answer : Answer: A

Description : A three-phase alternator operates at 450 volts with a power factor of 0.8. If the ammeter indicates 250 amperes, what should be the KW meter reading? A. 90.00 KW B. 127.27 KW C. 155.70 KW D. 194.85 KW

Last Answer : Answer: C