What is the difference between isolator and contactor?

1 Answer

Answer :

Contactor is used for on load operation. Because they are fast acting devices. They posses arc chamber and arc chutes. Arc chamber and arc chute make it easy to extinguish the arc produced during on load operation. 


Isolator is off load devices. Because they are slow acting devices. The arc time is more in slow acting devices and operated only in off load. 

Related questions

Description : What is the difference between Isolator and Circuit Breaker?

Last Answer : Isolator is an off load device which is used for isolating the downstream circuits from upstream circuits for the reason of any maintenance on downstream circuits. It is manually operated and does ... is rated current and 2 is short circuit breaking capacity and 3 is instantaneous tripping current.

Description : What is the difference between Isolator and Circuit Breaker?

Last Answer : A: Isolator is a off load device which is used for isolating the downstream circuits from upstream circuits for the reason of any maintenance on downstream circuits. it is manually operated ... specification 1) rated current 2) short circuit breaking capacity and 3) Instantaneous tripping current.

Description : What is the difference between circuit breaker and isolator?

Last Answer : Isolator is a disconnecting switch which is not having the making and breaking capacity. Bus coupler - 2000A Feeders - 1600 A

Description : Which of the following statements represents the main difference between a relay and a contactor? A. Contactors control current and relays control voltage. B. A relay is series connected and a contactor ... loads than relays. D. Contactors are made from silver and relays are made from copper.

Last Answer : Answer: C

Description : What is the difference between a contactor and a breaker?

Last Answer : Contactor is not designed to open on short circuit condition (fuse will take care of this situation). Breaker is having complicated mechanism for closing and tripping. 

Description : Give the details of switchyard 220 kV CB, Isolator, CT, CVT and lightning arrestor.  

Last Answer : 220 kV SF6 Circuit Breaker 1. Make - ABB 2. Air pressure blocking a. Close Block - 17.3 bar. b. Open block - 16.7 bar. c. Auto reclose block - 19 bar. 3. SF6 pressure block a. Alarm - 5. ... , storage and erection. Rated voltage : 216 kV rms. Operating voltage : 184 kV rms. 

Description : In the illustration shown, coil 'MR' is a ____________. EL-0012 A. running contactor coil B. rupture (blowout) coil C. resistance coil D. reversing coil

Last Answer : Answer: A

Description : Which component is responsible for energizing solenoid 'B1-B2' and releasing the brake for the winch motor shown in the illustration? EL-0102 A. Contactor '3M' B. A spring not shown in the schematic diagram C. Resistor 'B2-R1' D. Relay 'FR-B.O.'

Last Answer : Answer: A

Description : The winch shown in the illustration will not operate in any speed in the lowering direction and at an abnormal speed in 'first point hoist'. The possible cause is that _______________. EL-0102 A. ... '1M' in the power circuit are badly corroded D. master switch contacts 'MS6' have weak springs

Last Answer : Answer: B

Description : The winch shown in the illustration operates in any of the positions with the master switch in the 'lower' direction, but will not 'hoist' in any of the master switch hoist positions. Which of the listed faults ... '2M' in the power circuit may be badly corroded. D. Series relay 'FR' may be open.

Last Answer : Answer: A

Description : The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical ... D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

Last Answer : Answer: B

Description : If many turns of an alternating current coil for a contactor become short circuited, the coil _____________. A. will continue to operate B. will probably burn out immediately C. will operate on reduced current D. temperature will drop

Last Answer : Answer: B

Description : The heaters for the winch circuit shown in the illustration are powered from _____________. EL-0102 A. a separate source B. the winch main bus C. the master switch power circuit D. the contactor control circuit

Last Answer : Answer: A

Description : When troubleshooting motor controllers, a shorted relay or contactor coil is often indicated by _______________. A. a resistance reading of 'infinity' on an ohmmeter B. charred insulation and/or a blown ... of the coil's leads to ground D. a higher-than-normal voltage reading across the winding

Last Answer : Answer: B

Description : The 'safe switch' of the winch controller shown in the illustration is operated _______________. EL-0102 A. through the master switch handle B. when heater circuit current is high C. by contactor coil 'FR' D. manually by the winch operator

Last Answer : Answer: D

Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil

Last Answer : Answer: D

Description : If many turns of an alternating current coil for a contactor become short circuited, the coil _____________. A. temperature will drop B. will probably burn out immediately C. will continue to operate D. will operate on reduced current

Last Answer : Answer: B

Description : Magnet chatter or 'pumping' occurring in a magnetic contactor can be caused by ______________. A. dirt or grease on pole faces B. mechanical interference in the contacts C. chattering contacts on the control relay D. magnetic lock out of the contacts

Last Answer : Answer: C

Description : During its operation, loud buzzing and resultant welding of contacts of a magnetic relay may be caused by __________. A. overheating of the contactor coil B. low voltage on the operating coil C. low insulation resistance to ground D. lubrication of the contact bearing points

Last Answer : Answer: B

Description : A circuit is protected from overheating by a/an ___________. A. pyrometer B. thermal overload relay C. magnetic contactor D. overload transformer

Last Answer : Answer: B

Description : A shading coil used in an AC magnetic controller, functions to _____________. A. reduce vibration and noise in the contactor B. prevent flux buildup in the operating coil C. eliminate arcing when the contacts close D. energize the operating coil and 'pull in' the contacts

Last Answer : Answer: A

Description : What is the safety reason to keep the contactor / MCC remote from motor?  

Last Answer : Contactor = sparking equipment. Not suiting for hazardous location.  

Description : Can we file the pitted contacts of contactor?

Last Answer : No, use emery paper and etc.  

Description : What material used for contactor?

Last Answer : Silver-nickel for

Description : Why pure silver is not used in contactor? 

Last Answer : Affected by sulphur, mechanical or arcing damages (adv. Lower voltage drop) 

Description : Why copper contact are not used in contactor? 

Last Answer : Because corrosion rate increases. Poor surface property , large closing force required. 

Description : Why shading rings provided in armature core of ac contactor. Why not for dc contactor? 

Last Answer : Because the force developed is not steady in ac therefore contacts will chatter but if shading ring is used force developed becomes steady due to splitting of phases of flux, therefore contacts becomes bounce free and humming sound reduces.  

Description : Can we use AC contactor in DC circuit?  

Last Answer : Yes, but with adequate de-rating.  

Description : DC relay coil or contactor coils must be connected to which side?

Last Answer : Negative side of the DC supply to avoid galvanic effect on the coil, which will corrode the coil.  

Description : What is the difference between relay and contactor?

Last Answer : Relay have smaller ratings. Contactor is a high rating relay.

Description : Does the Wire Rope Isolator dash number at the end of the model number have meaning?

Last Answer : In general it represents the number of loops in the isolator.

Description : Do the three digit Wire Rope Isolator (WRI) model index numbers have any meaning?

Last Answer : The difference between a 200, 400, 600, and 800 index number has relative meaning within a series. The larger the number the taller the isolator but the lower the isolator stiffness.

Description : What does the WR series number represent on standard Wire Rope Isolator (WRI)?

Last Answer : The number following WR represents the wire diameter in 32nd of an inch. The WRS series isolators use 5/32” diameter wire.

Description : What type of mounting option should I select on a Wire Rope Isolator (WRD?

Last Answer : Application dependent, but in general, for shock applications use mounting options "B," "D," or "E"

Description : How much damping can be expected from a Wire Rope Isolator (WRI)?

Last Answer : WRI have between 5% and 20% damping. The amount of damping is related to wire diameter and stroke. The larger the wire diameter, the more damped (and stiffer) the isolator. Damping can be less with small amplitude vibration.

Description : A component that samples the microwave signal travelling in one direction down to the transmission line A. Isolator B. Combiner C. Directional coupler D. Attenuator

Last Answer : C. Directional coupler

Description : What is the device used in fiber optic communication which consist of a receiver transmitter use to clean up and amplify digital data moving in one direction and another in the opposite direction? A. Optic compressors B. Optic retarders C. Optic isolator D. Optic regenerators

Last Answer : D. Optic regenerators

Description : A quarter wavelength devices made of crystalline calcite that changes polarization in the optic fiber communication. A. Isolator B. Retarder C. Polarizer D. Filters

Last Answer : B. Retarder

Description : How can intermodulation interference between two transmitters in close proximity reduced or eliminated? A. Through installing a band-pass filter in the antenna feed line B. Through installing terminated circulator ... high driving power D. By installing a low-pass filter in the antenna feed line

Last Answer : A. Through installing a band-pass filter in the antenna feed line

Description : Referred to as a ferrite device that can be used in lieu of a duplexer to isolate a microwave transmitter and receiver when both are connected to the same antenna. A. Isolator B. Circulator C. Coupler D. Diode.

Last Answer : B. Circulator

Description : Curl cannot be employed in which one of the following? a) Directional coupler b) Magic Tee c) Isolator and Terminator d) Waveguides

Last Answer : d) Waveguides

Description : Which of the following is the least expensive protection for overcurrent is low voltage system ? (a) Rewireable fuse (b) Isolator (c) Oil circuit breaker (d) Air break circuit breaker (e) None of the above

Last Answer : (a) Rewireable fuse

Description : A function of an optic isolator ∙ a. Cancels reflective waves ∙ b. Amplifies signal transmitted ∙ c. Filters unnecessary signals ∙ d. All of these

Last Answer : a. Cancels reflective waves

Description : Suppose a student is a chain smoker and generally he leaves the period or comes late due to smoking, How would you like to compromise with such a student in the class? Options: A) Applying ... him on assembly ground C) Expelling him from the school D) Sharing the habit and become friendly

Last Answer : A) Applying suggestive measures in a isolator conditions

Description : With neat diagram explain the operation of Horizontal break isolator.

Last Answer : Operation of Horizontal Break Isolator: 1) Fixed female contacts of metal are supported on stack of insulator. 2) Male contact rod is connected to central insulating support which can be ... on galvanized steel channel or steel frame. The moving male contact can be move through 90o.

Description : Sequence of operation of isolator and circuit breaker while opening and closing

Last Answer : Sequence of operation of Isolator and C.B while opening & closing is as below:  While Opening:   1. Open circuit breaker  2. Open Isolator  3. Close earthing switch  While Closing:  ... breaker is open  2. Open earthing switch  3. Close isolator  4. Close circuit breaker

Description : Write working of opto coupler as an isolator.

Last Answer : Optocoupler is as shown in fig. it consist of LED as an light source and phototransistor act as light detector.  When input pulse is applied LED turns ON.Light emitted by LED focused on CB ... starts flowing.As input pulse reduces to zero LED turns OFF collector current becomes zero. 

Description : What is the significance of signal conditioner? Explain the need of following in mechatronics system. i) Isolator ii) Filter iii) Amplifier iv) Data converter

Last Answer : Significance: Signal conditioning means manipulating an analog signal in such a way that it meets the requirements of the next stage for further processing. Signal inputs accepted by signal ... -frequency converters, current-to-voltage converters, current loop converters, and charge converters.  

Description : Define opto-isolator. Explain the role of opto-isolator in PLC.

Last Answer : Role of optoisolator in PLC: An optoisolator is a semiconductor device that uses a short optical transmission path to transfer an electrical signal between circuits or elements of a ... disruptions, optoisolators offer a safe interface between high-voltage components and low-voltage devices.