Draw a typical time-current characteristic for IDMT relay. 

1 Answer

Answer :

Time-Current Characteristic for IDMT Relay:

image

Related questions

Description : A relay has a rating of 5 A, 2.2 sec IDMT and a relay setting of 125% TMS = 0.6. It is connected to a supply circuit through a C.T. 400/5 ratio. The fault current is 4000 A. The operating current of the relay is

Last Answer : A relay has a rating of 5 A, 2.2 sec IDMT and a relay setting of 125% TMS = 0.6. It is connected to a supply circuit through a C.T. 400/5 ratio. The fault current is 4000 A. The operating current of the relay is 6.25A

Description : Why IDMT over current relay is always used as backup?

Last Answer : Because setting has to be 200% to emergency loading and TMS be large to grade with feeder. Therefore very slow for internal faults/terminal faults/uncleared LV faults. 

Description : IDMT relays are used to protect the transformer against :  (A) Internal short -circuits (B) Open circuits (C) External short circuits (D) Oil leakage

Last Answer : IDMT relays are used to protect the transformer against : External short circuits

Description : Describe over current relay with time-current characteristic.

Last Answer : Over current relay with time-current characteristics:- 1. Definite time over current relay: Operating time is constant, the relays operates after a predetermined time when the current exceeds the pickup ... of fault current and definite time characteristics at higher values of fault current.

Description : Define IDMT relay?

Last Answer : It is an Inverse Definite Minimum Time relay. In IDMT relay its operating is inversely proportional and also a characteristic of minimum time after which this relay operates. It is inverse in the sense; the tripping time will decrease as the magnitude of fault current increase.

Last Answer : The relay with inverse time characteristic will operate within 5 to 10 sec.

Description : Define the following terms with respect to protective relays i) Relay time ii) Reset current iii) Plug setting multiplier and iv) Time setting multiplier

Last Answer : 1) Relay Time: The time interval between occurrence of fault and closure of relay contacts.  2) Reset Current: The value of current below which the relay resets and comes back to ... The adjustment arrangement provided for setting the operation time of relay is known as Time setting multiplier. 

Description : Describe the operation of current differential relay with neat sketch.

Last Answer : Operation of Current Differential Relay: Figure shows an arrangement of an overcurrent relay connected to operate as a differential relay for alternator protection under fault conditon. ... current flows through relay coil, causing relay to operate for protection of alternator winding.

Description : Explain construction and operation of induction type directional over current relay.

Last Answer : Directional overcurrent relay: Construction: It consists of two units: i) Non-directional Over-current unit ii) Directional power unit The directional unit consists of upper electromagnet ... closes the trip circuit. This operates circuit breaker which isolates the faulty section. 

Description : If the fault current is 6000 A, the relay plug setting is 150% and the CT ratio is 400/5, the plug setting multiplier will be

Last Answer : If the fault current is 6000 A, the relay plug setting is 150% and the CT ratio is 400/5, the plug setting multiplier will be 10

Description : In the induction type directional over current relay, when a short-circuit occurs in the circuit (A) power flows in reverse direction (B) power flows in normal direction (C) directional power element does not operate (D) over current element is not energized

Last Answer : In the induction type directional over current relay, when a short-circuit occurs in the circuit power flows in reverse direction

Last Answer : In order that current should flow without causing excessive heating or voltage drop, the relay contacts should have low contact resistance, be clean and smooth, be of sufficient size and proper shape.

Description : The operating time of instantaneous relay is

Last Answer : The operating time of instantaneous relay is 0.1 sec

Description : What is the characteristic of inverse time over current relay?  

Last Answer : If the fault current increases the time of the operation of the relay will be decreases.  

Description : With the help of neat diagram, explain operation of static relay.

Last Answer : Operation of Static Relay: Operation: 1) The solid-state component used are transistors, diodes, resistors, IC s, capacitor etc. The function of comparison and measurement are accomplished by ... ) An auxiliary dc supply is provided for operation of static relay elements as shown in figure.

Description : Describe the construction and Operation of Buchholz relay with neat labeled diagram.

Last Answer : Construction of Buchholz Relay: It takes the form of a domed vessel placed in the connecting pipe between the main tank and the conservator. The device has two elements. The upper element ... manner that it senses the sudden violent movement of oil/gas from transformer tank to conservator. 

Description : With a neat sketch, explain the working of Thermal relay.

Last Answer : Working of Thermal Relay: 1) When the system is in normal operating condition, the heating element carries normal current from CT, this current produces heat = I2Rt. This heat ... of the spring releases which operates relay contacts resulting into providing trip signal to trip circuit.

Description : Explain operation of balanced beam type relay.

Last Answer : Balanced Beam Type Relay: Under normal operating condition the current through relay coil is such that the beam is held in the horizontal position by the spring. When the fault occurs on the system the ... becomes greater than pick-up value and beam is attracted to close the trip circuit. 

Description : Explain Buchholz relay with neat labelled diagram.

Last Answer : Buchholz relay: The relay is located in the path of the oil from transformer tank to conservator. As seen from diagram, the upper mercury switch operates the alarm circuit due to tilting of the ... manner that it senses the sudden violent movement of oil from transformer tank to conservator.

Description : Explain MHO relay in detail.

Last Answer : MHO Relay: In this relay, poles 1, 2, 3 are energized by a voltage V through polarizing coil to produce flux, the capacitor connected provides phase shift. The left pole 4 is energized by a current which is the ... hence on the ratio (I/V) = Y i.e. admittance, hence called as MHO relay.

Description : Explain operation of µP based relay with block diagram

Last Answer : Operation of Microprocessor (µP) based relay: The inputs from the power system through CTs and PTS are received by the analog Input receiver; they are sampled simultaneously or ... compares the dynamic inputs and decides accordingly to generate trip/alarm signal to the output device.

Description : The reactance relay is essentially: A) an over-voltage relay with current restraint B) an over-voltage relay with directional restraint C) a directional relay with voltage restraint D) a directional relay with current restraint 

Last Answer : an over voltage relay with delay an over voltage relay with directional resistance

Description : The operation of the relay which is most affected due to arc resistance is A) Mho relay B) Reactance relay C) Impedance relay D) All are equally affected

Last Answer : The operation of the relay which is most affected due to arc resistance is Mho relay

Description : The most efficient torque — producing actuating structure for induction — type relay is:

Last Answer : The most efficient torque — producing actuating structure for induction — type relay is: induction-cup structure

Description : In a biased differential relay, the bias is defined as the ratio of  A) Number of turns of restraining coil and operating coil B) Operating coil current and restraining coil current C) Faulteurrent and operating coil current D) Fault current and restraining coil current

Last Answer : In a biased differential relay, the bias is defined as the ratio of Number of turns of restraining coil and operating coil 

Description : 30°, 60° and 90° connections are made in a directional relay to render the relay (A) Sufficient torque under fault conditions (B) Zero torque under fault conditions (C) Current grading (D) Time grading

Last Answer : 30°, 60° and 90° connections are made in a directional relay to render the relay Sufficient torque under fault conditions

Description : If a relay fails to operate for a fault within its reach, it is said to

Last Answer : If a relay fails to operate for a fault within its reach, it is said to Under reach

Description : Which relay is more sensitive ? 1 VA or 2 VA ? (A) 1 VA (B) 2 VA (C) Both are equally sensitive (D) Both are insensitive

Last Answer : Which relay is more sensitive ? 1 VA or 2 VA ? (A) 1 VA (B) 2 VA (C) Both are equally sensitive (D) Both are insensitive

Description : The purpose of the restraining coil in a biased differential relay is  (A) To reduce CT saturation during fault.  (B) To increase the sensitivity of the relay.  (C) To match the transformation ratio.  (D) To limit the spill current through the relay during heavy external fault.

Last Answer : d

Description : A relay used for protection of motors against overload is :  (A) Impedance relay (B) Electromagnetic attraction type (C) Thermal relay (D) Buchholz's relay

Last Answer : D

Description : What is the difference between relay and contactor?

Last Answer : Relay have smaller ratings. Contactor is a high rating relay.

Description : A negative sequence relay is used for protection of  (1) Generator (3) Motor (2) Transformer (4) Long Transmission lines

Last Answer : A negative sequence relay is used for protection of Generator 

Description : Buchholz relay is  (1) located in the conservator tank  (2) located in the transformer tank itself  (3) connected in the pipe connecting main tank of transformer and conservator  (4) installed in the circuit breaker

Last Answer : Buchholz relay is connected in the pipe connecting main tank of transformer and conservator 

Description : To prevent mal-operation of differentially connected relay while energizing a transformer, the relay restraining coil is based with  (1) second harmonic current  (2) third harmonic current  (3) fifth harmonic current  (4) seventh harmonic current

Last Answer : To prevent mal-operation of differentially connected relay while energizing a transformer, the relay restraining coil is based with  second harmonic current 

Description : Reactance relay is normally preferred for protection against

Last Answer : Reactance relay is normally preferred for protection against earth faults

Description : A solid state relay (A) withstands voltage transients (B) does not require auxiliary dc supply (C) provide low burden on CT and P (D) does not provide earth fault protection

Last Answer : A solid state relay provide low burden on CT and P

Last Answer : The torque produced in induction type relay (shaded pole structure) is inversely proportional to the square of the current.

Last Answer : Admittance relay is directional relay.

Last Answer : The under voltage relay can be used for generators, busbars, transformers, motors.

Last Answer : Reactance relay is preferred for phase fault on short transmission line.

Last Answer : Induction cup relay is operated due to changes in current, voltage, impedance.

Last Answer : Interruption of large currents by relay requires arc suppressing blow out coils, wide separation of the opened contacts, high speed opening of contacts.

Last Answer : Overheating of relay contacts or contact born out is due to slow making and breaking of load circuit contacts, foreign matter on the contact surface, too low contact pressure.

Last Answer : A differential relay measures the vector difference between two or more similar electrical quantities.

Last Answer : Burden of a protective relay is the power absorbed by the circuit of relay.

Last Answer : The relay operating speed depends upon the spring tension, the rate of flux built up, armature core air gap.

Description : How do relay works ?

Last Answer : Relay working like contact it is noise less 

Description : What is the use of Buchholz relay in transformer?

Last Answer : This is a transformer that is used to step up and down current. 

Description : What is the difference between a switch and a relay?

Last Answer : Switch is simply a mechanical contact mechanism and relay is a electromagnetic switch . Switch can be direct mechanically turn on and off but relay can be operated by energising coil .

Description : The relay with inverse time characteristic will operate within (a) 1.5 sec (b) 5 to 10 sec (c) 5 to 20 sec (d) 20 to 30 sec (e) none of the above

Last Answer : (b) 5 to 10 sec