In buchholz relay how the top and bottom mercury switches are connected?

1 Answer

Answer :

Top mercury switch is connected for alarm and bottom switch for trip.

Related questions

Description : In buchholz relay how the top and bottom mercury switches are connected?  

Last Answer : Top mercury switch is connected for alarm and bottom switch for trip.  

Description : Where is buchholz relay located?

Last Answer : It is located between transformer tank and conservator.

Description : What is buchholz relay?

Last Answer : It protects the transformer from their internal faults like earth faults, winding short circuit, short circuit between phases, Puncture of bushing etc..

Description : 76 The changes in volume of transformer cooling oil due to variation of atmospeheric temperature during day and night is taken care of by which part of transformer? A. Conservator B. Breather C. Bushings D. Buchholz relay

Last Answer : A. Conservator

Description : What is the use of Buchholz relay in transformer?

Last Answer : This is a transformer that is used to step up and down current. 

Description : To prevent mal-operation of differentially connected relay while energizing a transformer, the relay restraining coil is based with  (1) second harmonic current  (2) third harmonic current  (3) fifth harmonic current  (4) seventh harmonic current

Last Answer : To prevent mal-operation of differentially connected relay while energizing a transformer, the relay restraining coil is based with  second harmonic current 

Description : What Is Buchholz Relay And The Significance Of It In To The transformer ?

Last Answer : Buchholz Relay is a device which is used for the protection of transformer from its internal faults, it is a gas based relay. whenever any internal fault occurs in a transformer, the Buchholz Relay ... then it stop its sound itself other wise it trips the circuit by its own tripping mechanism.

Description : What is buchholz relay and the significance of it in to the transformer?

Last Answer : A:Buchholz relay is a gas based relay which is used for the protection of transformer from its internal faults. whenever any internal fault occurs in a transformer, the buchholz relay at once gives an ... then it stop its sound itself other wise it trips the circuit by its own tripping mechanism.

Description : what is Buchholz relay and the significance of it in to the transformer?

Last Answer : Buchholz relay is a device which is used for the protection of transformer from its internal faults, it is a gas based relay. whenever any internal fault occurs in a transformer, the Buchholz ... circuit then it stop its sound itself otherwise it trips the circuit by its own tripping mechanism.

Description : What are the limitations of Buchholz relay?

Last Answer : (a) Only fault below the oil level are detected. (b) Mercury switch setting should be very accurate, otherwise even for vibration, there can be a false operation. (c) The relay is of slow operating type, which is unsatisfactory.

Description : What is the use of buchholz relay in the transformer?

Last Answer : It's a protection relay used in oil immersed transformer to protect the transformer from insulation failure, core heating or any other type of internal faults, which may cause the heating of ... relay first operates and then the trip relay operates to isolate the transformer from the circuit.

Description : In a Tap changing transformer on which side is the tap connected, primary side or secondary side?

Last Answer : A. Tapings are always connected to high voltage winding side, because of low current. If we connect tapings to low voltage side, sparks will produce while tap changing operation due to high current.

Description : Describe the construction and Operation of Buchholz relay with neat labeled diagram.

Last Answer : Construction of Buchholz Relay: It takes the form of a domed vessel placed in the connecting pipe between the main tank and the conservator. The device has two elements. The upper element ... manner that it senses the sudden violent movement of oil/gas from transformer tank to conservator. 

Description : Explain Buchholz relay with neat labelled diagram.

Last Answer : Buchholz relay: The relay is located in the path of the oil from transformer tank to conservator. As seen from diagram, the upper mercury switch operates the alarm circuit due to tilting of the ... manner that it senses the sudden violent movement of oil from transformer tank to conservator.

Description : Buchholz relay is  (1) located in the conservator tank  (2) located in the transformer tank itself  (3) connected in the pipe connecting main tank of transformer and conservator  (4) installed in the circuit breaker

Last Answer : Buchholz relay is connected in the pipe connecting main tank of transformer and conservator 

Description : Buchholz relay is used as a safety device with respect to which of the following? A) Audio transformers B) Oil filled power transformers C) Air core transformer D) None of these

Last Answer : Buchholz relay is used as a safety device with respect to which of the following? A) Audio transformers B) Oil filled power transformers C) Air core transformer D) None of these

Last Answer : A Buchholz relay can be installed on oil cooled transformers.

Last Answer : The buchholz relay is one type of relay which is used in the oil filled power transformerand is for the safety device .

Description : Motor controllers are seldom troubled with grounds because _____________. A. the auxiliary contacts have a high resistance connection B. the contactors and relays are mounted on a nonconducting panel ... individual series-connected units D. there are separate switches for the motor and the control

Last Answer : Answer: B

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Last Answer : D. Loading of the transformers not in proportion to their kVA ratings

Description : 52 A transformer has 1000 primary turns, connected to 250V ac supply. To get 400V secondary voltage the no of secondary turns should be A. 1600 B. 250 C. 400 D. 1250

Last Answer : A. 1600

Description : What will happen if the primary of a transformer is connected to D.C. supply?  (A) Transformer will operate with low efficiency (B) Transformer will operate with high efficiency (C) No effect (D) Transformer may start to smoke and burn 

Last Answer : What will happen if the primary of a transformer is connected to D.C. supply?  (A) Transformer will operate with low efficiency (B) Transformer will operate with high efficiency (C) No effect (D) Transformer may start to smoke and burn 

Description : What would happen if a power transformer designed for operation on 50 Hz (frequency) were connected to a 500 Hz (frequency) source of the same voltage:  (A) Eddy Current and Hysteresis losses will be ... Current will be too much high  (C) Transformer may start to smoke and burn  (D) No effect

Last Answer : What would happen if a power transformer designed for operation on 50 Hz (frequency) were connected to a 500 Hz (frequency) source of the same voltage:  (A) Eddy Current and Hysteresis losses will be ... will be too much high  (C) Transformer may start to smoke and burn  (D) No effect

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : Batteries 'A' and 'B' shown in the illustration are 6 volts each and batteries 'C' and 'D' are 24 volts each. If 'A' were connected in series-opposing to 'C' and 'B' was similarly ... the top terminal C. 30 volts, negative at the bottom terminal D. 30 volts, positive at the bottom terminal

Last Answer : Answer: A

Description : In Frame Relay, when a _____ is selected, the correspondingtable entry is recorded for all switches by the administrator A) PVC B) SVC C) either (a) or (b) D) neither (a) nor (b)

Last Answer : PVC

Description : What are the transformer losses?

Last Answer : Answer: TRANSFORMER LOSSES - There are mainly two kinds of losses in a transformer namely 1. Copper loss (ohmic loss) and 2.magnetic loss (core loss). Copper losses are caused by the ... ohmic loss the following two losses are also present in the transformer stray load loss and dielectric loss.

Description : Why Silica gel is used in transformers?

Last Answer : Silica Gel is used to remove the moisture in the air entering in to the transformer. During the breathing of the transformer air enters in to the transformer. This air makes contact with the hot ... Silica gel crystals will be in blue color initially and after absorbing moisture it turns to pink.

Description : What are the conditions for parallel operation of two transformers ?

Last Answer : Transformers which are to be operated parallel should have to satisfy the following conditions: Polarities of both the transformers should be same else lead to short circuit Voltage rating of ... Phase displacement of transformers should be same Phase sequence of two transformers should be same

Description : At what power maximum efficiency of power transformer and distribution transformer is designed

Last Answer : Maximum efficiency of the transformer is attained at certain load factor (α) when core losses of transformer is equal to the copper losses. PCore loss = α ^2 X PCopper loss From the ... the day. Hence distribution transformers are designed to have maximum efficiency at 50% of the rated full load

Description : What happen when Transformer is given DC supply ?

Last Answer : When DC supply is given to the transformer primary winding no back emf is induced in the transformer. Importance of Back emf is that it limits the current drawn by the machine. In the absence ... in burning down of primary winding. So when dc supply is given to transformer primary windings will burn

Description : During No load why the power factor of the transformer is very low ?

Last Answer : Current flowing through the transformer consists of two components. Magnetizing current (Im) which is in quadrature (90 0 ) to the applied voltage and in phase current which is in phase to the applied voltage ... power factor of transformer during no load condition will by in the order of 0.1 to 0.2

Description : What is the significance of vector grouping in Power Transformers?

Last Answer : Answer:Every power transformer has a vector group listed by its manufacturer. Fundamentally it tells you the information about how the windings are connected (delta or wye) and the phace difference betweent ... Delta primary, Wye Secondry and the current is at 11 o clock reffered to the voltage.

Description : What is the supply rated o/p if two single phase transformer connect to give three phase o/p from a three phase I/p?

Last Answer : A. Each transformer is only capable of supplying 86.6%of its o/p rating

Description : How to connect two single phase transformer to give three phase o/p from a three phase I/p ?

Last Answer : A. They would have to connect in an open-delta.

Description : What advantage has the star connection over the delta connection ?

Last Answer : A. Each star connection transformer is wound for only 57.7% of line voltage . In hv transmission, this admits of much smaller transformer being built for high voltage than possible with delta connection, because of less insulation.

Description : What is the advantage is obtained in the delta connection ?

Last Answer : A. When three transformer are obtained in delta, one may be removed and two remaining unit will carry 57.7% of the original three phase load and thus maintain the continuity of supply.

Description : What is the 3 ph transformer ?

Last Answer : A. A 3ph transformer is that transformer which is equivalent to three single phase transformer but wound on one core and enclosed within one common case.

Description : What parameters or technical particulars are important to be considered while designing protection scheme of the transformer?

Last Answer : 1.Network Diagram showing the position of the transformer in the system 2.kVA or MVA rating of the transformer 3.Fault Level at the transformer 4.Voltage Ratio 5.Winding Connections 6.Per Unit ... Oil Filled 11.Length and area of cross section of the connecting leads between CTs and Relay Panel

Description : What can be the reasons for the failure of the transformer?

Last Answer : Answer: Transformer is one of the most expensive equipments in the Power System. Failure of the transformer can cause outage of power supply for even days. However, multiple things can go wrong with ... relays. 3.Short Circuits 4.Open Circuits 5.Earth Faults 6.Over Voltage 7.Reduced system frequency

Description : How Transformer Protection provided for internal faults?

Last Answer : 1.Bucholz Relay (1st Stage Alarm and 2nd Stage Trip) 2.Sudden Pressure Relay (1st Stage Alarm and 2nd Stage Trip) 3.Pressure Relief Valve (1st Stage Alarm and 2nd Stage Trip) 4.Pressure Switch ... 8.Gas Temperature Indicator (Alarm) 9.Silicon Breather (Passive - no alarm) 10.Smoke Detector (Alarm)

Description : What are the tests done to minimize internal faults?

Last Answer : 1.Dissolved Gas Analysis (DGA): Faults due to arcing, high current breakdown of oil, localized sparking, partial discharge of oil, localized overheating or hot spots, etc. causes ... Over current relays with under voltage blocking 6.Zero sequence protection. 7.Negative phase sequence protection

Description : What are the reasons for Oil degradation?

Last Answer : 1.Degradation 2.Oxidation 3.Contamination a) Dielectric breakdown voltage indicates the presence of electrically conductive contaminants in oil. b) Interfacial tension and acid number (sometimes called ... c) Water content is temperature dependent. d) Power factor is also temperature dependent.

Description : How does change in frequency affect the operation of a given transformer?

Last Answer : a) Iron loss .........increases with a decrease in frequency. A 60-Hz transformer will have nearly 11% higher losses when worked on 50Hz instead of 60 Hz. However, when a 25-Hz ... ....since total loss is greater at a lower frequency, the temperature is increased with decrease in frequency.

Description : What effects are produced by change in voltage?

Last Answer : a) Iron loss.........varies approximately as V2. b) Cu loss.........it also varies as V2 but decreases with an increase in voltage if constant kVA output is assumed. c ... ..for constant kVA output, iron temperatures increase whereas Cu temperatures decrease with increase in voltages and vice-versa.

Description : Does the transformer draw any current when its secondary is open?

Last Answer : Yes, no-load primary current.

Description : In practice, what determines the thickness of the laminate or stampings?

Last Answer : Frequency.

Description : How can eddy current loss be minimized?

Last Answer : By laminating the core.

Description : Mention the factors on which hysteresis loss depends?

Last Answer : (i) Quality and amount of iron in the core (ii) Flux density and (iii) Frequency.