Explain about the losses in Transformer?

2 Answers

Answer :

A. As the Transformer is a static device mechanical losses do not come into picture. Transformer losses have two sources-copper loss and core loss. Copper losses are caused by the resistance of the wire (I2R). In primary side it is I12R1 and in secondary side it is I22R2 loss, where I1 & I2 are primary & secondary currents of transformer and R1 & R2 are resistances of primary & secondary winding. As the both primary & secondary currents depend upon load of transformer, copper losses vary with load. Core losses are caused by eddy currents and hysteresis in the core. Eddy current losses: In transformer we supply alternating current in the primary, this alternating current produces alternating magnetizing flux in the core and as this flux links with secondary winding there will be induced voltage in secondary, resulting current to flow through the load connected with it. Some of the alternating fluxes of transformer may also link with other conducting parts like steel core or iron body of transformer etc. As alternating flux links with these parts of transformer, there would be an locally induced  emf. Due to these emfs there would be currents which will circulate locally at that parts of the transformer. This type of energy loss is called eddy current loss of transformer. Hysteresis losses: The magnetic core of transformer is made of Silicon Steel, Steel is very good ferromagnetic material. The domains are arranged inside the material structure in such a manner, that net resultant magnetic field of the said material is zero. Whenever external magnetic field or mmf is is applied to that substance, these randomly directed domains arrange themselves in parallel to the axis of applied mmf. After removing this external mmf, maximum numbers of domains again come to random positions, but some few of them still remain in their changed position. Because of these unchanged domains the substance becomes slightly magnetized permanently. This magnetism is called “Spontaneous Magnetism”. To neutralize this magnetism some opposite mmf is required to be applied. For this reason, there will be a consumption of electrical energy which is known as Hysteresis loss of transformer. Hysteresis loss is constant for a particular voltage and current. Eddy-current loss, however, is different for each frequency passed through the transformer.

Answer :

TRANSFORMER LOSSES - Transformer losses have two sourcescopper loss and magnetic loss. Copper losses are caused by the resistance of the wire (I2R). Magnetic losses are caused by eddy currents and hysteresis in the core. Copper loss is a constant after the coil has been wound and therefore a measurable loss. Hysteresis loss is constant for a particular voltage and current. Eddy-current loss, however, is different for each frequency passed through the transformer.

Related questions

Description : What are the transformer losses?

Last Answer : Answer: TRANSFORMER LOSSES - There are mainly two kinds of losses in a transformer namely 1. Copper loss (ohmic loss) and 2.magnetic loss (core loss). Copper losses are caused by the ... ohmic loss the following two losses are also present in the transformer stray load loss and dielectric loss.

Description : Why are iron losses considered as constant losses in transformer?

Last Answer : Iron losses depend on supply frequency and flux density in the core. For all normal operations, the frequency of flux reversals which is same as supply frequency is constant and the value of flux density ... . Hence iron losses remain constant under all load conditions. i-e from no-load to full-load

Description : 72 Harmonics in transformer result in A. Increased core losses B. Increased I2R losses C. Magnetic interference with communication circuits D. All of the above

Last Answer : D. All of the above

Description : 64)During the short-circuit test on a small transformer the frequency is increased from 50-200Hz. The copper losses will increase by a factor of A. 16 B. 4 C. 1 D. 1/4

Last Answer : A) 16

Description : [53] The iron loss of the transformer is negligible during short circuit test because A. The entire input is just sufficient to meet Cu losses only B. Flux produced is a small fraction of the normal flux C. Iron core becomes fully saturated D. Supply frequency is held constant

Last Answer : B. Flux produced is a small fraction of the normal flux

Description : 48.During light loads, the transformer efficiency is low because A. Secondary output is low B. Transformer losses are high C. Fixed loss is high in proportion to the output D. Cu loss is small

Last Answer : C. Fixed loss is high in proportion to the output

Description : 45 The function of conservator in a transformer is A. To protect against internal fault B. To reduce copper as well as core losses C. To cool the transformer oil D. To take care of the expansion and contraction of transformer oil due to variation of temperature of surroundings

Last Answer : D. To take care of the expansion and contraction of transformer oil due to variation of temperature of surroundings

Description : 43 The purpose of providing an iron core in a transformer is to A.Provide support to windings B. Reduce hysteresis loss C. decrease the reluctance of the magnetic path D. reduce eddy current losses

Last Answer : C. Decrease the reluctance of the magnetic path

Description : 42 The efficiency of a transformer will be maximum when A. copper losses = hysteresis losses B. Hysteresis losses = eddy current losses C. Eddy current losses = copper losses D. Copper losses = iron losses

Last Answer : D. Copper losses = iron losses

Description : 8 The transformer core is laminated to A. Reduce the copper losses B. Reduce the core losses C. Reduce the eddy current losses D. None of the above

Last Answer : C. Reduce the eddy current losses

Description : 13) In an ideal transformer A. windings have no resistance B. core has no losses C. core has infinite permeability D. all of the above

Last Answer : D. All of the above

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : 7 The main advantage of auto transformer over a two winding transformer is A. Hysteresis losses are reduced B. Saving in winding material C. Copper losses are negligible D. Eddy losses are totally eliminated

Last Answer : A) hysteresis losses is reduced

Description : Reduction in core losses and increase in permeability are obtained with transformer employing?

Last Answer : Reduction in core losses and increase in permeability are obtained with transformer employing core built-up of laminations of cold rolled grain oriented steel.

Description : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are?

Last Answer : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are hysteresis and eddy current losses.

Description : Explain about auto transformer?

Last Answer : A. It is type of transformer with only one winding a portion of which is shared by both primary and secondary. Advantages: It is used where transformation ratio differs little from unity. As ... voltage as per out requirements and can smoothly increase or decrease its value as per our requirement.

Description : Explain about the open and short circuit tests on transformer?

Last Answer : A. Open circuit test (No load test) and short circuit test (full load test) are performed on a transformer to determine (i) Equivalent circuit of transformer (ii) Voltage ... determine copper loss in transformer at full load and parameters of approximate equivalent circuit of transformer.

Description : Explain the operation of variable frequency transformer?

Last Answer : A. A variable frequency transformer is used to transmit electricity between two asynchronous alternating current domains. It is a double fed electric machine resembling a vertical shaft hydroelectric ... adjustable phase shifting transformer. It allows control of the power flow between two networks.

Description : Explain the working principle of Transformer?

Last Answer : A. Working principle of Transformer is based on Faraday's Laws of Electromagnetic Induction. If an alternating current is applied to an electric coil, there will be an alternating flux surrounding ... second coil. Therefore emf will be induced in it as per Faraday's laws electromagnetic induction.

Description : At what power maximum efficiency of power transformer and distribution transformer is designed

Last Answer : Maximum efficiency of the transformer is attained at certain load factor (α) when core losses of transformer is equal to the copper losses. PCore loss = α ^2 X PCopper loss From the ... the day. Hence distribution transformers are designed to have maximum efficiency at 50% of the rated full load

Description : What happen when Transformer is given DC supply ?

Last Answer : When DC supply is given to the transformer primary winding no back emf is induced in the transformer. Importance of Back emf is that it limits the current drawn by the machine. In the absence ... in burning down of primary winding. So when dc supply is given to transformer primary windings will burn

Description : During No load why the power factor of the transformer is very low ?

Last Answer : Current flowing through the transformer consists of two components. Magnetizing current (Im) which is in quadrature (90 0 ) to the applied voltage and in phase current which is in phase to the applied voltage ... power factor of transformer during no load condition will by in the order of 0.1 to 0.2

Description : What is the supply rated o/p if two single phase transformer connect to give three phase o/p from a three phase I/p?

Last Answer : A. Each transformer is only capable of supplying 86.6%of its o/p rating

Description : How to connect two single phase transformer to give three phase o/p from a three phase I/p ?

Last Answer : A. They would have to connect in an open-delta.

Description : What is the 3 ph transformer ?

Last Answer : A. A 3ph transformer is that transformer which is equivalent to three single phase transformer but wound on one core and enclosed within one common case.

Description : What parameters or technical particulars are important to be considered while designing protection scheme of the transformer?

Last Answer : 1.Network Diagram showing the position of the transformer in the system 2.kVA or MVA rating of the transformer 3.Fault Level at the transformer 4.Voltage Ratio 5.Winding Connections 6.Per Unit ... Oil Filled 11.Length and area of cross section of the connecting leads between CTs and Relay Panel

Description : What can be the reasons for the failure of the transformer?

Last Answer : Answer: Transformer is one of the most expensive equipments in the Power System. Failure of the transformer can cause outage of power supply for even days. However, multiple things can go wrong with ... relays. 3.Short Circuits 4.Open Circuits 5.Earth Faults 6.Over Voltage 7.Reduced system frequency

Description : How Transformer Protection provided for internal faults?

Last Answer : 1.Bucholz Relay (1st Stage Alarm and 2nd Stage Trip) 2.Sudden Pressure Relay (1st Stage Alarm and 2nd Stage Trip) 3.Pressure Relief Valve (1st Stage Alarm and 2nd Stage Trip) 4.Pressure Switch ... 8.Gas Temperature Indicator (Alarm) 9.Silicon Breather (Passive - no alarm) 10.Smoke Detector (Alarm)

Description : How does change in frequency affect the operation of a given transformer?

Last Answer : a) Iron loss .........increases with a decrease in frequency. A 60-Hz transformer will have nearly 11% higher losses when worked on 50Hz instead of 60 Hz. However, when a 25-Hz ... ....since total loss is greater at a lower frequency, the temperature is increased with decrease in frequency.

Description : Does the transformer draw any current when its secondary is open?

Last Answer : Yes, no-load primary current.

Description : WHAT is ZIG ZAG Grounding Transformer

Last Answer : ANSWER: Three Single Phase Transformers can be connected to have a three phase Zig Zag Transformer. This system can be used for either grounding or developing a fourth WIRE from a three phase neutral. An example ... - three phase - three wire system to a 480Y/277 V - three phase - four wire system

Description : What is Meant by Temperature Rise in a Transformer?

Last Answer : ANSWER: Temperature rise in a transformer is the temper¬ature of the windings and insulation above the existing ambi¬ent or surrounding temperature, and is determined by the insulation class used in the transformer coils.

Description : What is Meant by Regulation in a Transformer?

Last Answer : ANSWER: Voltage regulation in transformers is the difference between the no load voltage and the full load voltage. This is usually expressed in terms of percentage. For example: A transformer delivers 100 ... from 2% to 4%, depending on the size and the application for which they are used

Description : What is Polarity, When Associated With a Transformer?

Last Answer : A: Polarity is the instantaneous voltage obtained from the primary winding in relation to the secondary winding. Transformers 600 volts and below are normally connected in additive polarity - that ... parallel for three phase operations. Polarity is a term used only with single phase transformers

Description : During No load why the power factor of the transformer is very low ?

Last Answer : A. Current flowing through the transformer consists of two components. Magnetizing current (Im) which is in quadrature (900) to the applied voltage and in phase current which is in phase to the applied voltage ... factor of transformer during no load condition will by in the order of 0.1 to 0.2

Description : EMF equation of the transformer?

Last Answer : A. E = 4.44ΦmfN Volts. If E1 & E2 are primary and secondary emf’s and N1 & N2 are primary and secondary turns then, Voltage ratio= E1/E2 and Turns ratio of transformer = N1/N2 E1/E2 = N1/N2

Description : What is tertiary winding? What is Three Winding Transformer? What are its advantages?

Last Answer : A. In some high rating transformers, one winding, in addition to the primary and secondary winding, is used. This is known as Tertiary Winding of Transformer. Because of this third winding, the ... it assists in limitation of fault current in the event of a short circuit from line to neutral.

Description : What is polarity, when associated with a transformer?

Last Answer : A. Polarity is the instantaneous voltage obtained from the primary winding in relation to the secondary winding. Transformers 600 volts and below are normally connected in additive polarity - that ... parallel for three phase operations. Polarity is a term used only with single phase transformers.

Description : Can a Single Phase Transformer be used on a Three Phase source?

Last Answer : A. Any single phase transformer can be used on a three phase source by connecting the primary leads to any two wires of a three phase system, regardless of whether the source is three phase 3-wire or three phase 4 wire. The transformer output will be single phase.

Description : What is meant by regulation in a transformer?

Last Answer : A. Voltage regulation in transformers is the difference between the no load voltage and the full load voltage. This is usually expressed in terms of percentage. Example: A Transformer delivers 100 ... The regulation capacity varies depending on the size and the application for which they are used.

Description : What will happen if DC supply is given on the primary of a transformer?

Last Answer : A. Mainly transformer has high inductance and low resistance. In case of DC supply there is no inductance, only resistance will act in the electrical circuit. So, high electrical current will flow through primary side of the transformer. Due to this the coil and insulation will burn out.

Description : What is voltage ratio of a transformer?

Last Answer : A. Voltage ratio is the ratio of the voltage between the line terminals of one winding to that between the line terminals of another winding at no load.

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer : A. As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : What is the function of transformer oil?

Last Answer : A. Transformer Oil serves mainly two purposes 1. It acts as liquid insulation in electrical power transformer 2. It dissipates heat of the transformer i.e acts as coolant. In addition to these ... acid (C7, C8) esters are also becoming increasingly common as alternatives to naphthenic mineral oil.

Description : What is the difference between delta-delta, delta-star transformer?

Last Answer : A. Delta-delta transformer is used at generating station or a receiving station for Change of Voltage (i,e) generally it is used where the Voltage is high & Current is low whereas Delta-star ... star neutral is taken as a return path and this configuration is used for Step down voltage phenomena.

Description : What current flows in the transformer primary when its secondary is open?

Last Answer : A. When the secondary is open, there is no current in the secondary of the transformer. The primary takes a small current I0) from the source called no-load current which has a magnetizing ... ) producing the magnetic flux and a working component (I0 cosθ0) supplying real power for iron losses.

Description : What is an ideal transformer?

Last Answer : A. Transformer having an overall efficiency of 100 per cent is called an ideal transformer.

Description : In a Tap changing transformer on which side is the tap connected, primary side or secondary side?

Last Answer : A. Tapings are always connected to high voltage winding side, because of low current. If we connect tapings to low voltage side, sparks will produce while tap changing operation due to high current.

Description : What is an isolation transformer?

Last Answer : A. An isolation transformer also referred to as insulating transformer, is one where the primary and secondary windings are separate.