Why Delta Star Transformers are used for Lighting Loads?

1 Answer

Answer :

A. For lighting loads, neutral conductor is must and hence the secondary must be star winding.This lighting load is always unbalanced in all three phases. To minimize the current unbalance in the primary we use delta winding in the primary. So delta / star transformer is used for lighting loads.

Related questions

Description : Why Delta Star Transformers are used for Lighting Loads?

Last Answer : For lighting loads, neutral conductor is must and hence the secondary must be star winding and this lighting load is always unbalanced in all three phases.  To minimize the current unbalance in the primary we use delta winding in the primary So delta / star transformer is used for lighting loads.

Description : Why Delta Star transformer Are Used For Lighting Loads?

Last Answer : For lighting loads, neutral conductor is must and hence the secondary must be star winding. and this lighting load is always unbalanced in all three phases. To minimize the current unbalance in the primary we use delta winding in the primary. So delta / star trformer is used for lighting loads.

Description : What advantage has the star connection over the delta connection ?

Last Answer : A. Each star connection transformer is wound for only 57.7% of line voltage . In hv transmission, this admits of much smaller transformer being built for high voltage than possible with delta connection, because of less insulation.

Description : What is the difference between delta-delta, delta-star transformer?

Last Answer : A. Delta-delta transformer is used at generating station or a receiving station for Change of Voltage (i,e) generally it is used where the Voltage is high & Current is low whereas Delta-star ... star neutral is taken as a return path and this configuration is used for Step down voltage phenomena.

Last Answer : Star/star transformers work satisfactorily when load is balanced .

Description : If an unsymmetrical line to ground fault occurs at the secondary terminals of a delta/star, ungrounded transformer, then  (A) zero sequence currents are present on both sides of the transformer  (B) ... side  (D) zero sequence currents are present on the primary side but not on the secondary side

Last Answer : If an unsymmetrical line to ground fault occurs at the secondary terminals of a delta/star, ungrounded transformer, then zero sequence currents are absent on both sides of the transformer 

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Last Answer : Delta/star transformer works satisfactorily when on balanced as well as unbalanced loads.

Description : Why Silica gel is used in transformers?

Last Answer : Silica Gel is used to remove the moisture in the air entering in to the transformer. During the breathing of the transformer air enters in to the transformer. This air makes contact with the hot ... Silica gel crystals will be in blue color initially and after absorbing moisture it turns to pink.

Description : What are the conditions for parallel operation of two transformers ?

Last Answer : Transformers which are to be operated parallel should have to satisfy the following conditions: Polarities of both the transformers should be same else lead to short circuit Voltage rating of ... Phase displacement of transformers should be same Phase sequence of two transformers should be same

Description : What is the significance of vector grouping in Power Transformers?

Last Answer : Answer:Every power transformer has a vector group listed by its manufacturer. Fundamentally it tells you the information about how the windings are connected (delta or wye) and the phace difference betweent ... Delta primary, Wye Secondry and the current is at 11 o clock reffered to the voltage.

Description : How is magnetic leakage reduced to a minimum in commercial transformers?

Last Answer : By interleaving the primary and secondary windings.

Description : What are the conditions for parallel operation of two transformers ?

Last Answer : Transformers which are to be operated parallel should have to satisfy the following conditions: Polarities of both the transformers should be same else lead to short circuit Voltage rating of ... Phase displacement of transformers should be same Phase sequence of two transformers should be same

Description : Can Transformers be Reconnected as Autotransformers to Increase Their KVA Rating?

Last Answer : ANSWER: Several of standard single phase transformers can be connected as autotransformers. The KVA capacity will be greatly increased when used as an Autotransformer, in comparison to the ... This voltage is normally used for operating fluorescent lamps or similar devices requiring 277 volts

Description : What is BIL and How Does it Apply to our Transformers ?

Last Answer : ANSWER: BIL is an abbreviation for Basic Impulse Level. Impulse tests are dielectric tests that consist of the applica¬tion of a high frequency steep wave front voltage between windings ... breakdowns when his system is properly protected with lightning arrestors or similar surge protection devices.

Description : What is Meant by "Impedance" in Transformers?

Last Answer : ANSWER: Impedance is the current limiting characteristic of a transformer and is expressed in percentage.

Description : Can 60 Hz Transformers be Used at Higher Frequencies?

Last Answer : A: Transformers can be used at fre¬quencies above 50 Hz up through 400 Hz with no limitations provided nameplate voltages are not exceeded. However, 50 Hz transformers will have less voltage ... Where better regulation and smaller physical size are required, contact us for special 400 Hz designs.

Description : What are the Conditions for parallel operation of transformers?

Last Answer : A. a) Same voltage ratio of transformer: If two transformers of different voltage ratio, are connected in parallel with same primary supply voltage, there will be a difference in secondary voltages. If ... not in same phase sequence, during the cycle, each pair of phases will be short circuited.

Description : What are the advantages of parallel operation of transformers?

Last Answer : A. 1) To maximize electrical power system efficiency: Generally electrical power transformer gives the maximum efficiency at full load. If we run numbers of transformers in parallel, we can switch ... running in parallel can be removed from system to balance the capital investment and its return.

Description : Can the transformers be used at higher frequencies than rated frequency?

Last Answer : A. Yes. Transformers can be used at higher frequencies than rated frequency. However as the frequency increases voltage regulation decreases.

Description : What is meant by “impedance” in transformers? Why is it important?

Last Answer : A. Impedance is the current limiting characteristic of a transformer and is expressed in percentage. It is used for determining the interrupting capacity of a circuit breaker or fuse employed to protect the primary of a transformer

Description : Can Single Phase Transformers be used for Three Phase applications?

Last Answer : A. Yes. Three phase transformers are sometimes not readily available whereas single phase transformers can generally be found in stock. Three single phase transformers can be used in delta connected primary and ... K VA single phase transformers can be used to accommodate a 30 KVA three phase load.

Description : Can Transformers develop Three Phase power from a Single Phase source?

Last Answer : A. NO. Phase converters or phase shifting devices such as reactors and capacitors are required to convert single phase power to three phase.

Description : What is the significance of vector grouping in Power Transformers?

Last Answer : A. Every power transformer has a vector group listed by its manufacturer. Fundamentally it tells you the information about how the windings are connected (delta or wye) and the phase difference between the ... Delta primary, Wye Secondary and the current is at 11 o clock referred to the voltage.

Description : What are the types of cooling systems it transformers?

Last Answer : A. 1. ONAN (oil natural, air natural) 2. ONAF (oil natural, air forced) 3. OFAF (oil forced, air forced) 4. ODWF (oil direct, water forced) 5. OFAN (oil forced, air forced)

Description : How do you classify transformers based on construction?

Last Answer : A. Based on construction transformers are of two types. They are distinguished from each other based on merely the manner by which primary and secondary windings are placed around the core. ... surrounds considerable part of windings. Another recent development is wound core type or spiral core.

Description : Why do transformers hum?

Last Answer : Transformer noise is caused by a phenomenon which causes a piece of magnetic sheet steel to extend itself when magnetized. When the magnetization is taken away, it goes back to its original condition ... core. The degree of flux determines the amount of magnetostriction and hence, the noise level.

Description : Why we need isolation transformers in power circuit ? why cant we use breakers to isolate?

Last Answer : In Isolation transformer is used, if there is change in parameter values of any side, the other side parameters will remain unchanged.

Description : Is it Possible to Change Three Phase to Two Phase or Vice-Versa with Standard Transformers?

Last Answer : Yes. This is a very practical application for standard single phase off-the-shelf transformers. Some typical voltage combinations are as follows: 480 volts three phase to 240 volts two phase, or 240 volts ... 240 volts three phase to 240 volts two phase. Please refer to us for an exact schematic.

Description : Can 60 Hz transformers be operated at 50 Hz?

Last Answer : The transformers rated below 1 KVA can be used on 50 Hz service. Transformers 1 KVA and larger, rated at 60 Hz, should not be used on 50 Hz service, due to the higher losses and resultant heat ... designs are required for this service. However, any 50 Hz transformer will operate on a 60 Hz service.

Description : Can Transformers be Operated at Voltages other than Nameplate Voltages?

Last Answer : In some cases, transformers can be operated at voltages below the nameplate rated voltage. In NO case should a transformer be operated at a voltage in excess of its name- plate rating unless taps are ... 10 KVA, the reduced rating would be 5 KVA, or in direct proportion to the applied voltage.

Description : What is the Difference Between "Insulating", "Isolating", and "Shielded Winding" Transformers?

Last Answer : Insulating and Isolating transformers are identical. These terms are used to describe the isolation of the primary and secondary windings, or insulation between the two. A shielded winding transformer, ... are connected to each other electrically, are not of the insulating or isolating variety.

Description : List some methods of cooling of transformers.

Last Answer : A:Air natural, Air blast, Oil Natural, Oil natural air forced, Oil natural water forced, Oil forced, Oil forced air natural, Oil forced air natural, Oil forced water forced.

Description : In transformers, why the low voltage winding is placed near the core?

Last Answer : The winding & Core are both made of metals and so an insulation have to be placed in between them, the thickness of insulation depends on the voltage rating of the winding. In order to reduce the insulation requirement the low voltage winding place near the core.

Description : Mention the properties of oil used in transformers.

Last Answer : The following are the desirable properties of transformer oil: -->It should be free from moisture --> It should have high dielectric strength --> It should have thermally stability and higher thermal conductivity -->It should be contaminated by temperature rise.

Description : Why are breathers used in transformers ?

Last Answer : Breathers are used to entrap the atmospheric moisture and thereby not allowing it to pass on to the transformer oil. Also to permit the oil inside the tank to expand and contract as its temperature increases and decreases. Also to avoid sledging of oil i.e. decomposition of oil.

Description : Why the range of efficiency in transformers higher than those of other electrical machines?

Last Answer : Transformers operate at higher efficiency when compared to other electrical machines.This is due to the absence of mechanical losses which is due to the absence of moving parts

Description : What is the range of efficiency of transformers?

Last Answer : A:The efficiency of the transformer will be in the range of 94% to 99%. Among the available electrical machines the transformer has the highest efficiency

Description : why transformers are rated in kVA ?

Last Answer : A:Copper loss of a transformer depends on current and iron loss on voltage . Hence total losses depends on Volt- Ampere and not on the power factor. That is why the rating of transformers are in kVA and not in kW.

Description : What is yoke section of transformers?

Last Answer : The sections of the core which connect the limbs are called yoke. The yoke is used to provide a closed path for the flux.

Description : What are isolation transformers?

Last Answer : In this type of transformer the primary and secondary are same. When it is required to isolate the primary and secondary circuits these type of transformers are used. It protects the circuits connected in secondary side when major fault occurs in primary side.

Description : What are step down transformers?

Last Answer : They step up voltage from higher value to lower value.

Description : What are step up transformers?

Last Answer : They step up voltage from lower value to higher value.

Description : What are the advantages of shell type transformer over core type transformers?

Last Answer : In shell type transformers the coils are well supported on the all sides and so they can withstand higher mechanical stresses developed during short circuit conditions. Also the leakage reactance will be less in shell type transformers.

Description : What are the various types of Transformers?

Last Answer : Based on supply 1.Single phase transformer 2.Three phase transformer Based on winding 1.Auto transformer (single winding) 2.Two winding transformer 3. Three winding transformer 4. Six ... transformer Based on function 1. Step up transformer 2.Step down transformer 3.Isolation transformer

Description : Can DC be applied to transformers ?

Last Answer : No i) Transformer works on Faraday's law of Electromagnetic Induction for which current in coil must change. If DC is applied current will not change and transformer will not work. ii) Practically ... is zero. Therefore impedance is low. Thus winding draws more current which may damage the winding.

Description : What is the advantage is obtained in the delta connection ?

Last Answer : A. When three transformer are obtained in delta, one may be removed and two remaining unit will carry 57.7% of the original three phase load and thus maintain the continuity of supply.

Description : 48.During light loads, the transformer efficiency is low because A. Secondary output is low B. Transformer losses are high C. Fixed loss is high in proportion to the output D. Cu loss is small

Last Answer : C. Fixed loss is high in proportion to the output

Description : The efficiency of a transformer, under heavy loads, is comparatively low because?

Last Answer : The efficiency of a transformer, under heavy loads, is comparatively low because copper loss becomes high in proportion to the output.

Description : 76 The changes in volume of transformer cooling oil due to variation of atmospeheric temperature during day and night is taken care of by which part of transformer? A. Conservator B. Breather C. Bushings D. Buchholz relay

Last Answer : A. Conservator