Locations where Gas Insulated Substation is preferred

1 Answer

Answer :

Gas Insulated Substations are preferred in the places where land requirement for the substation is difficult such as in populated areas and highly polluted areas where outdoor switchyard is not preferred. In Gas Insulated Substations all the switching electrical equipment such as circuit breakers, isolators, earth switches, and busbars are completely enclosed inside modules which are filled with SF6 gas. These modules are factory made and site assembled. Hence takes very little time for commissioning compared to air insulated substations.

The main advantage of this  Gas Insulated Substation is because of its compact size due to high dielectric strength of the SF6 gas. And the availability and reliability of the GIS substations are more compared to air insulated substations (Faults occurring chances of Air insulated substation or conventional substations are more. Hence GIS substations are provided where high reliability of electric power is required such as nuclear plants and  and other important facilities where un interruption of power is more required.
Some of the places where Gas insulated substations are preferred are:
Large towns where space available is limited
Industrial complexes where un interruption of power is necessarily
Mountain regions and valleys
Underground substations
Off-shore (On sea or lake) substations
HVDC transmission system terminal substations
In large cities area for commissioning an ordinary Air insulated substation is difficult because of the lack of space available. In such conditions GIS substations out rule the ordinary substation. However it is to be considered that GIS substation requires high capital cost compared to ordinary substation.
Off shore and highly polluted areas where equipment present in the outdoor will be corroded due to the pollution and saline environment. Under such case indoor GIS substation is very much helpful.

Related questions

Description : Which of the device is employed in substation to limit the short circuit current in the power system: a) Shunt condenser b) Reactor c) Series capacitor d) Shunt capacitor

Last Answer : Ans: B

Description : In order to improve the power factor ___ device is employed in the substation a) Synchronous condenser b) Synchronous reactor c) Series Capacitors d) None of the above

Last Answer : Ans: A

Description : Stones are provided in the substation to: a) To avoid fire accident by draining oil from transformer if leaks b) To avoid growing of weeds and plants c) To provide insulation d) All the above

Last Answer : Ans: D

Description : What is the first equipment of the substation connected to the incoming transmission line?

Last Answer : Lightning arrestor is the first equipment of the substation connecting the incoming transmission lines. It protects other substation equipment from lightning and switching surges by suppressing them to ... between both the ends of major equipment such as power transformers for protection.

Description : What are different Bus bar materials used in Substation?

Last Answer : Busbars are generally made of copper and Aluminum. Aluminim has the advantage of one third the weight of the copper and also Aluminum requires less maintenance and proper use of alloys provide necessary rigidity required for bus material. Aluminum is used widely in EHV and HV stations

Description : What are the different electrical clearances in Substation?

Last Answer : Ground Clearance: This is the minimum distance between any live conductor and the earth or ground. Phase Clearance: It is the clearance between the different phases in a circuit or same phases in different ... The limits of work section may be ground or the platform on which the person is working.

Description : What are the different substation components

Last Answer : Circuit Breakers, Disconnecting switches, Grounding switches, Current Transformers, Potential Transformers or Capacitor voltage Transformers, Line Traps, Lightning Arrestors, Power Transformers, Shunt ... Station Buses and Insulators, Grounding system, Series capacitors and shunt capacitors.

Description : What are different insulators used in substation

Last Answer : Different Insulators: Over head electrical conductors used for transmitting electric power is mostly bare and not covered with any insulation medium. The bare line conductors are ... Post insulators for support Stray arm insulators Shaft insulators Sectionalising insulators Connecting rod insulators

Description : Gas Insulated Substations Advantages Disadvantages

Last Answer : Gas Insulated Substations (GIS): Gas Insulated Substations (GIS) are differ from Air Insulated Substations (substations we usually see) such that all the substation equipment such as busbars, circuit breakers ... in the pressure of the SF6 gas in any module results in flash overs and faults

Description : On some electrical generating equipment one outboard bearing pedestal is insulated from the bedplate. To check this insulation with the machine assembled you should use a____________. A. millivolt meter and a jumper B. ohmmeter C. megohm meter D. high potential tester

Last Answer : Answer: A

Description : On some electrical generating equipment one outboard bearing pedestal is insulated from the bedplate. To check this insulation with the machine assembled you should use a____________. A. ohmmeter with the ... C. megohm meter with the machine running D. voltmeter and ampmeter with the machine running

Last Answer : Answer: B

Description : One of the generator bearing shells is generally insulated from the end housing in order to prevent _____________. A. rapid brush wear B. residual magnetism leak off C. excessive field winding heat D. circulation of shaft currents

Last Answer : Answer: D

Description : One of the generator or motor bearings is generally insulated from the end housing in order to prevent ________. A. rapid brush wear B. current leakage from the shaft C. excessive field winding heat D. circulation of shaft currents induced in the machine's frame

Last Answer : Answer: D

Description : When changing fuses and the spring clips are found to have lost their grip, they should be replaced or _____________. A. tightened firmly with insulated pliers B. clip clamps should be used C. wired closed with uninsulated, varnished copper wire D. carefully bent back to their original shapes

Last Answer : Answer: B

Description : When replacing fuses, always make sure _______________. A. to stand on a rubber mat and use rubber gloves B. to use insulated pliers or screwdriver C. the fuse clips are straight, tight, and in good contact D. to increase the fuse rating 10% to guard against 'nuisance blowing'

Last Answer : Answer: C

Description : When a transformer is used to step down voltage, the low voltage winding is _____________. A. part of the core B. the primary coil C. not insulated D. the secondary coil

Last Answer : Answer: D

Description : Before touching a small capacitor connected to a de-energized circuit, or even one that is completely disconnected, you should ____________. A. gently tap the body with a screwdriver B. tag it ... insulated fuse puller D. short circuit the terminals to make sure that the capacitor is discharged

Last Answer : Answer: D

Description : In an impressed current cathodic protection system, the anode is ____________. A. connected to the hull and deteriorates with time B. insulated from the hull and does not waste away C. connected to the hull but does not waste away D. insulated from the hull but deteriorates with time

Last Answer : Answer: B

Description : A 'dead front' switchboard is one _____________. A. without switches on it B. with insulated switches and no exposed terminals C. without circuit breakers D. without safety hand rails nor rubber mats

Last Answer : Answer: B

Description : A tubular fuse should always be removed from a fuse panel with _____________. A. a screwdriver B. a pair of insulated metal pliers C. any insulated object D. fuse pullers

Last Answer : Answer: D

Description : To properly use a hook-on-type volt/ammeter to check current flow, you must FIRST _____________. A. de-energize the circuit to allow connection of the instrument in series B. hook the jaws ... test leads to the appropriate terminals D. short the test leads and calibrate the instrument to zero

Last Answer : Answer: B

Description : What are the advantages of PVC insulated cable? 

Last Answer : a. Plumbing is not required. Joints can be made easily. b. As PVC is light the injury caused to it while laying is less. c. It is corrosion resistant. d. It has high fire retarding property. e. It does not break down even if moisture enters. 

Description : Define insulated wire. 

Last Answer : Insulated wire: A conductor or multi-stranded conductor which has a insulating material on it is called a insulated wire. 

Description : Define unprotected insulated wire. 

Last Answer : Unprotected insulated wire: Unprotected insulated wire is which the insulation of the wire is not covered by a protective sheathing to prevent it from mechanical damage. 

Description : What are the parts of paper insulated lead covered cable?

Last Answer : a. Core. b. Insulation of cable. c. Metallic sheath. d. Bedding. e. Armouring. f. Serving.

Description : For LV applications (below 1 kV), ______________ cables are used. (A) Paper insulated. (B) Plastic. (C) Single core cables. (D) Oil filled.

Last Answer : Ans: C For low voltage applications single core cables are suitable.

Description : In a substation the following equipment is not installed (a) exciters (b) series capacitors (c) shunt reactors (d) voltatre transformers

Last Answer : (a) exciters

Description : Draw a block diagram of WPP substation. State function of each block.

Last Answer : Block Diagram of WPP Substation: OR Wind Turbine : Converts wind power to rotational mechanical energy Gear Box: Transfer low speed to high. Generator: Converts rotational ... to DC and vice-versa of correct frequency. Transformer: Step up the voltage to grid level.

Description : State the condition for selecting site for distribution substation. 

Last Answer : Following condition should be considered while selecting site for distribution sub-station:-  1. Near load center :  Sub-station should be located near load center to reduce cost of Transmission and ... free from earthquake :  To avoid damage to sub-station area should be free earth quake. 

Description : State significance of earthing. Draw and explain pipe earthing. State the values of earth resistances for : (i) Substation (ii) Residential wiring (iii) H.T. Line (iv) L.T. Line

Last Answer : Significance of earthing:  * Earthing means connecting the body of the electrical equipment (it means the part which does not carries current under normal condition) to the earth. For example electrical equipment' ... surrounded by charcoal and salt.  the values of earth resistances for: 

Description : State the classification of distribution substation. 

Last Answer : The classification of distribution substation. 1. Pole mounted distribution substation 2. Plinth mounted distribution substation 3. Compact/prefabricated distribution substation 4. ... Indoor distribution substation 6. Outdoor distribution substation 7. Mobile distribution substation 

Description : What is the purpose of auxiliary controller in substation?

Last Answer : The systems of substation auxiliaries ensure operation of substations providing internal consumers of substations with operating direct and alternating currents. Any breakdown (loss) of auxiliary systems ... whole substation, as well as serious problems during its subsequent putting into operation.

Description : Classification of Substation According to Method of Construction

Last Answer : Classification of Substation According to Method of Construction:- 1. Indoor Substation 2. Outdoor Substation 3. Gas insulated Substation 4. Underground Substation 5. Pole mounted substation 6. Plinth Substation 7. Compact/prefabricated substation

Description : Write down the circuit breaker with their rating used in traction substation. Explain any one.

Last Answer : Circuit Breaker With Their Rating Used in Traction Substation: Rated capacity of a circuit breaker is 750Amps at 25 kV, 500MVA. Its overall tripping time is 0.14 seconds composed of 0.04 ... but in case of traction substation application, mostly Minimum Oil Circuit Breaker (MOCB) is preferred.

Description : Isolator in substation is open under ___________ condition?  (A) No load (B) Short circuit (C) Full load (D) None of the above

Last Answer : no load

Description : Distributed under Creative Commons Attribution-ShareAlike - CC BY-SA.

Last Answer : Some important components/equipments in substation  As told earlier, the function of a substation is to receive power at some voltage through incoming lines and transmit it at some other voltage through ... range ammeter to indicate the line current. Version 2 EE IIT, Kharagpur 

Description : What does a substation do?

Last Answer : At  the  substations,  power  is  boosted  up  for  long  distance  transmission.

Description : Pick out the correct statement. (A) If an insoluble gas is passed through a volatile liquid placed in a perfectly insulated container, the temperature of the liquid will increase (B) A ... compound is defined as the heat of reaction leading to the formation of the compound from its reactants

Last Answer : (D) The heat of formation of a compound is defined as the heat of reaction leading to the formation of the compound from its reactants

Description : 1m3 of an ideal gas at 500 K and 1000 kPa expands reversibly to 5 times its initial volume in an insulated container. If the specific heat capacity (at constant pressure) of the gas is 21 J/mole . K, the final temperature will be (A) 35 K (B) 174 K (C) 274 K (D) 154 K

Last Answer : (C) 274 K

Description : An ideal gas is compressed in a cylinder so well insulated that there is essentially no heat transfer. The temperature of gas  a. Remains constant  b. increases  c. decreases  d. is basically zero

Last Answer : increases

Description : Cables for 220 kV lines are invariably (a) mica insulated (b) paper insulated (c) compressed oil or compressed gas insulated (d) rubber insulated (e) none of the above

Last Answer : (c) compressed oil or compressed gas insulated

Description : Wire in general, when used aboard vessels must meet minimum requirements. Which of the following statements is/are correct? A. Each wire must be 14 AWG or larger, regardless of locations and use. B. ... enclosure or cover is the ground wire used with portable tools and lights. D. All of the above.

Last Answer : Answer: B

Description : As shown in the illustration, what is the meaning of the numbers in brackets [ ] at location '31/33U'? EL-0100 A. Four separate devices with these part numbers feed signals into this point. ... continues on those four pages and connects to devices at the indicated coordinates. D. None of the above.

Last Answer : Answer: C

Description : The Aldi grocery store, do they sell gas at any of their locations that you know of?

Last Answer : In Illinois there are called box stores, cut rate cheap groceries, no bags, no gas, no anything else.

Description : An auto transformer is preferred over an ordinary two winding transformer due to: a) Safety of operation b) Availability of taps on secondary c) Copper savings d) All the above

Last Answer : Ans: C

Description : Why Negative Feedback is preferred in the Control System?

Last Answer : The role of Feedback in control system is to take the sampled output back to the input and compare output signal with input signal for error ( deviation from the desired result). ... and is less sensitive to the parameter variations. Hence in control systems negative feedback is considered.

Description : Why thyristors are not preferred for inverters?

Last Answer : Thyristors require extra commutation circuits for turn off which resulting Increased complexity of the circuit. For these reasons thyristors are not preferred for inverters.

Description : Which type of winding is preferred for armature windings of alternator? Why?

Last Answer : Double layer, short pitched and distributed type of armature winding. It eliminates high frequency harmonics hence it makes induced emf more sinusoidal.