What is the first equipment of the substation connected to the incoming transmission line?

1 Answer

Answer :

Lightning arrestor is the first equipment of the substation connecting the incoming transmission lines. It protects other substation equipment from lightning and switching surges by suppressing them to ground. Lightning arrestors also placed in the substation between both the ends of major equipment  such as power transformers for protection.

Related questions

Description : What are different Bus bar materials used in Substation?

Last Answer : Busbars are generally made of copper and Aluminum. Aluminim has the advantage of one third the weight of the copper and also Aluminum requires less maintenance and proper use of alloys provide necessary rigidity required for bus material. Aluminum is used widely in EHV and HV stations

Description : What are the different electrical clearances in Substation?

Last Answer : Ground Clearance: This is the minimum distance between any live conductor and the earth or ground. Phase Clearance: It is the clearance between the different phases in a circuit or same phases in different ... The limits of work section may be ground or the platform on which the person is working.

Description : What are the different substation components

Last Answer : Circuit Breakers, Disconnecting switches, Grounding switches, Current Transformers, Potential Transformers or Capacitor voltage Transformers, Line Traps, Lightning Arrestors, Power Transformers, Shunt ... Station Buses and Insulators, Grounding system, Series capacitors and shunt capacitors.

Description : State the condition for selecting site for distribution substation. 

Last Answer : Following condition should be considered while selecting site for distribution sub-station:-  1. Near load center :  Sub-station should be located near load center to reduce cost of Transmission and ... free from earthquake :  To avoid damage to sub-station area should be free earth quake. 

Description : State the classification of distribution substation. 

Last Answer : The classification of distribution substation. 1. Pole mounted distribution substation 2. Plinth mounted distribution substation 3. Compact/prefabricated distribution substation 4. ... Indoor distribution substation 6. Outdoor distribution substation 7. Mobile distribution substation 

Description : What is the purpose of auxiliary controller in substation?

Last Answer : The systems of substation auxiliaries ensure operation of substations providing internal consumers of substations with operating direct and alternating currents. Any breakdown (loss) of auxiliary systems ... whole substation, as well as serious problems during its subsequent putting into operation.

Description : Classification of Substation According to Method of Construction

Last Answer : Classification of Substation According to Method of Construction:- 1. Indoor Substation 2. Outdoor Substation 3. Gas insulated Substation 4. Underground Substation 5. Pole mounted substation 6. Plinth Substation 7. Compact/prefabricated substation

Description : Isolator in substation is open under ___________ condition?  (A) No load (B) Short circuit (C) Full load (D) None of the above

Last Answer : no load

Description : What does a substation do?

Last Answer : At  the  substations,  power  is  boosted  up  for  long  distance  transmission.

Description : Why EHV busbars are hallowed and circular?

Last Answer : Answer: To avoid corona effect

Description : Factors on which material of station busbar depends?

Last Answer : Some of the factors on which station busbar depends are: Current Carrying capacity Short Circuit Stresses Establishing minimum electrical clearances

Description : For distribution network which type of Switching scheme is employed?

Last Answer : For distribution network Ring Main busbar scheme is employed. It has the provision that if power interruption occurs to one bus section due to maintenance or fault, power can be fed the bus from other side of the power system.

Description : Which type of bus arrangement is costlier and more reliable?

Last Answer : One and half breaker scheme is most reliable and costlier scheme. In one and half breaker scheme 3 circuit breakers are provided for 2 bus-bars. Hence the name is coined as One and half breaker scheme

Description : What are different types of busbar arrangement Schemes in Substations?

Last Answer : Different switching schemes or busbar arrangement scheme employed in switch-yard are: Single Bus Scheme Double bus single breaker scheme Main and Transfer busbar scheme Double bus single breaker scheme Breaker and half scheme Ring main bus scheme

Description : What is the neutral point earthing and its advantages?

Last Answer : In substation all the neutrals of rotating machines, transformers, busbars and other equipment are connected to ground. Some of the advantages are: Earth fault protection is based on the method of ... , grounding of neutral helps to reduce the over-voltages which occur on the one healthy phases

Description : What is the significance of Corona rings in substations?

Last Answer : It is observed that corona discharge occurs mostly at sharp corners, edges near the conductor fixing points. Corona rings also called grading rings are hallow metallic rings having large diameter ... is reduced to much lower value Corona discharge is eliminated Dust deposition is also minimized

Description : What are the disadvantages of corona?

Last Answer : Some of the disadvantages of corona are: Corona causes power loss Corona causes unacceptable noise Corona cause radio interference

Description : What is Basic Impulse Level (BIL)?

Last Answer : Basic Impulse Level (BIL) refer to the peak value of lightning impuse voltage withstand capability of the equipment

Description : What is creepage distance?

Last Answer : Creepage distance is the shortest distance between two conducting points along the surface of the insulating material.

Description : What are different insulators employed in substations?

Last Answer : Some of the insulators employed in substations are: Pin insulators Post insulators Strain insulators Suspension insulators Hallow apparatus insulators Dead-end insulators Solid core insulators

Description : In a substation the following equipment is not installed (a) exciters (b) series capacitors (c) shunt reactors (d) voltatre transformers

Last Answer : (a) exciters

Description : Which of the device is employed in substation to limit the short circuit current in the power system: a) Shunt condenser b) Reactor c) Series capacitor d) Shunt capacitor

Last Answer : Ans: B

Description : In order to improve the power factor ___ device is employed in the substation a) Synchronous condenser b) Synchronous reactor c) Series Capacitors d) None of the above

Last Answer : Ans: A

Description : Stones are provided in the substation to: a) To avoid fire accident by draining oil from transformer if leaks b) To avoid growing of weeds and plants c) To provide insulation d) All the above

Last Answer : Ans: D

Description : Locations where Gas Insulated Substation is preferred

Last Answer : Gas Insulated Substations are preferred in the places where land requirement for the substation is difficult such as in populated areas and highly polluted areas where outdoor switchyard is not ... pollution and saline environment. Under such case indoor GIS substation is very much helpful.

Description : What are different insulators used in substation

Last Answer : Different Insulators: Over head electrical conductors used for transmitting electric power is mostly bare and not covered with any insulation medium. The bare line conductors are ... Post insulators for support Stray arm insulators Shaft insulators Sectionalising insulators Connecting rod insulators

Description : Why is it a good practice to have the frequency of the incoming alternator adjusted slightly higher than that of the loaded alternator when paralleling two alternators? A. This allows the oncoming machine to ... line. C. The reverse power relay is prevented from activating. D. All of the above.

Last Answer : Answer: D

Description : An alternator is being paralleled with one on the line. At the INSTANT the circuit breaker is closed, the frequency of the incoming alternator will normally _____________. A. increase B. not change C. decrease D. be exactly 60 hertz

Last Answer : Answer: C

Description : Prior to closing the breaker when paralleling two AC generators, the recommended practice is to have the frequency of the incoming machine _____________. A. slightly less than the line frequency B. the same as the line frequency C. slightly greater than the line frequency D. all of the above

Last Answer : Answer: C

Description : When paralleling two AC generators, the frequency (cycles) of the incoming generator, just prior to closing the circuit breaker, should be _____________. A. slightly less than the frequency of the generator on ... C. slightly more than the frequency of the generator on the line D. all of the above

Last Answer : Answer: C

Description : State significance of earthing. Draw and explain pipe earthing. State the values of earth resistances for : (i) Substation (ii) Residential wiring (iii) H.T. Line (iv) L.T. Line

Last Answer : Significance of earthing:  * Earthing means connecting the body of the electrical equipment (it means the part which does not carries current under normal condition) to the earth. For example electrical equipment' ... surrounded by charcoal and salt.  the values of earth resistances for: 

Description : Which of the following problems will occur if the circuit breaker of the incoming alternator is closed and it is 180° out of phase with the loaded alternator when paralleling? A. The rotor of the ... The rotor of the incoming alternator will stop. D. Both alternators will parallel 180° out of phase.

Last Answer : Answer: B

Description : An equalizing connection between two compound-wound DC generators when paralleled, serves to _____________. A. reverse the polarity of the incoming generator as the series field weakens B. automatically ... the series field of the incoming generator D. parallel the series fields of the generators

Last Answer : Answer: D

Description : When paralleling two AC generators, the frequency of the incoming machine immediately prior to closing its breaker should be ____________. A. controlled by placing the governor switch in the automatic ... regulator C. slightly greater than the bus frequency D. slightly less than the bus frequency

Last Answer : Answer: C

Description : When paralleling two alternators, the synchronizing lamps remain lit as the synchroscope pointer approaches the 0°. This indicates the _____________. A. incoming alternator is running too fast B. alternator ... apart C. synchroscope is defective or broken D. alternator power factors are in phase

Last Answer : Answer: C

Description : When paralleling two alternators the synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates the ____________. A. alternator voltages ... alternator is in phase with the bus voltage D. synchroscope pointer is defective or broken

Last Answer : Answer: C

Description : When paralleling two alternators using three synchronizing lamps, the flickering of all three lamps becomes progressively slower and slower. This means the ______________. A. frequency of the incoming ... the bus D. terminal voltage of the incoming alternator is approaching that of the bus

Last Answer : Answer: A

Description : If the pointer of the synchroscope is rotating in the slow direction when you are preparing to parallel two alternators, the _____________. A. incoming machine is turning faster than the load alternator B ... alternator is ready to split D. incoming machine is beginning to pick up some of the load

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving fast in the clockwise direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... at any pointer position D. the same as the bus frequency but out of phase with it

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving in the fast direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... the same as the bus frequency and the circuit breaker may be closed at any pointer position

Last Answer : Answer: A

Description : You are paralleling two alternators. The synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates that the ____________. A. alternator ... be closed C. incoming alternator is running too slowly D. synchroscope is defective or broken

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0° prior to closing the circuit breaker. This indicates ___________. A. the frequency of ... be closed after breaker has been reset D. there is an existing cross current between generators

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer is revolving in the slow direction. This indicates that the frequency of the incoming machine is _____________. A. higher than ... same as the bus frequency, and the circuit breaker may be closed at any pointer position

Last Answer : Answer: B

Description : Draw a block diagram of WPP substation. State function of each block.

Last Answer : Block Diagram of WPP Substation: OR Wind Turbine : Converts wind power to rotational mechanical energy Gear Box: Transfer low speed to high. Generator: Converts rotational ... to DC and vice-versa of correct frequency. Transformer: Step up the voltage to grid level.

Description : Write down the circuit breaker with their rating used in traction substation. Explain any one.

Last Answer : Circuit Breaker With Their Rating Used in Traction Substation: Rated capacity of a circuit breaker is 750Amps at 25 kV, 500MVA. Its overall tripping time is 0.14 seconds composed of 0.04 ... but in case of traction substation application, mostly Minimum Oil Circuit Breaker (MOCB) is preferred.

Description : Distributed under Creative Commons Attribution-ShareAlike - CC BY-SA.

Last Answer : Some important components/equipments in substation  As told earlier, the function of a substation is to receive power at some voltage through incoming lines and transmit it at some other voltage through ... range ammeter to indicate the line current. Version 2 EE IIT, Kharagpur 