If the contacts of a motor starter or controller fail to drop out when the 'stop' button is depressed the ____________. A. contacts are carrying excessive current B. contacts have become welded together C. shading coil is broken D. shading coil is loose

1 Answer

Answer :

Answer: B

Related questions

Description : Motor starter or controller contacts may become welded together if the contacts _____________. A. open too quickly and arc B. close under excessive pressure C. open or close too quickly D. close under excessive starting current

Last Answer : Answer: D

Description : If a magnetic controller relay fails to drop out when the coil voltage is removed from the relay, the probable cause may be _____________. A. excessive spring tension B. overvoltage C. excessive current D. welded contacts

Last Answer : Answer: D

Description : To stop the electric motor shown in the illustration, the stop button is depressed, causing ____________. EL-0012 A. coil 'MS' to become de-energized B. contacts 'CR1' and 'MR4' to open C. contacts 'MR1', 'MR2', and 'MR3' to open D. contacts 'MS1', 'MS2', and 'MS3' to open

Last Answer : Answer: C

Description : Magnetic controller contacts may become welded together during operation because of _____________. A. excessive magnetic gap B. low contact pressure C. an open coil D. excessive ambient temperature

Last Answer : Answer: B

Description : Magnetic controller contacts may become welded together during operation due to _____________. A. an open coil B. low contact pressure C. excessive ambient temperature D. excessive magnetic gap

Last Answer : Answer: B

Description : Motor controller or starter contacts may become pitted and welded together if the contacts _____________. A. open under loaded conditions B. close slowly with light pressure C. open too quickly and arc D. close quickly with proportionate pressure

Last Answer : Answer: B

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : When troubleshooting a magnetic controller, it is found that the contacts are welded together. The most probable cause is _____________. A. excessive operation at low load B. high ambient temperature C. low voltage on the operating coil D. high voltage on the operating coil

Last Answer : Answer: C

Description : Magnetic controller contacts may become welded together during operating conditions as a result of _____________. A. high spring pressure B. high ambient temperature C. an open coil D. low voltage on operating coil

Last Answer : Answer: D

Description : Excessive heat in an operating motor controller can result from _____________. A. a closed starter contact B. loose connections C. missing arc chutes D. low motor starting torque

Last Answer : Answer: B

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : A shading coil used in an AC magnetic controller, functions to _____________. A. reduce vibration and noise in the contactor B. prevent flux buildup in the operating coil C. eliminate arcing when the contacts close D. energize the operating coil and 'pull in' the contacts

Last Answer : Answer: A

Description : Excessive humming of AC contactors may be caused by ______________. A. burnt arc shields B. shorted armature coils C. a broken shading coil D. high voltage

Last Answer : Answer: C

Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

Last Answer : Answer: B

Description : A loud buzzing noise coming from the contacts in a magnetic controller can be caused by ____________. A. excessive current B. excessive magnet gap C. bouncing of contacts D. dirt on magnet faces

Last Answer : Answer: D

Description : As shown in the illustration, which listed action will occur first when push button 'Q' is depressed? EL-0017 A. Contacts 'H-1', 'H-2' and 'H-3' close. B. Contact 'H-4' closes. C. Operating coil 'C' energizes. D. Switch 'R' opens.

Last Answer : Answer: C

Description : The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical ... D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

Last Answer : Answer: B

Description : When the motor shown in the illustration is running and the stop button is pushed, which of the following statements will hold true? EL-0010 A. Coil 'M' will now be energized. B. Coil 'CR' will now be energized. C. Contact 'M' will close as contact 'CR' opens. D. Contacts 'M' and 'CR' will open.

Last Answer : Answer: D

Description : Low voltage releases as used in some shipboard motor starter and control equipment will have which of the following characteristics? A. They trip circuit contactors when the motor starts to overspeed. B. ... coil of the starter. D. They allow the motor to restart upon restoration of normal voltage.

Last Answer : Answer: D

Description : If the motor shown in the illustration will not start when 'Q' is depressed, which of the listed components should be checked FIRST? EL-0017 A. Fuses 'F-1' and 'F-2'. B. Operating coil 'C'. C. Contacts 'H-1', 'H-2', and 'H-3'. D. Contact 'H-4'.

Last Answer : Answer: A

Description : The pitting of controller contacts can be caused by _____________. A. excessive spring pressure B. insufficient contact pressure C. continuous motor overload D. all of the above

Last Answer : Answer: B

Description : Shading coils are installed on AC full-voltage starters to _____________. A. eliminate contact chatter B. dissipate opening contact arcs C. delay current build up in the holding coil D. protect the motor windings from momentary starting current overload

Last Answer : Answer: A

Description : A molded-case breaker provides protection against short circuits by using a/an ____________. A. shading coil B. arc quencher C. electromagnet D. holding coil

Last Answer : Answer: C

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : A loud buzzing noise at the contacts of a magnetic controller could indicate _____________. A. weak contact spring pressure B. misalignment of the magnet faces C. excessive line current D. mechanical binding

Last Answer : Answer: B

Description : A megohmmeter is connected to each end of an individual motor winding. A low ohm reading indicates ____________. A. an open coil B. a loose coil C. good continuity D. a dirty coil

Last Answer : Answer: C

Description : Complete controller maintenance includes _____________. A. periodic testing of protective devices B. checking for loose or worn contacts and weak springs C. maintaining a sufficient supply of spare parts D. all of the above

Last Answer : Answer: D

Description : A motor controller contains three selector push buttons labeled 'start', 'jog', and 'stop'. When the 'jog' button is pushed, the motor _____________. A. will run continuously after the 'jog' button is ... 'jog' and 'start' buttons are pushed D. will not stop unless the 'stop' button is pushed

Last Answer : Answer: B

Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil

Last Answer : Answer: D

Description : As shown in the illustration, which of the operations listed will happen when the 'jog button' is pushed? EL-0010 A. Coil 'CR' closes the normally open 'CR' contacts. B. Coil 'M' opens contact 'M'. C. Coil 'M' closes contact 'M'. D. Contact 'M' remains open despite the jog button being pushed.

Last Answer : Answer: C

Description : Refering to the illustrated schematic diagram, which of the following statements is true when the motor is running in the forward direction? EL-0011 A. Normally-open contacts '4-5' are closed. B. Current ... switch. C. Normally-closed contacts 'R' are open. D. The blowout coils must be closed.

Last Answer : Answer: B

Description : As shown in the illustration, the symbol is used in electrical drawings to designate a ____________. EL-0026 A. limit switch with one set of normally open contacts B. maintaining type ... type push button with a mechanical interlock D. normally closed contact held open mechanically by an interlock

Last Answer : Answer: C

Description : The diagram shown in the illustration represents a _________. EL-0058 A. dual speed, 2-winding motor controller B. navigation running light circuit C. single phase, 2-motor selectable starter D. common fluorescent lighting circuit

Last Answer : Answer: B

Description : The contacts operated by the D.C. relay coil shown in the illustration are located in the schematic diagram prints at coordinates ____________. EL-0100 A. '41Y' on this page B. '52M52M' and '52H35M' C. '57R' on this page D. '52N' on page '57R'

Last Answer : Answer: C

Description : Humming or buzzing of electric contacts is a symptom of ____________. A. low voltage on the operating coil B. power failure to the operating coil C. a control circuit ground D. a control circuit overload

Last Answer : Answer: A

Description : If a transformer is connected to a DC source, the transformer will overload at the ____________. A. contacts B. primary coil C. secondary coil D. core

Last Answer : Answer: B

Last Answer : In a shaded pole motor, the shading coil usually consist of a single turn of heavy copper wire which is short-circuited and carries only induced current.

Description : A molded-case circuit breaker provides protection against short circuits by using a/an ________________. A. electromagnet B. shading coil C. arc quencher D. burn away strip

Last Answer : Answer: A

Description : In order that current should flow without causing excessive heating or voltage drop, the relay contacts should (a) have low contact resistance (b) be clean and smooth (c) be of sufficient size and proper shape (d) have all above properties

Last Answer : (d) have all above properties

Last Answer : In order that current should flow without causing excessive heating or voltage drop, the relay contacts should have low contact resistance, be clean and smooth, be of sufficient size and proper shape.

Description : One function of the movable cams in a drum-type motor controller is to _____________. A. regulate the speed of the motor B. maintain resistance contacts in clean condition C. insulate the operating handle D. limit the amount of load put on the motor

Last Answer : Answer: A

Description : If the line voltage to the controller shown in the illustration is 440 volts, what voltage is applied across the motor when contacts 'S' close? EL-0080 A. 110 volts B. 220 volts C. 440 volts D. 660 volts

Last Answer : Answer: B

Description : One method of testing for a reversed shunt field coil in a DC generator or motor is by connecting the field to a direct current source, at reduced field rated voltage, and test for ... placed near each field C. test lamp across adjacent fields D. copper jumper across the interpole connections

Last Answer : Answer: B

Description : Which of the listed conditions could cause a DC motor to have excessively hot windings and sparking at the brushes? A. Reversed interpole polarity B. High bar-to-bar voltage C. Loose brushes D. Excessive humidity

Last Answer : Answer: A