When charging a 100 amp-hour lead-acid battery, ___________. A. the temperature of the electrolyte should not be allowed to exceed 90°F B. the charging rate should be no greater than 125% of the battery amp-hour rating C. the source of power for charging should be 2.5 volts per cell D. gassing within the battery decreases when nearing full charge and it will be necessary to reduce the charging current to a low finishing rate

1 Answer

Answer :

Answer: C

Related questions

Description : If violent gassing occurs when a lead-acid storage battery is first placed on charge, the _____________. A. battery must be given an emergency charge B. charging rate is too low C. charging rate is too high D. specific gravity of the electrolyte solution is too low

Last Answer : Answer: C

Description : When charging lead-acid batteries, you should reduce the charging rate as the battery nears its full charge capacity to ______________. A. prevent excessive gassing and overheating B. allow equalization of cell voltages C. reduce lead sulfate deposits D. increase lead peroxide formation

Last Answer : Answer: A

Description : Violent gassing from a lead-acid battery while it is being charged, indicates that the _____________. A. plate separators are grounded B. battery compartment ventilation is inadequate C. electrolyte specific gravity is too low D. charging rate is too high

Last Answer : Answer: D

Description : When a nickel-cadium battery begins gassing while connected to the battery charging circuit, you should _____________. A. do nothing as this is a normal condition when charging B. add distilled water ... to each cell to increase the specific gravity of the electrolyte D. decrease the charging rate

Last Answer : Answer: A

Description : When charging a nickel-cadmium battery, ____________. A. the charging rate should be lessened when gassing commences B. overcharging should be avoided C. the specific gravity of the electrolyte will be ... by the state of charge D. add distilled water just prior to charging to insure proper mixing

Last Answer : Answer: C

Description : When a lead-acid battery begins gassing freely while receiving a normal charge, the charging current should _____________. A. be increased B. remain unchanged C. be decreased D. shut off

Last Answer : Answer: C

Description : When a lead-acid battery begins gassing freely while receiving a normal charge, the charging current should be _____________. A. increased B. shut off C. decreased D. unchanged

Last Answer : Answer: C

Description : Violent gassing developed by a lead-acid battery during charging indicates that the ____________. A. plate separators are grounded B. cell voltages are excessive C. specific gravity in insufficient D. charging rate is excessive

Last Answer : Answer: D

Description : Which of the following conditions indicates that a lead-acid battery is being charged too rapidly? A. Sparks occurring at the positive terminal. B. Unusually high electrolyte specific gravity. C. Low plate potentials being developed. D. Excessively high temperatures and gassing rates.

Last Answer : Answer: D

Description : Which of the following statements describes the effects of ambient temperature on local action within lead-acid storage batteries? A. Increasing ambient temperature increases local action. B. Increasing ambient ... has no effect on local action. D. At 90°F all local action virtually ceases.

Last Answer : Answer: A

Description : A breakable, mercury-filled thermometer should not be used in a lead-acid battery to measure electrolyte temperature, as an accidental breakage can cause ____________. A. severe sparking and explosions ... battery plates C. violent gassing at the positive plates D. corrosion on the battery terminals

Last Answer : Answer: A

Description : When charging lead-acid batteries, the charging rate should be reduced as the battery nears its full charge to ____________. A. prevent damaging battery plates B. allow equalization of cell voltages C. reduce lead sulfate deposits D. increase lead peroxide formation

Last Answer : Answer: A

Description : The specific gravity of the electrolyte solution in a lead acid battery _____________. A. is not effected during charging B. remains the same during discharge C. would read close to 1.830 when discharged D. gives an indication of the state of charge of the battery

Last Answer : Answer: D

Description : The state of charge of a lead-acid battery is best indicated by the ____________. A. individual cell voltage B. ampere-hour capacity C. electrolyte specific gravity D. total cell voltage

Last Answer : Answer: C

Description : The state of charge of a lead acid storage battery is best indicated by the _____________. A. testing of the individual cell voltages B. ampere hour capacity of the battery C. specific gravity of the electrolyte D. total cell voltages

Last Answer : Answer: C

Description : Which of the problems listed will occur if a lead-acid battery is allowed to remain in a discharged condition for a long period of time? A. The battery may be unable to accept a full charge ... . C. The concentrated sulfuric acid will attack the lead peroxide plates. D. The separators will harden.

Last Answer : Answer: A

Description : During the charging process of storage batteries, the charging rooms should be well ventilated because __________. A. without ventilation excessive gassing will occur B. highly poisonous gases are ... gases will otherwise accumulate D. without ventilation the battery will not take a full charge

Last Answer : Answer: C

Description : Which of the following represents the corrected specific gravity of a lead acid battery, with a temperature of 90°F, and a hydrometer reading of 1160? A. 1150 B. 1156 C. 1160 D. 1164

Last Answer : Answer: D

Description : Maintenance of alkaline batteries should include _________. A. checking the electrolyte weekly using a hydrometer B. replacing the electrolyte every 5 years C. trickle charging D. replacment when the volts per cell drops below 1.8 VDC

Last Answer : Answer: C

Description : Which of the following statements concerning nickel-cadmium batteries is true? A. When mixing electrolyte always add acid to the water. B. Nickel-cadmium batteries can be charged and ... The electrolyte of an idle nickel-cadmium battery must be replaced monthly to maintain battery condition.

Last Answer : Answer: C

Description : A slow continual loss of electrolyte level from one cell of a storage battery could be due to _______________. A. a cracked casing B. too low a charging rate C. the specific gravity being higher than normal D. one filler cap installed too tightly

Last Answer : Answer: A

Description : The charge of a lead-acid battery can be restored by ______. A. passing an alternating electric current through the cell B. passing a direct electric current through the cell C. adding acid to the electrolyte D. all of the above

Last Answer : Answer: B

Description : A lead-acid battery may become hotter than normal during a charge if the _________. A. battery has a shorted cell B. charging voltage is too low C. specific gravity is too high D. battery room door is secured

Last Answer : Answer: A

Description : Periodic testing of circuit breakers is necessary to assure that a correctly rated and properly installed unit _________________. A. can trip faster as it increases in age B. will continue to provide ... not exceed its interrupting capacity D. be able to withstand at least 125% of applied voltage

Last Answer : Answer: B

Description : Following will happen if battery charging rate is too high A. Excessive gassing will occur B. Temperature rise will occur C. Bulging and buckling of plates we occur D. All of the above

Last Answer : D. All of the above

Description : Which of the following problems is indicated if a lead-acid battery begins to gas violently when it is first placed on charge? A. Insufficient compartment ventilation is being provided. B. A short ... undergoing its normal charging rate. D. An excessive charging rate is being applied to the battery.

Last Answer : Answer: D

Description : When mixing electrolyte for a lead-acid storage battery, you should pour the ___________. A. distilled water into the acid in a zinc-plated container B. distilled water into the acid in a glass ... into the distilled water in a zinc-plated container D. acid into distilled water in a glass container

Last Answer : Answer: D

Description : In the illustrated circuit the voltage is 12 VDC and the resistance is 3 ohms. If the battery is rated for 120 amp-hours, how long before the voltage will drop to 1.75 volts per cell? EL-0018 A. 12 hours B. 1.75 days C. 30 hours D. 2.5 days

Last Answer : Answer: C

Description : Which of the listed ranges represents specific gravity corrected for temperature for the electrolyte of a fully charged portable lead-acid battery? A. 1.100 to 1.150 B. 1.180 to 1.200 C. 1.280 to 1.300 D. 1.750 to 2.000

Last Answer : Answer: C

Description : A nickel-cadmium battery is receiving a normal charge and gases freely. The charging current should _____________. A. be increased B. be decreased C. be cut off and the battery allowed to cool D. remain the same

Last Answer : Answer: D

Description : When choosing a battery for a particular application, major consideration should be given to the battery's ____________. A. amp-hour capacity B. terminal polarity C. stability under charge D. ambient temperature rise

Last Answer : Answer: A

Description : During charging, the specific gravity of the electrolyte of a lead acid battery _____.

Last Answer : During charging, the specific gravity of the electrolyte of a lead acid battery increases.

Description : When troubleshooting a lead-acid storage battery, a weak or dead cell is best detected by _________________. A. measuring and comparing all cells' specific gravity B. taking an open circuit ... electrolyte levels of each cell D. taking each cell's temperature with a calibrated mercury thermometer

Last Answer : Answer: A

Description : To determine the state of charge of a nickel-cadmium battery, you should ___________. A. check the electrolyte with a hydrometer B. use the constant specific gravity method C. use a nonbreakable mercury thermometer D. connect a voltmeter to the battery terminals

Last Answer : Answer: D

Description : Under which of the following conditions will a lead-acid battery be given a 'test discharge'? A. To determine its capacity. B. Whenever a cell cannot be brought within 10 points of full charge ... cells is found to have less than normal voltage after an equalizing charge. D. All of the above.

Last Answer : Answer: D

Description : Which of the following activities occurs during the charging process of a lead-acid storage battery? A. The specific gravity of the acid increases. B. Both plates change chemically to lead sulfate. C. The specific gravity of the acid decreases. D. Hydrogen gas is absorbed.

Last Answer : Answer: A

Description : Proper storage battery maintenance includes ____________. A. keeping connections tight and casing surfaces clean B. making sure electrolyte level is below the separator plates C. insulating the terminals with naval jelly D. maintaining a high charging rate at all times

Last Answer : Answer: A

Description : A lead-acid battery can deliver 20 amperes continuously for 10 hours with an ampere-hour rating of ____________. A. 20 B. 40 C. 200 D. 400

Last Answer : Answer: C

Description : A circuit breaker for a 300 KW alternator is rated at 470 amperes of full continuous load. The amount of overcurrent allowed is 125%. Which of the following conditions will trip the breaker? A. ... 10 minutes. C. Momentary starting load of 550 amperes. D. Sustained current flow of 590 amperes.

Last Answer : Answer: D

Description : The illustrated circuits are used to measure ___________. EL-0024 A. resistance B. gauss or magnetic field strength C. battery discharge rate in Amp-hours D. current

Last Answer : Answer: A

Description : A lead-acid battery is considered fully charged when the ______________. A. electrolyte gasses freely B. battery charger ammeter indicates a positive reading C. terminal voltage reaches a constant value at a ... cells reaches the correct value and no longer increases over a period of 1 to 4 hours

Last Answer : Answer: D

Description : Which of the following temperatures represents the maximum allowable temperature for the electrolyte of a lead-acid battery? A. 100°F B. 125°F C. 145°F D. 212°F

Last Answer : Answer: B

Description : Local action in a dry-cell, or lead-acid storage battery is the process whereby ________________. A. hydrogen gas is liberated B. the electrolyte compensates for overcharging C. potassium hydroxide ... carbon dioxide from the air D. the battery becomes discharged without being connected to a load

Last Answer : Answer: D

Description : What would be the total current flowing in the circuit shown in the illustration if the source is 30 volts, the resistance of R1 is 10 ohms, R2 is 10 ohms and R3 is 10 ohms? EL-0032 A. 1 amp B. 2 amps C. 5 amps D. 15 amps

Last Answer : Answer: B

Description : Local action in a nickel-cadmium battery is offset by _____________. A. separating the positive and negative plates with plastic spacers B. separating the positive and negative plates with resin impregnated spacers C. adding a small amount of lithium hydroxide to the electrolyte D. trickle charging

Last Answer : Answer: D

Description : When you check the specific gravity of the battery electrolyte with a hydrometer, it should be kept in mind that ____________. A. the battery is fully charged when the indicator floats low in ... taken immediately after water is added to the cell D. temperature has no effect on hydrometer readings

Last Answer : Answer: C

Description : The open-circuit voltage of a fully charged lead-acid battery cell is _____________. A. 1.5 volts B. 1.8 volts C. 2.0 volts D. 2.3 volts

Last Answer : Answer: C

Description : Which of the listed battery charging circuits is used to maintain a wet-cell, lead-acid, storage battery in a fully charged state during long periods of disuse? A. Normal charging circuit B. Quick charging circuit C. Trickle charging circuit D. High ampere charging circuit

Last Answer : Answer: C