When securing an AC generator, you should FIRST ___________. A. open the generator circuit breaker B. switch the voltage regulator to 'manual' C. decrease the field excitation to minimum D. reduce the load on the unit

1 Answer

Answer :

Answer: D

Related questions

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : Prior to starting an AC generator prime mover, the voltage regulator cutout switch should be placed in the __________. A. manual position B. bus neutral position C. raise voltage position D. transfer position

Last Answer : Answer: A

Description : The voltage developed by an AC generator is controlled by varying the ____________. A. speed of the prime mover B. AC excitation to the field C. DC excitation to the field D. DC excitation of the voltage regulator

Last Answer : Answer: C

Description : Why is it desirable to operate paralleled AC generators at the same power factor? A. Circulating currents are kept to a minimum. B. Field excitation losses are kept to a minimum. C. Generator ... will have a lesser tendency to hunt. D. Because a power factor increase will decrease kilowatt output.

Last Answer : Answer: A

Description : When paralleling two AC generators, the frequency of the incoming machine immediately prior to closing its breaker should be ____________. A. controlled by placing the governor switch in the automatic ... regulator C. slightly greater than the bus frequency D. slightly less than the bus frequency

Last Answer : Answer: C

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : Automatic voltage regulators provided on switchboards function to _____________. A. regulate the AC load on the generator B. protect the switchboard from high voltage C. govern prime mover speed to control voltage D. vary the field excitation to the generators

Last Answer : Answer: D

Description : The standard method of controlling the output voltage of a 440 volt, 60 Hz, AC generator is accomplished by adjusting the ____________. A. prime mover speed droop B. number of poles C. alternator field excitation D. load on the alternator

Last Answer : Answer: C

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : As load is added to an AC generator provided with constant field excitation, the prime mover slows down with the effect of ____________. A. lowering frequency and lowering generated ... C. increasing frequency and lowering generated voltage D. lowering frequency and increasing generated voltage

Last Answer : Answer: A

Description : The device labeled 'REG SW' in the illustration is used to ___________. EL-0003 A. shift from the automatic voltage regulator to the manual voltage regulator B. shift the governor control from manual to ... device 'REG ADJ' or device 'MAN ADJ' D. supply regulated control power to the switchboard

Last Answer : Answer: A

Description : The simplest method of controlling the terminal voltage of compound-wound DC generator is with a _____________. A. hand-operated field rheostat connected in series with the shunt field circuit B. ... in series with the load D. balance coil diverting neutral current through the shunt field

Last Answer : Answer: A

Description : To increase the frequency of an operating AC generator, you should ____________. A. increase the field excitation B. decrease the field excitation C. increase the number of magnetic poles D. increase the speed of the prime mover

Last Answer : Answer: D

Description : The instantaneous reduction in voltage of an AC generator, resulting from an increase in load, and prior to the automatic voltage regulator correcting the situation, is called voltage ____________. A. droop B. drop C. dip D. regulation

Last Answer : Answer: C

Description : Regarding an AC generator connected to the main electrical bus; as the electric load and power factor vary, a corresponding change is reflected in the generator armature reaction. These changes in ... . governor speed droop setting B. voltage regulator C. balance coil D. phase-balance relay

Last Answer : Answer: B

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : To remove an alternator operating in parallel with another unit from the main electrical bus, you must FIRST _________. A. adjust the power factor on both units B. set the desired voltage on ... C. open the circuit breaker on the outgoing alternator D. remove the load from the outgoing alternator

Last Answer : Answer: D

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : If an AC generator experiences voltage failure, the cause may be _____________. A. an open in the field circuit B. the brushes shifting out of the neutral plane C. excessive locked-rotor current D. a rotating slip ring

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : The voltage of an operating AC turbogenerator is raised or lowered by adjusting the _____________. A. exciter generator governor controls B. synchronizing switch C. phase sequence switch D. generator field exciter

Last Answer : Answer: D

Description : In the illustration, if one of the devices labeled 'TURB' should fail the ___________. EL-0003 A. device labeled 'EXC' will drive the alternator B. device labeled 'BKR' for that ... -alternator D. emergency generator should automatically start and be placed on line to supply emergency load centers

Last Answer : Answer: B

Description : The most common source of excitation for synchronous motors is a/an _____________. A. low voltage battery B. motor attenuator set C. DC exciter generator D. AC supply

Last Answer : Answer: C

Description : A constant output voltage from an AC generator is maintained by the _____________. A. prime mover governor B. exciter generator C. voltage regulator D. reverse power relay

Last Answer : Answer: C

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : The purpose of DC generator brushes is to _____________. A. neutralize armature reaction B. conduct electric current to an outside circuit C. convert DC current to AC current D. provide excitation to a DC generator

Last Answer : Answer: B

Description : In a diesel electric plant, raising the generator's field excitation will cause the DC propulsion motor to ________. A. increase in speed B. decrease in speed C. affect generator speed only D. affect main motor speed if done in conjunction with higher generator engine speeds

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0° prior to closing the circuit breaker. This indicates ___________. A. the frequency of ... be closed after breaker has been reset D. there is an existing cross current between generators

Last Answer : Answer: A

Description : ___________ is device that measures the internal open circuit voltage of an equivalent noise generator having an impedance of 600Ω and delivering noise power to a 600 Ω load. A. Psophometer B. Barometer C. Reflectometer D. Voltmeter

Last Answer : A. Psophometer

Description : When paralleling two AC generators, the frequency of the machine coming online, immediately prior to closing its breaker, should be ____________. A. slightly less than the oncoming generator frequency B. the ... bus frequency C. slightly greater than the bus frequency D. the same as the bus voltage

Last Answer : Answer: C

Description : Kilowatt load is divided between two AC generators operating in parallel by _____________. A. adjusting the governor controls B. varying the excitation voltage C. increasing both prime mover speeds simultaneously D. decreasing both prime mover speeds simultaneously

Last Answer : Answer: A

Description : When paralleling two AC generators, the frequency (cycles) of the incoming generator, just prior to closing the circuit breaker, should be _____________. A. slightly less than the frequency of the generator on ... C. slightly more than the frequency of the generator on the line D. all of the above

Last Answer : Answer: C

Description : Three factors responsible for the change in voltage as load is applied to an AC generator are: 1) the drop in resistance in the armature circuit, 2) the change in flux, and 3) the ____________. A. armature winding speed B. inductance load drop C. coil pitch factor D. armature reactance voltage drop

Last Answer : Answer: D

Description : The most practical way to control the voltage output of an AC generator is to vary the _____________. A. number of windings B. speed of the rotating field C. strength of the rotating magnetic field D. power factor of the load

Last Answer : Answer: C

Description : If two AC generators have just been placed in parallel, the true power load is initially distributed evenly by _____________. A. a balance coil B. changing field excitation C. adjusting the governor control settings D. a rheostat

Last Answer : Answer: C

Last Answer : A 220 V D.C. generator is run at full speed without any excitation. The open circuit voltage will be about 2 V.

Description : An open occurring within the field rheostat of an AC generator can be detected by short circuiting its terminals and observing a ____________. A. negative deflection of the wattmeter pointer B. ... of the wattmeter pointer C. buildup of alternator voltage D. low, but constant alternator voltage

Last Answer : Answer: C

Description : If reading the AC voltage from the line lead of a 440 VAC controller the range switch illustrated should be set to ___________. EL-0047 A. 1,000 V B. 250 V C. R X 10,000 D. Unable to safely read with this meter.

Last Answer : Answer: A

Description : If reading the AC voltage from a typical wall outlet, the range switch of the device illustrated should be set to ___________. EL-0047 A. 1,000 V B. 250 V C. R X 10,000 D. 10 ma/amps

Last Answer : Answer: B

Description : Before any work on electrical or electronic equipment is performed, which of the following precautions should be carried out? A. De-energize the applicable switchboard bus. B. Bypass the interlocks. C. ... supply circuit breaker in the open position. D. Station a man at the circuit supply switch.

Last Answer : Answer: C

Description : In an emergency, the fastest way to interrupt power and stop the winch shown in the illustration is for the ____________. EL-0102 A. mate to open the disconnect switch at 'L1' and 'L2' B. ... watch engineer to open the winch circuit breaker D. electrician to open the test link at the controller

Last Answer : Answer: B

Description : Before working on an electric cargo winch master switch or controller, you should _____________. A. spray the gasket surface with a solvent B. drain condensate from the box C. open the circuit breaker in the power supply and tag D. heat the switch box to remove any moisture

Last Answer : Answer: C

Description : An alternator will fail to produce line voltage as a result of _____________. A. a closed circuit breaker B. oxidized slip rings C. improperly staggered brushes D. exciter generator failure

Last Answer : Answer: D

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : If field excitation is suddenly lost to an alternator operating in parallel, that alternator will _____________. A. supply excessive current to the bus B. operate at the same load, but with reduced voltage C. lose its load and tend to overspeed D. become overloaded and slow down

Last Answer : Answer: C

Description : A change in field excitation of an alternator operating in parallel will cause a change in its _____________. A. alternator frequency B. kilowatt load C. voltage output D. all of the above

Last Answer : Answer: C