Description : In addition to testing the calibration of a circuit breaker, maintenance should include all of the following EXCEPT ______________. A. changing out of magnetic elements and thermal heaters yearly B. ... for loose or missing parts D. making sure foreign matter does not block tripping element
Last Answer : Answer: A
Description : A loud buzzing noise at the contacts of a magnetic controller could indicate _____________. A. weak contact spring pressure B. misalignment of the magnet faces C. excessive line current D. mechanical binding
Last Answer : Answer: B
Description : Routine maintenance of dry-type transformers should include ______________. A. preventing the entrance of water from broken pipe lines steam lines B. keeping protective surfaces and insulating bushings free of ... debris C. periodic testing of insulation resistance with a megger D. all of the above
Last Answer : Answer: D
Description : Periodic testing by a shoreside support technician using a special camera which can detect potentially dangerous loose or corroded bus bar and controller connections is termed ______________. A. heat sensitive thermography B. visual pyrotronics C. corrosion electrolysis D. electric vibroanalysis
Description : Complete maintenance of electrical motors should include periodic checks for machine _____________. A. vibration B. watertight integrity C. speed droop D. reactive power
Description : After turning on the fluorescent lamp shown in the illustration, you note that the ends of the tube alternately glow and becomce dark without illuminating the center. The most obable cause for ... the lamp D. component 'B' contacts are opening and closing thus prohibiting sufficient current flow
Last Answer : Answer: C
Description : The illustration shows a fluorescent light fixture. The ends of the lamp alternately glow and become dark, but the tube will not light. The most probable cause is that ____________. EL-0081 ... start the lamp D. component 'B' contacts are opening and closing thus prohibiting sufficient current flow
Description : During start-up of the circuit shown in the illustration, it is noted that the ends of component 'C' alternately glow and become dark without the tube illuminating. The most probable cause ... start the lamp D. component 'B' contacts are opening and closing thus prohibiting sufficient current flow
Description : The winch shown in the illustration will not operate in any speed in the lowering direction and at an abnormal speed in 'first point hoist'. The possible cause is that _______________. EL-0102 A. ... '1M' in the power circuit are badly corroded D. master switch contacts 'MS6' have weak springs
Description : If the contacts of a motor starter or controller fail to drop out when the 'stop' button is depressed the ____________. A. contacts are carrying excessive current B. contacts have become welded together C. shading coil is broken D. shading coil is loose
Description : The devices marked 'T' in the illustration are _____________. EL-0080 A. trouble alarm units whose contacts activate when problems arise either on starting or stopping of the motor B. topping ... contactor parts whose contacts start and stop the defrosting cycle of the compressor driven by the motor
Description : Proper storage battery maintenance includes ____________. A. keeping connections tight and casing surfaces clean B. making sure electrolyte level is below the separator plates C. insulating the terminals with naval jelly D. maintaining a high charging rate at all times
Description : Routine A.C. motor maintenance should include periodic ______________. A. thermometer readings at normal loads to detect abnormal temperature rises B. inspection of the motor's internals for loose rotor bars ... C. bearing replacement each year using sealed units if available D. all of the above
Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil
Description : Motor starter or controller contacts may become welded together if the contacts _____________. A. open too quickly and arc B. close under excessive pressure C. open or close too quickly D. close under excessive starting current
Description : Magnetic controller contacts may become welded together during operating conditions as a result of _____________. A. high spring pressure B. high ambient temperature C. an open coil D. low voltage on operating coil
Description : The pitting of controller contacts can be caused by _____________. A. excessive spring pressure B. insufficient contact pressure C. continuous motor overload D. all of the above
Description : Motor controller or starter contacts may become pitted and welded together if the contacts _____________. A. open under loaded conditions B. close slowly with light pressure C. open too quickly and arc D. close quickly with proportionate pressure
Description : Magnetic controller contacts may become welded together during operation because of _____________. A. excessive magnetic gap B. low contact pressure C. an open coil D. excessive ambient temperature
Description : When troubleshooting a magnetic controller, it is found that the contacts are welded together. The most probable cause is _____________. A. excessive operation at low load B. high ambient temperature C. low voltage on the operating coil D. high voltage on the operating coil
Description : If a magnetic controller relay fails to drop out when the coil voltage is removed from the relay, the probable cause may be _____________. A. excessive spring tension B. overvoltage C. excessive current D. welded contacts
Description : Burning of controller contacts, when opening, is prevented by _____________. A. coating the contact surfaces lightly with petroleum jelly B. magnetic blowout coils C. an overvoltage release D. an overcurrent release
Description : Magnetic controller contacts may become welded together during operation due to _____________. A. an open coil B. low contact pressure C. excessive ambient temperature D. excessive magnetic gap
Description : One function of the movable cams in a drum-type motor controller is to _____________. A. regulate the speed of the motor B. maintain resistance contacts in clean condition C. insulate the operating handle D. limit the amount of load put on the motor
Description : A shading coil used in an AC magnetic controller, functions to _____________. A. reduce vibration and noise in the contactor B. prevent flux buildup in the operating coil C. eliminate arcing when the contacts close D. energize the operating coil and 'pull in' the contacts
Description : The most effective method of locating a loose commutator bar in a D.C. motor is by _____________. A. visual inspection B. jiggling each by hand C. sounding each bar with a light weight hammer D. checking with a calibrated torque wrench
Description : Excessive heat in an operating motor controller can result from _____________. A. a closed starter contact B. loose connections C. missing arc chutes D. low motor starting torque
Description : When troubleshooting an alkaline storage battery a weak or dead cell is best located by ____________. A. checking the specific gravity of each cell B. visually inspecting each cell's ... testing each cell with a voltmeter D. measuring the electrolyte temperature with an accurate mercury thermometer
Description : Routine maintenance of lead acid batteries should include _____________. A. keeping the terminals clean B. coating cable connections with petroleum jelly C. maintaining a trickle charge D. all of the above
Description : Routine maintenance of a ship's service alternator should include ______________. A. changing the pedestal bearing insulation yearly B. megger testing of all rectifying diodes C. lubricating excitation slip rings D. periodic cleaning of the air filters or screens
Description : The 'annunciator module' and 'controller' shown in the illustration together provide for _____________. EL-0094 A. blinking lamp on alarm; testing the lamp and alarm; and logging alarm conditions B ... visual and audible alarms; flashing lamp on alarm; and silencing the horn when answering an alarm
Description : As a general rule, the first troubleshooting action to be taken in checking faulty electric control devices is to _____________. A. draw a one line diagram of the circuitry B. test all fuses and measure the line voltage C. take megger readings D. insulate the apparatus from ground
Description : Receptacle outlets aboard ship should be designed so those mounted according to 46 CFR 111 have _____________. A. there must be a sufficient number of receptacle outlets in the crew accommodations for an ... outlet must not have any exposed parts with the plug opening uncovered D. all of the above
Description : Before working on an electric cargo winch master switch or controller, you should _____________. A. spray the gasket surface with a solvent B. drain condensate from the box C. open the circuit breaker in the power supply and tag D. heat the switch box to remove any moisture
Description : Which of the following statements, concerning the general maintenance of a brushless generator, is correct? A. Paint should be applied to insulating surfaces on an annual basis. B. Alcohol should be used to ... . D. Accessible generator parts should be wiped with a clean dry rag on a periodic basis.
Description : When maintenance personnel are working on electrical equipment, all supply switches should be secured in the open position and tagged specifically by the _____________. A. watch engineer B. chief engineer or first assistant C. chief electrician D. person performing the repair
Description : An essential to the sanitary maintenance of latrines is a. Sufficient supply of water b. Supply of latrine construction materials c. Health education program in latrine usage and upkeep d. All of the above
Last Answer : c. Health education program in latrine usage and upkeep
Description : For more complete vessel protection when using an impressed current cathodic system _____________. A. all ship's service alternators have additional temperature sensing devices and a thermal recorder ... with the hull and the propeller shaft is grounded through a slip ring/brush arrangement
Description : As shown in the illustration, the symbol is used in electrical drawings to designate a ____________. EL-0026 A. limit switch with one set of normally open contacts B. maintaining type ... type push button with a mechanical interlock D. normally closed contact held open mechanically by an interlock
Description : As shown in the illustration, what is responsible for maintaining the "LV" relay energized when the master switch handle is moved away from the "off" position? EL-0102 A. "DBa" contact. B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.
Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'
Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown
Description : Which of the following statments is true of the illustrated motor controller? EL-0023 A. The low speed is used for starting the motor and when the controller automaticly shifts to High speed. B. The HOL relay ... D. If the overload relay opens for high speed the motor can still be run in low speed.
Description : The 'reset' contacts of the master switch shown in the illustration provides the winch controller with ___________. EL-0102 A. low voltage release B. overload protection C. low voltage protection D. high power factor correction
Description : A loud buzzing noise coming from the contacts in a magnetic controller can be caused by ____________. A. excessive current B. excessive magnet gap C. bouncing of contacts D. dirt on magnet faces
Description : Controller contacts should be routinely cleaned by ________. A. blowing with compressed air B. filing with a bastard file C. wiping with a clean dry cloth D. dressing with crocus cloth
Description : If the line voltage to the controller shown in the illustration is 440 volts, what voltage is applied across the motor when contacts 'S' close? EL-0080 A. 110 volts B. 220 volts C. 440 volts D. 660 volts
Description : A shorted armature coil in a DC motor can be detected by _____________. A. sparking at the brushes B. shiny armature coil C. worn grooves in the armature D. undercut mica
Description : A split-phase induction squirrel-cage motor will not come up to speed, even though the rated voltage, rated frequency, and rated load are applied. The suspected trouble could be due to _____________. A. a faulty centrifugal switch B. broken rotor bars C. worn bearings D. all of the above
Description : What are the chemical protective overcoat and trousers when worn together called?
Last Answer : CPO