The motor starts when the start button in the illustration is pushed, but stops when the button is released the trouble is _________. EL-0007 A. the incorrect thermal overload coil B. a faulty 'M' coil C. a dirty contact on the Disc.Sw. at 'L3' D. a faulty holding relay contact

1 Answer

Answer :

Answer: D

Related questions

Description : If the illustrated motor fails to start and gives a loud hum when the start button is pushed, the problem is ________. EL-0007 A. one of the phases to the motor is not energized because of ... electrical distribution system D. 'OL1' is open because of 'T1' overload causing the motor to single phase

Last Answer : Answer: A

Description : The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical ... D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

Last Answer : Answer: B

Description : If the motor fails to start and a voltmeter reading between 1 and 6, as illustrated, indicates line voltage, your next step should be to ________. EL-0007 A. replace fuse '10a' B. replace or repair contact 'Ma' C. reset and determine the cause of the overload D. check line voltage between L1 and L3

Last Answer : Answer: C

Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

Last Answer : Answer: B

Description : When the motor shown in the illustration is running and the stop button is pushed, which of the following statements will hold true? EL-0010 A. Coil 'M' will now be energized. B. Coil 'CR' will now be energized. C. Contact 'M' will close as contact 'CR' opens. D. Contacts 'M' and 'CR' will open.

Last Answer : Answer: D

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : The schematic diagram shown in the illustration uses symbol 'A' to represent a/an _________. EL-0011 A. non-renewable fuse link B. circuit breaker coil C. overload relay coil D. thermal overload heater

Last Answer : Answer: D

Description : As shown in the illustration, which of the operations listed will happen when the 'jog button' is pushed? EL-0010 A. Coil 'CR' closes the normally open 'CR' contacts. B. Coil 'M' opens contact 'M'. C. Coil 'M' closes contact 'M'. D. Contact 'M' remains open despite the jog button being pushed.

Last Answer : Answer: C

Description : If the circuit shown in the illustration were energized and operating properly, which of the devices listed would be open? EL-0007 A. The stop push-button B. The start push-button C. Contact 'Ma' D. Contact 'OL1'

Last Answer : Answer: B

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : The devices located at coordinates '49W' in the illustration represents a/an _________. EL-0100 A. A.C. motor B. A.C. relay coil C. D.C. motor D. D.C. buzzer

Last Answer : Answer: B

Description : Component 'C' in section 'I' shown in the illustration represent ____________. EL-0093 A. a selectable holding coil arrangement B. a 'fuse blown' indicator circuit C. 'reset' and 'trouble' lamps D. a handset with switch and voice elements

Last Answer : Answer: D

Description : Shading coils are installed on AC full-voltage starters to _____________. A. eliminate contact chatter B. dissipate opening contact arcs C. delay current build up in the holding coil D. protect the motor windings from momentary starting current overload

Last Answer : Answer: A

Description : A three-phase, induction-type motor experiences an open in one phase. Which of the listed automatic protective devices will prevent the machine from being damaged? A. Overspeed trip B. Thermal overload relay C. Three-pole safety switch D. Magnetic blowout coil

Last Answer : Answer: B

Description : Low voltage releases as used in some shipboard motor starter and control equipment will have which of the following characteristics? A. They trip circuit contactors when the motor starts to overspeed. B. ... coil of the starter. D. They allow the motor to restart upon restoration of normal voltage.

Last Answer : Answer: D

Description : As shown in the illustration, 'S' is the __________. EL-0017 A. safety switch B. overload trip C. start button D. stop button

Last Answer : Answer: D

Description : The winch shown in the illustration operates in any of the positions with the master switch in the 'lower' direction, but will not 'hoist' in any of the master switch hoist positions. Which of the listed faults ... '2M' in the power circuit may be badly corroded. D. Series relay 'FR' may be open.

Last Answer : Answer: A

Description : In the illustration, the purpose of part B is to _________. EL-0033 A. increase resistance in series with the contacts as they close to prevent arcing B. create a magnetic field in the steel ... event of an overload D. provide ventilation to the contact when the breaker is close to rated capacity

Last Answer : Answer: B

Description : A motor controller contains three selector push buttons labeled 'start', 'jog', and 'stop'. When the 'jog' button is pushed, the motor _____________. A. will run continuously after the 'jog' button is ... 'jog' and 'start' buttons are pushed D. will not stop unless the 'stop' button is pushed

Last Answer : Answer: B

Description : Vessel pitch can be controlled by either the 'bridge or engine room thrust lever' shown in the illustration; but only with one engine on the line whether in 'cruise or maneuver' mode. The cause is most likely a faulty relay _____________. EL-0095 A. #1 B. #2 C. #3 D. #4

Last Answer : Answer: D

Description : As shown in the illustration, which listed action will occur first when push button 'Q' is depressed? EL-0017 A. Contacts 'H-1', 'H-2' and 'H-3' close. B. Contact 'H-4' closes. C. Operating coil 'C' energizes. D. Switch 'R' opens.

Last Answer : Answer: C

Description : If the motor shown in the illustration will not start when 'Q' is depressed, which of the listed components should be checked FIRST? EL-0017 A. Fuses 'F-1' and 'F-2'. B. Operating coil 'C'. C. Contacts 'H-1', 'H-2', and 'H-3'. D. Contact 'H-4'.

Last Answer : Answer: A

Description : The wiring diagram for the motor starting circuit shown in the illustration indicates ______________. EL-0007 A. resistance starting B. reduced voltage starting C. low voltage protection D. low voltage release

Last Answer : Answer: C

Description : To stop the electric motor shown in the illustration, the stop button is depressed, causing ____________. EL-0012 A. coil 'MS' to become de-energized B. contacts 'CR1' and 'MR4' to open C. contacts 'MR1', 'MR2', and 'MR3' to open D. contacts 'MS1', 'MS2', and 'MS3' to open

Last Answer : Answer: C

Description : The device at coordinates '63/1' in the illustration represents a/an _____________. EL-0100 A. A.C. buzzer B. A.C. motor C. D.C. motor D. D.C. relay coil

Last Answer : Answer: D

Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0042 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open

Last Answer : Answer: C

Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0043 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open

Last Answer : Answer: C

Description : 'A-1', as shown in the illustration, is/are ____________. EL-0017 A. normally-closed overload relay contacts B. a double pole knife switch C. normally-open overload relay contacts D. a single pole knife switch

Last Answer : Answer: A

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : If coil 'R1-R2' on the transmitter in figure 'A' shown in the illustration is turned 30 degrees clockwise, corresponding coil 'R1-R2' on the receiver should ____________. EL-0092 A. make coils 'S1 ... a higher voltage depending on the turns ratio D. align itself to the same position if free to move

Last Answer : Answer: D

Description : In the illustration, 'D' is the symbol for a/an __________. EL-0005 A. thermal overload heater B. portable cable C. fuse D. indicating lamp

Last Answer : Answer: C

Description : The contacts operated by the D.C. relay coil shown in the illustration are located in the schematic diagram prints at coordinates ____________. EL-0100 A. '41Y' on this page B. '52M52M' and '52H35M' C. '57R' on this page D. '52N' on page '57R'

Last Answer : Answer: C

Description : The vertical dotted line connecting the small circular symbols at coordinates '05L', '09L', '13L', '21L', '25L', etc., shown in the illustration, indicate that all _______________. EL-0100 A. contacts are ... board 'TB2' C. wires are grounded at both ends of the line D. wires have a common shield

Last Answer : Answer: B

Description : Power necessary to operate the horn shown in the illustration _____________. EL-0093 A. comes from each station's magneto B. is supplied from a 115 volt source C. is conducted through a relay coil D. also lights lamps 'R' and 'T'

Last Answer : Answer: B

Description : If the total source voltage of the three-wire distribution system shown in the illustration is 240 volts, what is the voltage across load L3? [NOTE: Kirchhoff's voltage and current laws apply.] EL-0075 A. 110.4 volts B. 112.2 volts C. 113.0 volts D. 114.8 volts

Last Answer : Answer: B

Description : Which of the following statements is true concerning the motor controller diagram shown in the illustration? EL-0023 A. Terminal 'T2' is hot only on high speed. B. Both indicating lights will be lit on ... high speed operation only. D. 'L2' is always connected to 'T2' whenever the motor is running.

Last Answer : Answer: D

Description : RC time constant characteristics, as shown in the illustration, are important in _____________. EL-0086 A. bridge rectifiers for alternator excitation B. timing and pulse shaping circuits C. transistor power amplifier biasing D. motor controller overload protection

Last Answer : Answer: B

Description : Which component will stop the motor shown in the illustration in case of an overload in the control circuit? EL-0080 A. 'E' B. 'G' C. 'H' D. 'I'

Last Answer : Answer: B

Description : Which device will stop the motor shown in the illustration in case of a short-circuit (high current) motor overload? EL-0080 A. 'F' B. 'G' C. 'H' D. 'I'

Last Answer : Answer: A

Description : Which two components, shown in the illustration, acting together will disconnect the motor from the line in case of a sustained motor overload? EL-0080 A. 'G' and 'H' B. 'E' and 'I' C. 'F' and 'H' D. 'E' and 'G'

Last Answer : Answer: B

Description : In the illustration, the component 'B' is attached to the component 'G' by _________. EL-0031 A. melting the top of 'G' and pressing 'B' onto it B. 'C' holding it in place C. sealing compound made of bituminous substance D. vacuum created in the battery by electrolytic action

Last Answer : Answer: C

Description : The device labeled 'REG SW' in the illustration is used to ___________. EL-0003 A. shift from the automatic voltage regulator to the manual voltage regulator B. shift the governor control from manual to ... device 'REG ADJ' or device 'MAN ADJ' D. supply regulated control power to the switchboard

Last Answer : Answer: A

Description : As shown in the illustration, the symbol is used in electrical drawings to designate a ____________. EL-0026 A. limit switch with one set of normally open contacts B. maintaining type ... type push button with a mechanical interlock D. normally closed contact held open mechanically by an interlock

Last Answer : Answer: C

Description : If all three ground-detection lamps continue to burn at equal intensity after the test button is depressed and released, which of the listed conditions is indicated? A. No grounds exist B. All three phases are grounded C. The test switch is faulty D. The current transformers are shorted out

Last Answer : Answer: A

Description : As shown in the illustration, what is responsible for maintaining the "LV" relay energized when the master switch handle is moved away from the "off" position? EL-0102 A. "DBa" contact. B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : The small circular symbols to which wire '52N57E' is connected at coordinates '57L' and '57P' shown in the illustration represent ___________________. EL-0100 A. relay contact solder points B. wire wrap connections C. terminal board screws D. switch contact terminals

Last Answer : Answer: C

Description : In the illustration, the diode between terminals 16 and 17 is to _________. EL-0046 A. act as a short circuit for the sensing coil when CEMF is applied B. insure that the voltage across the coil does not exceed 9 volts C. improve response time D. act as a filter to prevent hunting

Last Answer : Answer: A