When a megohmmeter is used to test the insulation of a large motor, the initial dip of the pointer toward 'zero' is caused by ____________. A. good insulation B. the capacitance of the windings C. the leakage of the current along the surface of dirty insulation D. the dielectric-absorption effect of the insulation

1 Answer

Answer :

Answer: B

Related questions

Description : When a megohmmeter is used to test the dielectric strength of wire insulation, the initial dip of the pointer toward 'zero' is caused by _____________. A. good insulation B. the leakage of ... of dirty insulation C. the capacitance of the circuit D. the dielectric absorption effect of the insulation

Last Answer : Answer: C

Description : When using a megohmmeter to test the dielectric strength of wire insulation, a continuous series of slight downscale kicks by the pointer is result of ____________. A. good insulation B. the ... dirty insulation C. the capacitance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : When a megohmmeter is used to test insulation, the gradual rise of the pointer reading as a result of continued cranking, is caused by _____________. A. good conductor resistance B. the ... insulation C. the inductive reactance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: D

Description : When a megohmmeter is being used on a alternating current machine, the meter pointer will dip toward 'zero' and then gradually rise to the true resistance value if the motor insulation is _____________. A. grounded B. good C. shorted D. dirty

Last Answer : Answer: B

Description : When a megohmmeter is being used to test insulation resistance, current leakage along the surface of the insulation is indicated by the megohmmeter's pointer _____________. A. dipping toward ... kicking slightly down scale as voltage is applied D. fluctuating around a constant resistance reading

Last Answer : Answer: C

Description : When a megohmmeter is being used to test insulation resistance, current leakage along the surface of the insulation is indicated by the megohmmeter pointer _____________. A. fluctuating around a ... slightly downscale as voltage is applied D. continually rising as the test voltage is applied

Last Answer : Answer: C

Description : When using a megohmmeter to test insulation, good insulation will be indicated by _____________. A. slight kicks of the needle down scale B. a downward dip followed by a gradual climb to the true resistance ... C. a gradual rise in the pointer reading at the outset D. the initial dip of the pointer

Last Answer : Answer: B

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test as the ______________. A. insulation may be damaged ... number of leakage paths D. larger machines may acquire a charge of static electricity during operation

Last Answer : Answer: D

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test, because the ___________. A. static charge of the machine ... number of leakage paths C. insulation may be damaged D. insulation may be covered with moisture

Last Answer : Answer: A

Description : You are testing the insulation in an AC generator with a megohmeter. The resistance value of a dry, clean winding will ____________. A. continue to rise as the test potential is maintained, ... fairly steady after 5 to 7 minutes D. stabilize after approximately 2 to 4 minutes of fluctuation

Last Answer : Answer: A

Description : The removal of paint from electrical equipment, such as generators, should be cautiously undertaken because ____________. A. the mechanical shock of paint removal lessens the dielectric strength ... phase windings frequently become isolated from each other due to dust interference at the terminals

Last Answer : Answer: B

Description : A megohmmeter is connected to each end of an individual motor winding. A low ohm reading indicates ____________. A. an open coil B. a loose coil C. good continuity D. a dirty coil

Last Answer : Answer: C

Description : When you are making a high potential test on a piece of repaired electrical machinery, a rise in leakage current indicates ____________. A. good insulation B. bad insulation C. high insulation power factor D. a high slot discharge factor

Last Answer : Answer: B

Description : The greatest detrimental effect on idle electrical equipment, such as cargo pump motors, is the _____________. A. loss of residual magnetism B. absorption of moisture in the insulation C. insulation varnish flaking D. dirt collecting on the windings

Last Answer : Answer: B

Description : A capacitor is to be tested with a megohmmeter. If the meter is connected to a shorted capacitor, the meter pointer should _____________. A. immediately swing to the maximum resistance value ... and gradually decrease D. swing to zero then gradually increase with slight pointer movements down scale

Last Answer : Answer: B

Description : A capacitor can be tested using a megohmmeter or an ohmmeter. If the meter is connected to a shorted capacitor, the meter pointer should _____________. A. immediately swing to the maximum resistance ... deflect to and remain at zero D. immediately swing to a high reading and then gradually decrease

Last Answer : Answer: C

Description : In testing a three-phase delta winding for an open circuit using a megohmmeter, you must ______________. A. test each phase with all connections intact B. measure the voltage across the open ... groups to avoid short circuiting D. open the delta-connections to avoid shunting the phase being tested

Last Answer : Answer: D

Description : An open in the armature of a DC motor is suspected, but is not found by visual inspection of the commutator. The next step in troubleshooting this problem is to ________________. A. conduct a ... windings C. conduct an insulation resistance test of the armature D. test the commutator for a ground

Last Answer : Answer: A

Description : The counter EMF produced in the windings of a DC motor is 'zero' when the ____________. A. armature has just begun to turn B. armature is not turning C. motor is almost up to rated speed D. motor is at rated speed

Last Answer : Answer: B

Description : On tank vessels with an electrically-driven capstan, the motor should be meggered periodically to test _____________. A. insulation resistance B. eddy currents C. capacitance D. armature reactance

Last Answer : Answer: A

Description : Unnecessary and frequent applications of varnish to the generator windings to repair defective insulation will result in ____________. A. heavy coatings of varnish interfering with heat dissipation B. ... of the rectifier assembly D. a built-up of varnish without changing generator operation

Last Answer : Answer: A

Description : Routine maintenance of dry-type transformers should include ____________. A. cleaning the windings, if accessible, with a vacuum cleaner or very low pressure air B. measuring and recording the winding ... . making sure that the units are close to bulkheads or corners to protect them from damage

Last Answer : Answer: A

Description : A megohmmeter is used to measure _____________. A. voltage B. dielectric strength C. current D. power

Last Answer : Answer: B

Description : Moisture absorbed in the windings or condensed on the surface of electrical machinery insulation ________. A. is good for long term preserving since most insulation is organic and contains some amount B. ... D. reduces the amount of current supplied or drawn by the machine so horsepower is limited

Last Answer : Answer: B

Description : To carry out an insulation resistance test, one terminal of the megohmmeter should be connected to the winding, with the other terminal being connected to the ____________________. A. power supply B. variable resistor C. frame of the machine D. armature

Last Answer : Answer: C

Description : The final step in testing a circuit for a ground involves the use of a megohmmeter. A grounded switch or cable will be indicated by a megohmmeter reading of ____________. A. 'zero' B. infinity C. steady in the high range D. unsteady in the low range

Last Answer : Answer: A

Description : When using a megohmmeter to determine which shunt field coil is grounded in a DC machine, you must ____________. A. insulate the field frame from the ship's hull B. disconnect each shunt ... C. use a motor driven high capacity megohmmeter D. remove all main line lead connections before testing

Last Answer : Answer: B

Description : The leads from a megohmmeter are attached to the leads of an AC motor field coil. A reading of infinity is obtained indicating a/an ____________. A. open field coil B. shorted field coil C. grounded field coil D. shunted field coil

Last Answer : Answer: A

Description : While starting a main propulsion synchronous motor, the ammeter pegs out at maximum and then returns to the proper value after synchronization. This indicates the _____________. A. motor has started ... field windings are grounded C. slip rings are dirty D. power transmission cables are grounded

Last Answer : Answer: A

Description : Damp armature windings in a D.C. motor may lead to ____________. A. reduced voltage B. reduced current C. increased resistance D. overheating

Last Answer : Answer: D

Description : If you obtain a low resistance reading with a megohmmeter connected between terminals 'A' and 'C' of the three-phase, wye-connected winding shown in the illustration, there is __________. EL-0074 A. no open circuit ... 'B' C. an open circuit between 'A' and 'C' D. an open circuit in both windings

Last Answer : Answer: A

Description : Which of the following conditions indicates a short circuited capacitor when checking its condition with an ohmmeter? A. The capacitor shows charging, but the final resistance reading is appreciably less ... moves quickly to the low resistance side of the scale, then slowly recedes toward infinity.

Last Answer : Answer: B

Description : A megohmmeter can be used to test for ____________. A. an open field coil B. synchronous speed C. undercut mica D. reversed polarity

Last Answer : Answer: A

Description : To test fuses in an energized circuit, you should use a ____________. A. low voltage light bulb B. megohmmeter C. voltmeter D. resistance meter

Last Answer : Answer: C

Description : Which of the conditions listed will indicate the need to clean the insulation on the windings of an electric motor? A. Higher than normal operating temperature. B. Excessive vibration at normal speed. C. Sparking at the brushes. D. High megger readings.

Last Answer : Answer: A

Description : Which of the listed statements is correct when using an analog multimeter as an ohmmeter? A. The pointer should be adjusted to zero each time a new resistance range is selected. B. The ... C. Ohmmeters are not sufficiently sized to measure conductor insulation resistance. D. All of the above.

Last Answer : Answer: D

Description : Basically, a magnetic amplifier is a saturable reactor with the addition of _____________. A. AC to the bias winding B. variable capacitance to all windings C. eddy current protectors D. a rectifier in the load circuit

Last Answer : Answer: D

Description : In preparing to take insulation resistance readings on a main generator, the windings should be grounded for about 15 minutes prior to the test to _____________. A. allow accurate zeroing of the meter ... the windings D. help the windings to cool to the same temperature as the ground test connection

Last Answer : Answer: C

Description : In a three-phase, squirrel-cage type, induction motor the rotating magnetic field is established by the _____________. A. current induced in the rotor windings B. application of a three-phase voltage ... caused by the induced current in the squirrel-cage bars with the magnetic field of the stator

Last Answer : Answer: B

Description : When an AC or a DC motor fails to start, the FIRST step in troubleshooting should be to check the ____________. A. motor windings for obvious opens B. motor controller leads for continuity C. fuse or circuit breaker D. motor controller leads for grounds

Last Answer : Answer: C

Description : Which of the instruments listed is used to check insulation resistance? A. Magneto B. Megohmmeter C. Dynamometer D. Rheostat

Last Answer : Answer: B

Description : Sparking at the brushes of a running motor could be an indication of _____________. A. normal operation B. a dirty commutator C. increased brush capacity D. water vapor absorption

Last Answer : Answer: B

Description : State the methods used to measure insulation resistance and explain Dielectric Absorption method.

Last Answer : There are three types of tests for measuring insulation resistance:  1. Spot test reading or Short Time test  2.Time-resistance test or Dielectric absorption test or Testing methods based on the PI & DAR  3. ... and if value of PI is less than 2 and value of DAR is less than 1.25

Description : A saturable-core reactor operates on the principle of controlling a load winding's inductance by varying the core's _____________. A. dielectric B. permeability C. reactance D. inductance

Last Answer : Answer: B

Description : What you mean by dielectric absorption test?

Last Answer : Whenever we apply a potential from the megger to test the IR value, initially the needle of the megger will go to low value of the resistance. This is due the capacitance effect of the ... A. After the test terminals to be discharged so that molecules may return to their unstressed state. 

Description : Increasing the load to the secondary windings of a transformer will cause a/an ____________. A. decrease in the primary voltage B. increase in the primary voltage C. decrease in the primary current D. increase in the primary current

Last Answer : Answer: D

Description : Electrical leads and insulation on a motor should be painted with ____________. A. heat-resisting acrylic B. heat-resisting aluminum C. insulating varnish D. insulating white lead

Last Answer : Answer: C