In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL-0007 A. the control fuse is the wrong amperage not allowing full current to pass through B. the stop switch is open C. an open in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

1 Answer

Answer :

Answer: B

Related questions

Description : If the motor fails to start and a voltmeter reading between 1 and 6, as illustrated, indicates line voltage, your next step should be to ________. EL-0007 A. replace fuse '10a' B. replace or repair contact 'Ma' C. reset and determine the cause of the overload D. check line voltage between L1 and L3

Last Answer : Answer: C

Description : The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical ... D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

Last Answer : Answer: B

Description : If the illustrated motor fails to start and gives a loud hum when the start button is pushed, the problem is ________. EL-0007 A. one of the phases to the motor is not energized because of ... electrical distribution system D. 'OL1' is open because of 'T1' overload causing the motor to single phase

Last Answer : Answer: A

Description : If reading the AC voltage from the line lead of a 440 VAC controller the range switch illustrated should be set to ___________. EL-0047 A. 1,000 V B. 250 V C. R X 10,000 D. Unable to safely read with this meter.

Last Answer : Answer: A

Description : The motor starts when the start button in the illustration is pushed, but stops when the button is released the trouble is _________. EL-0007 A. the incorrect thermal overload coil B. a faulty 'M' coil C. a dirty contact on the Disc.Sw. at 'L3' D. a faulty holding relay contact

Last Answer : Answer: D

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil

Last Answer : Answer: D

Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0042 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open

Last Answer : Answer: C

Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0043 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open

Last Answer : Answer: C

Description : If the circuit shown in the illustration were energized and operating properly, which of the devices listed would be open? EL-0007 A. The stop push-button B. The start push-button C. Contact 'Ma' D. Contact 'OL1'

Last Answer : Answer: B

Description : When troubleshooting motor controllers, a shorted relay or contactor coil is often indicated by _______________. A. a resistance reading of 'infinity' on an ohmmeter B. charred insulation and/or a blown ... of the coil's leads to ground D. a higher-than-normal voltage reading across the winding

Last Answer : Answer: B

Description : When troubleshooting a motor controller, all indications are that a relay coil should be energized. If there were no magnetic pull, with rated voltage measured across the coil, the most probable cause ... open C. auxiliary contact in series with the coil is defective D. relay armature is stuck

Last Answer : Answer: A

Description : The 'reset' contacts of the master switch shown in the illustration provides the winch controller with ___________. EL-0102 A. low voltage release B. overload protection C. low voltage protection D. high power factor correction

Last Answer : Answer: C

Description : Refering to the illustrated schematic diagram, which of the following statements is true when the motor is running in the forward direction? EL-0011 A. Normally-open contacts '4-5' are closed. B. Current ... switch. C. Normally-closed contacts 'R' are open. D. The blowout coils must be closed.

Last Answer : Answer: B

Description : The illustrated circuit is a wheatstone bridge. If the meter 'G' reads 0 with the switch closed then ________. EL-0024 A. the current through R1 - R2 is equal to the current through R3 - Rx B. the voltage ... of E C. the resistance of Rx is equal to the resistance of R2 D. all the above are true

Last Answer : Answer: A

Description : When the motor shown in the illustration is running and the stop button is pushed, which of the following statements will hold true? EL-0010 A. Coil 'M' will now be energized. B. Coil 'CR' will now be energized. C. Contact 'M' will close as contact 'CR' opens. D. Contacts 'M' and 'CR' will open.

Last Answer : Answer: D

Description : If reading the AC voltage from a typical wall outlet, the range switch of the device illustrated should be set to ___________. EL-0047 A. 1,000 V B. 250 V C. R X 10,000 D. 10 ma/amps

Last Answer : Answer: B

Description : In the illustrated test, if the lamp fails to light on any of the three windings then _________. EL-0027 A. all three windings are grounded and the motor should be sent out for repair B. ... the motor controller and the controller should be checked D. the test should be redone at a higher voltage

Last Answer : Answer: C

Description : Component 'C' in section 'I' shown in the illustration represent ____________. EL-0093 A. a selectable holding coil arrangement B. a 'fuse blown' indicator circuit C. 'reset' and 'trouble' lamps D. a handset with switch and voice elements

Last Answer : Answer: D

Description : If a magnetic controller relay fails to drop out when the coil voltage is removed from the relay, the probable cause may be _____________. A. excessive spring tension B. overvoltage C. excessive current D. welded contacts

Last Answer : Answer: D

Description : A load is connected to the secondary of the transformer illustrated and the current through the load is 10 amps. If the step-up ratio is 10 to 1 and the input voltage is 110 VAC, what will be the current flow through the primary? EL-0055 A. 1 amp B. 10 amps C. 100 amps D. 1000 amps

Last Answer : Answer: C

Description : A load is connected to the secondary of the device illustrated and the current through the load is 10 amps. If the step-up ratio is 10 to 1 and the input voltage is 110 VAC, what will be the current flow through the primary? EL-0055 A. 1 amp B. 10 amps C. 100 amps D. 1000 amps

Last Answer : Answer: C

Description : Which of the following conditions is most likely to occur if a single element fuse were used to replace a blown dual element fuse in a motor controller circuit? A. The fuse will blow when the motor ... overheats at high motor loads. C. The motor runs at reduced voltage. D. The motor runs normally.

Last Answer : Answer: A

Description : When attempting to measure AC current with the device shown and you are unsure of the range, the range switch should be set to __________. EL-0047 A. 10 MA / AMPS with leads in the (-10 A) and ... (-COMMON) and (+10 A) jacks D. unable to accurately measure AC current with this device as illustrated

Last Answer : Answer: D

Description : The pitting of controller contacts can be caused by _____________. A. excessive spring pressure B. insufficient contact pressure C. continuous motor overload D. all of the above

Last Answer : Answer: B

Description : A load with an impedance of 440 ohms is connected across the secondary of the transformer illustrated. If the input voltage is 110 VAC and the step-up ratio is 10 to 1, what will be the primary current? EL-0055 A. 2.5 amps B. 25 amps C. 250 amps D. current cannot be determined with information given

Last Answer : Answer: B

Description : A load with an impedance of 440 ohms is connected across the secondary of the device illustrated. If the input voltage is 110 VAC and the step-up ratio is 10 to 1, what will be the primary current? EL-0055 A. 2.5 amps B. 25 amps C. 250 amps D. current cannot be determined with information given

Last Answer : Answer: B

Description : Shading coils are installed on AC full-voltage starters to _____________. A. eliminate contact chatter B. dissipate opening contact arcs C. delay current build up in the holding coil D. protect the motor windings from momentary starting current overload

Last Answer : Answer: A

Description : 'A-1', as shown in the illustration, is/are ____________. EL-0017 A. normally-closed overload relay contacts B. a double pole knife switch C. normally-open overload relay contacts D. a single pole knife switch

Last Answer : Answer: A

Description : If fuse 'F-1' in the illustrated schematic diagram opens, ____________. EL-0017 A. the motor will run slowly B. 'A-1' and 'A-2' will open C. the motor will not start D. the start button will jam in the closed position

Last Answer : Answer: C

Description : If the motor shown in the illustration will not start when 'Q' is depressed, which of the listed components should be checked FIRST? EL-0017 A. Fuses 'F-1' and 'F-2'. B. Operating coil 'C'. C. Contacts 'H-1', 'H-2', and 'H-3'. D. Contact 'H-4'.

Last Answer : Answer: A

Description : If the contacts of a motor starter or controller fail to drop out when the 'stop' button is depressed the ____________. A. contacts are carrying excessive current B. contacts have become welded together C. shading coil is broken D. shading coil is loose

Last Answer : Answer: B

Description : If a magnetic controller contact fails to pick up when the operating coil is energized, one possible cause may be _______________. A. low spring pressure B. low voltage to the coil C. the residual magnetism of the contact faces D. dirty contact faces

Last Answer : Answer: B

Description : During maintenance of circuit breakers, _______________. A. always smooth roughened contact surfaces with a file B. never pass more than rated breaker current through the overload heater element C. ... wear and misalignment of main contacts D. assume heater elements installed are of correct size

Last Answer : Answer: C

Description : As shown in the illustration, which of the operations listed will happen when the 'jog button' is pushed? EL-0010 A. Coil 'CR' closes the normally open 'CR' contacts. B. Coil 'M' opens contact 'M'. C. Coil 'M' closes contact 'M'. D. Contact 'M' remains open despite the jog button being pushed.

Last Answer : Answer: C

Description : In the illustration, the purpose of part B is to _________. EL-0033 A. increase resistance in series with the contacts as they close to prevent arcing B. create a magnetic field in the steel ... event of an overload D. provide ventilation to the contact when the breaker is close to rated capacity

Last Answer : Answer: B

Description : When an AC or a DC motor fails to start, the FIRST step in troubleshooting should be to check the ____________. A. motor windings for obvious opens B. motor controller leads for continuity C. fuse or circuit breaker D. motor controller leads for grounds

Last Answer : Answer: C

Description : If the line voltage to the controller shown in the illustration is 440 volts, what voltage is applied across the motor when contacts 'S' close? EL-0080 A. 110 volts B. 220 volts C. 440 volts D. 660 volts

Last Answer : Answer: B

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : As shown in the illustration, which listed action will occur first when push button 'Q' is depressed? EL-0017 A. Contacts 'H-1', 'H-2' and 'H-3' close. B. Contact 'H-4' closes. C. Operating coil 'C' energizes. D. Switch 'R' opens.

Last Answer : Answer: C

Description : To stop the electric motor shown in the illustration, the stop button is depressed, causing ____________. EL-0012 A. coil 'MS' to become de-energized B. contacts 'CR1' and 'MR4' to open C. contacts 'MR1', 'MR2', and 'MR3' to open D. contacts 'MS1', 'MS2', and 'MS3' to open

Last Answer : Answer: C

Description : As shown in the illustration, 'S' is the __________. EL-0017 A. safety switch B. overload trip C. start button D. stop button

Last Answer : Answer: D

Description : Magnetic controller contacts may become welded together during operation because of _____________. A. excessive magnetic gap B. low contact pressure C. an open coil D. excessive ambient temperature

Last Answer : Answer: B

Description : Magnetic controller contacts may become welded together during operation due to _____________. A. an open coil B. low contact pressure C. excessive ambient temperature D. excessive magnetic gap

Last Answer : Answer: B