An open occurring within the field rheostat of an AC generator can be detected by short circuiting its terminals and observing a ____________. A. negative deflection of the wattmeter pointer B. positive deflection of the wattmeter pointer C. buildup of alternator voltage D. low, but constant alternator voltage

1 Answer

Answer :

Answer: C

Related questions

Description : The frequency of an AC generator is adjusted by means of the ____________. A. main alternator field rheostat B. exciter field rheostat C. prime mover governor control D. equalizing reactor

Last Answer : Answer: C

Description : The standard method of controlling the output voltage of a 440 volt, 60 Hz, AC generator is accomplished by adjusting the ____________. A. prime mover speed droop B. number of poles C. alternator field excitation D. load on the alternator

Last Answer : Answer: C

Description : A large AC generator, supplying power to an infinite bus, has a sudden short-circuit occurring at its terminals. Assuming the prime mover input and the voltage behind the transient reactance to remain constant immediately after the fault, acceleration of the generator rotor is

Last Answer : A large AC generator, supplying power to an infinite bus, has a sudden short-circuit occurring at its terminals. Assuming the prime mover input and the voltage behind the transient reactance ... , acceleration of the generator rotor is inversely proportional to the moment of inertia of the machine

Description : Loss of or weak residual magnetism in an alternator or generator can be corrected for by _________________. A. running the rotor in the opposite direction for 5 minutes B. allowing the generator ... rheostat fully counterclockwise D. using a storage battery or battery charger to 'flash' the field

Last Answer : Answer: D

Description : The removal of paint from electrical equipment, such as generators, should be cautiously undertaken because ____________. A. the mechanical shock of paint removal lessens the dielectric strength ... phase windings frequently become isolated from each other due to dust interference at the terminals

Last Answer : Answer: B

Description : As load is added to an AC generator provided with constant field excitation, the prime mover slows down with the effect of ____________. A. lowering frequency and lowering generated ... C. increasing frequency and lowering generated voltage D. lowering frequency and increasing generated voltage

Last Answer : Answer: A

Description : The cycles per second developed by the alternator aboard your vessel is determined by _____________. A. the speed of the engine driving the alternator B. the resistance applied to the field rheostat C. the synchronous speed of induction D. the adjustments made to the voltage regulator

Last Answer : Answer: A

Description : When paralleling two alternators the synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates the ____________. A. alternator voltages ... alternator is in phase with the bus voltage D. synchroscope pointer is defective or broken

Last Answer : Answer: C

Description : Temporary repairs to an open DC propulsion armature coil can be made by _____________. A. connecting the coil ends directly to a pair of negative brushes B. disconnecting coil ends, insulating ... C. grounding the coil ends and short circuiting the commutator bar D. removing the sparking brushes

Last Answer : Answer: B

Description : In testing a three-phase delta winding for an open circuit using a megohmmeter, you must ______________. A. test each phase with all connections intact B. measure the voltage across the open ... groups to avoid short circuiting D. open the delta-connections to avoid shunting the phase being tested

Last Answer : Answer: D

Description : The true power indicated by the pointer movement of a wattmeter depends on the current flow through the load, the magnitude of the potential across the load, and the ____________. A. power factor of the ... B. angle of coil displacement C. inertia of the movable coil D. high resistance from the load

Last Answer : Answer: A

Description : Moving the rheostat handle shown in the illustration, that is used to control a DC generator, towards the 'raise' direction will increase the _____________. EL-0030 A. field resistance B. armature resistance C. armature speed D. line voltage

Last Answer : Answer: D

Description : The kilowatt load can be adjusted on a paralleled generator by using the _____________. A. field rheostat B. governor control C. automatic voltage regulators D. hand tachometer

Last Answer : Answer: B

Description : The simplest method of controlling the terminal voltage of compound-wound DC generator is with a _____________. A. hand-operated field rheostat connected in series with the shunt field circuit B. ... in series with the load D. balance coil diverting neutral current through the shunt field

Last Answer : Answer: A

Description : Which of the following is a characteristic of fractional horsepower repulsion start motors? A. They start with a rotating stator field. B. The short circuiting ring is removed from the commutator while ... brushes are removed from the commutator while starting. D. They have a low starting torque.

Last Answer : Answer: B

Description : The voltage developed by an AC generator is controlled by varying the ____________. A. speed of the prime mover B. AC excitation to the field C. DC excitation to the field D. DC excitation of the voltage regulator

Last Answer : Answer: C

Description : The amount of voltage induced in the windings of an AC generator depends on ____________. A. the number of conductors in series per winding B. the speed at which the magnetic field passes across the winding C. the strength of the magnetic field D. all of the above

Last Answer : Answer: D

Description : An electrical device which employs a stationary armature and a rotating electromagnetic field is used aboard ship as a ____________. A. magnetic amplifier B. ship's service alternator C. three-wire DC generator D. saturable core reactor

Last Answer : Answer: B

Description : You are paralleling two alternators. The synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates that the ____________. A. alternator ... be closed C. incoming alternator is running too slowly D. synchroscope is defective or broken

Last Answer : Answer: B

Description : The output voltage of a 440 volt, 60 Hz AC generator is controlled by the ______________. A. load on the alternator B. load on the prime mover C. speed of the prime mover D. exciter output voltage

Last Answer : Answer: D

Description : The output voltage of a 440 volt, 60 hertz, AC generator is controlled by the _____________. A. prime mover speed B. exciter output voltage C. load on the alternator D. number of poles

Last Answer : Answer: B

Description : A suspected 'open' in a motor field can be tested by using a/an ____________. A. potentiometer B. megger C. wattmeter D. ammeter

Last Answer : Answer: B

Description : The frequency of an AC generator is controlled by the _____________. A. rheostat B. governor C. exciter D. capacitor

Last Answer : Answer: B

Description : What is the calculated voltage at the positive and negative terminals of the battery shown in the illustration if each cell has a voltage of 1.5 volts? EL-0034 A. 1.5 volts B. 3.0 volts C. 6.0 volts D. 12.0 volts

Last Answer : Answer: A

Description : When using a multimeter for resistance measurements, it should be calibrated by clipping the loose ends of the leads together and _____________. A. setting the instrument pointer at 'zero' ohms B. ... the plus and minus terminals D. using a special purpose resistance measuring instrument (a bridge)

Last Answer : Answer: A

Description : If an AC generator experiences voltage failure, the cause may be _____________. A. an open in the field circuit B. the brushes shifting out of the neutral plane C. excessive locked-rotor current D. a rotating slip ring

Last Answer : Answer: A

Description : When securing an AC generator, you should FIRST ___________. A. open the generator circuit breaker B. switch the voltage regulator to 'manual' C. decrease the field excitation to minimum D. reduce the load on the unit

Last Answer : Answer: D

Description : At dead short circuit at terminals of Alternator then the current I is a) ZPF Lag b) ZPF lead c) Unity power factor d) 0.8 Power factor lag

Last Answer : Ans: ZPF Lag

Description : If a unloaded shunt motor's field were weakened by rheostat resistance or by an open circuit, the motor would _________. A. overspeed due to reduced CEMF B. stop because of low flux C. continue to run at base speed D. slow down and overheat

Last Answer : Answer: A

Description : A DC shunt generator has its field windings connected in _____________. A. series with the series windings B. parallel with the field rheostat C. series with the armature windings D. parallel with the armature windings

Last Answer : Answer: D

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : When paralleling two AC generators, the frequency of the machine coming online, immediately prior to closing its breaker, should be ____________. A. slightly less than the oncoming generator frequency B. the ... bus frequency C. slightly greater than the bus frequency D. the same as the bus voltage

Last Answer : Answer: C

Description : A variable shunt, connected across the series field coils of a DC compound wound generator, to permit adjustment of the degree of compounding, is called a _____________. A. divider B. diverter C. converter D. rheostat

Last Answer : Answer: B

Description : The output voltage of a three-phase alternator is regulated by the _____________. A. AC voltage to the armature B. AC voltage to the field C. DC voltage to the armature D. DC voltage to the field

Last Answer : Answer: D

Description : Three factors responsible for the change in voltage as load is applied to an AC generator are: 1) the drop in resistance in the armature circuit, 2) the change in flux, and 3) the ____________. A. armature winding speed B. inductance load drop C. coil pitch factor D. armature reactance voltage drop

Last Answer : Answer: D

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : The instantaneous reduction in voltage of an AC generator, resulting from an increase in load, and prior to the automatic voltage regulator correcting the situation, is called voltage ____________. A. droop B. drop C. dip D. regulation

Last Answer : Answer: C

Description : If two AC generators have just been placed in parallel, the true power load is initially distributed evenly by _____________. A. a balance coil B. changing field excitation C. adjusting the governor control settings D. a rheostat

Last Answer : Answer: C

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : You are testing the insulation in an AC generator with a megohmeter. The resistance value of a dry, clean winding will ____________. A. continue to rise as the test potential is maintained, ... fairly steady after 5 to 7 minutes D. stabilize after approximately 2 to 4 minutes of fluctuation

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : What component causes a generator to produce dc voltage rather than ac voltage at its output terminals?

Last Answer : A commutator

Description : To increase the frequency of an operating AC generator, you should ____________. A. increase the field excitation B. decrease the field excitation C. increase the number of magnetic poles D. increase the speed of the prime mover

Last Answer : Answer: D

Description : In a simple series circuit, the entire source voltage will drop across ______________. A. the resistor next to the negative terminal B. a short circuit C. the resistor next to the positive terminal D. an open circuit

Last Answer : Answer: D

Description : When two AC generators are being paralleled, the breaker should be closed with the synchroscope pointer rotating in the ____________. A. 'slow' direction, just before the 12 o'clock position B. 'fast' ... just before the 12 o'clock position D. 'slow' direction, just after the 12 o'clock position

Last Answer : Answer: C