Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0° prior to closing the circuit breaker. This indicates ___________. A. the frequency of ... be closed after breaker has been reset D. there is an existing cross current between generators
Last Answer : Answer: A
Description : When paralleling two AC generators, the frequency of the incoming machine immediately prior to closing its breaker should be ____________. A. controlled by placing the governor switch in the automatic ... regulator C. slightly greater than the bus frequency D. slightly less than the bus frequency
Last Answer : Answer: C
Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving fast in the clockwise direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... at any pointer position D. the same as the bus frequency but out of phase with it
Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving in the fast direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... the same as the bus frequency and the circuit breaker may be closed at any pointer position
Description : You are attempting to parallel two AC generators and the synchroscope pointer is revolving slowly in the fast direction. You should _____________. A. use the governor control switch to adjust the incoming ... the 0° position D. use the field rheostat to adjust the speed of the incoming machine
Description : You are attempting to parallel two AC generators and the synchroscope pointer is revolving in the slow direction. This indicates that the frequency of the incoming machine is _____________. A. higher than ... same as the bus frequency, and the circuit breaker may be closed at any pointer position
Last Answer : Answer: B
Description : When paralleling two AC generators, the frequency (cycles) of the incoming generator, just prior to closing the circuit breaker, should be _____________. A. slightly less than the frequency of the generator on ... C. slightly more than the frequency of the generator on the line D. all of the above
Description : When two AC generators are being paralleled, the breaker should be closed with the synchroscope pointer rotating in the ____________. A. 'slow' direction, just before the 12 o'clock position B. 'fast' ... just before the 12 o'clock position D. 'slow' direction, just after the 12 o'clock position
Description : Prior to closing the breaker when paralleling two AC generators, the recommended practice is to have the frequency of the incoming machine _____________. A. slightly less than the line frequency B. the same as the line frequency C. slightly greater than the line frequency D. all of the above
Description : When paralleling two AC generators, the frequency of the machine coming online, immediately prior to closing its breaker, should be ____________. A. slightly less than the oncoming generator frequency B. the ... bus frequency C. slightly greater than the bus frequency D. the same as the bus voltage
Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus
Description : You are paralleling two alternators. The synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates that the ____________. A. alternator ... be closed C. incoming alternator is running too slowly D. synchroscope is defective or broken
Description : When paralleling two AC generators, the synchroscope selector switch and frequency meter switch should be set up to sense the frequency of the _____________. A. bus B. generator on the line C. oncoming generator D. bus transfer relay
Description : The devices labeled 'L' in the illustration are _________. EL-0003 A. load lights indicating that the generator breaker is closed and the generator is supplying power to the main bus B. ... o'clock position the lights are at their dimmest or out indicating the the generators are in phase
Last Answer : Answer: D
Description : When paralleling two alternators the synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates the ____________. A. alternator voltages ... alternator is in phase with the bus voltage D. synchroscope pointer is defective or broken
Description : An AC generator panel is fitted with both synchronizing lamps and a synchroscope. When the synchroscope pointer reaches the noon position, one synchronizing light is bright and the other is dark. This ... sequence is incorrect C. the phase sequence is correct D. the generator breaker may be closed
Description : As shown in the illustration, which of the listed actions of the synchroscope pointer is occurring? EL-0002 A. Revolving slowly in the slow direction. B. Revolving rapidly in the slow direction. C. ... stationary at the 12 o'clock position since the leading edges of the A phases are in phase.
Description : While paralleling two (2) AC generators using synchronizing lamps only, both lamps will go dark when the generators are ____________. A. running at the same speed B. grounded C. of the same polarity D. in phase
Description : When paralleling two alternators, the synchronizing lamps remain lit as the synchroscope pointer approaches the 0°. This indicates the _____________. A. incoming alternator is running too fast B. alternator ... apart C. synchroscope is defective or broken D. alternator power factors are in phase
Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator
Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings
Description : Which of the following actions must be carried out prior to closing the alternator circuit breaker according to the graph shown in the illustration? EL-0002 A. Increase the alternator voltage. B. Decrease the line voltage. C. Increase the line voltage. D. Decrease the line frequency.
Description : Which of the following problems will occur if the circuit breaker of the incoming alternator is closed and it is 180° out of phase with the loaded alternator when paralleling? A. The rotor of the ... The rotor of the incoming alternator will stop. D. Both alternators will parallel 180° out of phase.
Description : As shown in the illustrations, which statement characterizes steering operations using the 'non-followup controller'? EL-0097 A. The rudder responds while the switch is held left or right and returns to mid- ... the switch is held right; in both cases, it remains in position when switch is 'off'.
Description : As shown in the illustrations of console schematic diagrams, each circuit card and component, such as a relay or indicating lamp, has an identifier attached. This identifier, which is composed of ... where the item may actually be found on the console by section, surface and possible subassembly
Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay
Description : An alternator switchboard has a synchroscope and synchronizing lamps. If the synchroscope is broken, which of the steps listed is the most essential before an alternator can be paralleled with the bus? ... D. A portable phase sequence indicator must be used to verify the information from the lamps.
Description : When paralleled, AC generators must have the same _________. A. frequency B. number of phases C. phase rotation D. all of the above
Description : When paralleling two alternators using three synchronizing lamps, the flickering of all three lamps becomes progressively slower and slower. This means the ______________. A. frequency of the incoming ... the bus D. terminal voltage of the incoming alternator is approaching that of the bus
Description : As a result of a mechanical malfunction in one of the ship's service generators operating in parallel, you must secure that generator. In order to prevent a possible overload to the ... feeder circuit breakers, the malfunctioning prime mover turbine throttle trip, and the generator circuit breaker.
Description : A shore power circuit breaker should be closed only _____________. A. when the ship's generators have been directly paralleled to those on shore B. in a shipyard C. if a quick disconnect coupling is used D. when the ship's generators have been removed from the bus
Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit
Description : After closing the circuit breaker to place two similar alternators in parallel, the NEXT step is to balance the _____________. A. power factor B. voltage load C. kilowatt load D. ampere load
Description : The purpose of the bias winding in figure 'B' shown in the illustration is for ____________. EL-0091 A. changing the direction of current in the control winding B. setting the operating point of the ... use of either AC or DC in the load circuit D. changing the direction of current through the load
Description : Which of the following statements is true about the illustrated circuit? EL-0030 A. The field rheostat is used for manual voltage control. B. if the generator is flat compounded then the field rheostat ... to act like a series motor and overspeed with the controller in the full raise position.
Description : As shown in the illustrations, most console schematic diagram sheets have letters and/or numbers placed across the top and numbers along the side boarders. The purpose of these markings is to ... small hole over a letter and number, what month and year that particular page was redrawn
Description : As shown in the illustrations, ordered rudder angle is fed back from the ________________. EL-0097 A. power unit to the magnetic amplifier B. steering gear to the control potentiometer C. magnetic amplifier to the steering gear D. rudder yoke to the non-followup controller
Description : As shown in the two illustrations for 'pitch control' and engine speed control', when the plant is in 'AUTO / CRUISE' propeller pitch is controlled by ___________. EL-0095 A. the 'trim potentiometer' and ... and speed by its 'trim pot'. D. either 'thrust lever' and speed by the 'trim potentiometer'
Description : As shown in the illustrations, fine adjustments such as 'weather' and 'turning rate' have no effect on steering stand operation when the 'operation control switch' is in ____________. EL-0097 A. GYRO B. HAND C. NFU D. DIFF
Description : As shown in the illustrations, feedback or rudder angle repeatback is used by the steering stand in which operational modes? EL-0097 A. Gyro-compass and hand steering only B. Hand steering and non-followup only C. Non-followup and gyro-compass only D. Gyro-compass and synchronizing only
Description : How many modes of rudder positioning are available using the steering stand shown in the illustrations? EL-0097 A. One B. Two C. Three D. Four
Description : Which of the illustrations listed below is representative of a motor controller's 'wiring' or 'connection' diagram? Book A. EL-0023 B. EL-0024 C. EL-0037 D. EL-0058
Description : Which of the illustrations listed below is representative of a motor controller's 'schematic' or 'elementary' diagram? A. EL-0023 B. EL-0007 C. EL-0037 D. EL-0058
Description : If power were lost to the winch shown in the illustration while in 'second point hoist' the winch would stop. When power is restored the winch would ______________. EL-0102 A. continue to run at ' ... switch' is returned to 'off' closing the 'reset' contacts and then moved to any 'run' position
Description : The RPM of an AC generator can be measured with a/an _____________. A. ammeter B. voltmeter C. vibrating reed meter D. synchroscope
Description : The electrical schematic illustrated in figure A, depicts a/an _____________. EL-0059 A. autotransformer B. Delta Wye transformer C. primary EMF generator D. potential transformer
Description : Which of the diagrams shown in the illustration depicts the proper method of aligning brushes on a commutator? EL-0057 A. A B. B C. C D. D
Description : As shown in the illustration, which of the drawings depicts a typical transistor? EL-0076 A. A B. B C. C D. D
Description : The three devices which make up the circuit shown in the illustration are ____________. EL-0087 A. flip-flops B. exclusive 'OR' gates C. summing op amps D. function generators
Description : If the pointer of the synchroscope is rotating in the slow direction when you are preparing to parallel two alternators, the _____________. A. incoming machine is turning faster than the load alternator B ... alternator is ready to split D. incoming machine is beginning to pick up some of the load