Description : The severity of line to ground and three phase faults at the terminals of an unloaded synchronous generator is to be same. If the terminal voltage is 1.0 pu, Z1=Z2=j0.1 p.u. and Z0= j0.05 p.u. for the alternator, then the required inductive ... a) 0.05 p.u. (b) 0.0166 p.u. (c) 0.1 p.u. (d) 0.15 p.u.
Last Answer : The severity of line to ground and three phase faults at the terminals of an unloaded synchronous generator is to be same. If the terminal voltage is 1.0 pu, Z1=Z2=j0.1 p.u. and Z0= j0.05 p.u. for the alternator, then the required inductive reactance for neutral grounding is 0.0166 p.u.