The X:R ratio of 220 kV line as compared to 400 kV line is?

1 Answer

Answer :

The X:R ratio of 220 kV line as compared to 400 kV line is smaller.

Related questions

Description : An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately (A) P (B) 2P (C) P / 2 (D) P / 4

Last Answer : An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately P / 4

Description : The minimum clearance between the ground and a 220 kV line is about (a) 4.3 m (b) 5.5 m (c) 7.0 m (d) 10.5 m

Last Answer : (c) 7.0 m

Description : The spacing between phase conductors of a 220 kV line is approximately equal to (a) 2 m (b) 3.5 m (c) 6 m (d) 8.5 m

Last Answer : (c) 6 m

Description : The minimum clearance between the ground and a 220 kV line is about (a) 4.3 m (b) 5.5 m (c) 7.0 m (d) 10.5 m

Last Answer : (c) 7.0 m

Description : What is the resistance value indicated by the multimeter scale illustrated, if the range switch is set at R X 100, and the needle is at the position indicated by the letter 'Y'? EL-0047 A. 220 ohms B. 240 ohms C. 2,400 ohms D. 24,000 ohms

Last Answer : Answer: C

Description : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of ... the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

Last Answer : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, ... line. The voltage of the alternator neutral with respect to ground during the fault is 642.2 V

Description : A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase line capacitance of 11.68 nF/km. Ignoring the length of the line, its ideal power transfer capability in MW is (A) 1204 MW (B) 1504 MW (C) 2085 MW (D) 2606 MW

Last Answer : A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase line capacitance of 11.68 nF/km. Ignoring the length of the line, its ideal power transfer capability in MW is 2085 MW

Description : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 ... load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

Last Answer : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/ ... MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be 36 

Description : The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is (A) 0.745 lagging (B) 0.775 lagging (C) 0.8 lagging (D) 0.85 lagging

Last Answer : Vscos¢s-Vrcos¢r=IR

Description : A voltage of 1000 kV is applied to an overhead line with its receiving end open. If the surge impedance of the line is 500 ohm, then the total surge power in the line ill

Last Answer : A voltage of 1000 kV is applied to an overhead line with its receiving end open. If the surge impedance of the line is 500 ohm, then the total surge power in the line ill 2000 MW .

Description : A 100 km long transmission line is loaded at 110 kV.if the loss of line is 5 MW and the load is 150 MVA, the resistance of the line is?

Last Answer : P = I^2  *  R 5*10^6  = [(150*10^6) / (110*10^3)  *  R R = 2.7 ohm/phase

Description : A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be   (a) 240 (b) 132 (c) 416 (d) 720

Last Answer : A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be 240 

Description : What are the levels of SF6 gas in 220 kV breaker and their significance?

Last Answer : 7 kg/cm2 - normal pressure 5.2 bar - alarm 5.0 bar - closing/tripping operation blocked. 

Description : What is the type of 220 kV circuit breaker? 

Last Answer : 220 kV, SF6 breaker, single pole, puffer type. 

Description : What are the main parts of 220 kV Circuit Breaker? 

Last Answer : Pole column filled with SF6 Pneumatic drive system with compressed air circuit Control cubicle unit 

Description : Give the details of switchyard 220 kV CB, Isolator, CT, CVT and lightning arrestor.  

Last Answer : 220 kV SF6 Circuit Breaker 1. Make - ABB 2. Air pressure blocking a. Close Block - 17.3 bar. b. Open block - 16.7 bar. c. Auto reclose block - 19 bar. 3. SF6 pressure block a. Alarm - 5. ... , storage and erection. Rated voltage : 216 kV rms. Operating voltage : 184 kV rms. 

Description : In 220 kV switchyard why lightning arrestor should be properly grounded?

Last Answer : a. During lightning, surges should be discharged to ground, otherwise it will puncture the equipment insulation and it is possible only when lightning arrestor is grounded properly.  b. In order to make it effective ... kV. Soil resistivity a should be minimum and may be it is 3.5 ohm per meter.  

Description : What is the difference in action of lock out pressure signal on 6.6 kV and 220 kV breakers?

Last Answer : When lock out signal comes to 6.6 kV breakers the breaker will trip. Where as in case of 220 kV breakers the breaker will not trip. If the breaker is open it will be open only and can not be closed. If it is in closed condition it will be closed.

Description : What are the protections provided for 220 kV lines and bus bars? 

Last Answer : a. Bus bar differential protection. b. Distance protection. c. Over current protection. d. Earth fault protection. 

Description : Why earth switches are provided in 220 kV bays?  

Last Answer : When bay CB trips, both end (station and grid) CB will trip. The earth switches are provided because the grid will always be alive so to prevent any shocks to the operator or maintenance personnel who is working on the line or bay due to accidental energizing of the bus.  

Description : Cables for 220 kV lines are invariably (a) mica insulated (b) paper insulated (c) compressed oil or compressed gas insulated (d) rubber insulated (e) none of the above

Last Answer : (c) compressed oil or compressed gas insulated

Description : For transmission of power over a distance of 500 km, the transmission voltage should be in the range (a) 150 to 220 kV (b) 100 to 120 kV (c) 60 to 100 kV (d) 20 to 50 kV

Last Answer : (a) 150 to 220 kV

Description : A single core cable is designed to work for a single phase system with a peak voltage of 220 kV. The maximum permissible stress in the dielectric is not to exceed 20 kV/mm. For economical size, the overall core diameter of the cable is (A) 28.2 mm (B) 26.4 mm (C) 24.4 mm (D) 22.0 mm

Last Answer : A single core cable is designed to work for a single phase system with a peak voltage of 220 kV. The maximum permissible stress in the dielectric is not to exceed 20 kV/mm. For economical size, the overall core diameter of the cable is 22.0 mm

Description : If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400:5, the plug setting multiplier will be

Last Answer : If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400:5, the plug setting multiplier will be 10 A

Description : The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: A) 400 Mega Joule B) 400 Kilo Joule C) 25 Mega Joule D) 25 Kilo Joule

Last Answer : The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: 400 Mega Joule

Description : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per ... 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

Last Answer : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained ... load to increase the line-to-line voltage at the load terminals to 11 kV is -10.1 MVAR

Description : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the ... the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

Last Answer : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume ... the shaft. The accelerating torque in the generator in MNm at the time of fault will be 1.018 

Description : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

Last Answer : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is 35 kA 

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

Last Answer : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is 1.316.

Description : The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be?

Last Answer : The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be 0.30.

Description : Why 6.6 kV transformer is resistance grounded by 10 ohms and current limited to 400 A?

Last Answer : a) To reduce burning and melting in faulted switchgear or machine. b) To reduce mechanical stresses in equipment. c) To reduce the electrical hazards by stray ground fault currents in the ground ... screen in 6.6 kV XLPE (cross-linked polyethylene). Therefore the cost of the cable decreases. 

Description : Air blast circuit breakers for 400 kV power system are designed to operate in (a) 100 microsecond (b) 50 millisecond (c) 0.5 sec (d) 0.1 sec

Last Answer : (b) 50 millisecond

Description : Overhead system can be designed for operation up to (a) 11 kV (b) 33 kV (c) 66 kV (d) 400 kV

Last Answer : (c) 66 kV

Description : Large industrial consumers are supplied electrical energy at (a) 400 V (b) 11 kV (c) 66 kV (d) 400 kV

Last Answer : (c) 66 kV

Description : Overhead system can be designed for operation up to (a) 11 kV (b) 33 kV (c) 66 kV (d) 400 kV

Last Answer : (c) 66 kV

Description : The generation voltage is usually (A) between 11 KV and 33 KV. (B) between 132 KV and 400 KV. (C) between 400 KV and 700 KV. (D) None of the above.

Last Answer : (A) between 11 KV and 33 KV.

Description : The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

Last Answer : 3500

Last Answer : Air blast circuit breakers for 400 kV power system are designed to operate in 50 millisecond.

Description : According to 1998 census the density of population in Punjab is: A. 220 Persons per Sq. Km B. 319 Persons per Sq. Km C. 353 Persons per Sq. Km D. 400 Persons per Sq. Km

Last Answer : ANSWER: C

Description : According to 1998 census the density of population in Punjab is: A. 220 Persons per Sq. Km B. 319 Persons per Sq. Km C. 353 Persons per Sq. Km D. 400 Persons per Sq. Km

Last Answer : ANSWER: C

Description : Suppose that we have numbers between 1 and 1000 in a binary search tree and want to search for the number 364. Which of the following sequences could not be the sequence of nodes examined? (A) 925, 221, 912, 245, 899, ... 926, 203, 912, 241, 913, 246, 364 (D) 3, 253, 402, 399, 331, 345, 398, 364 

Last Answer : (C) 926, 203, 912, 241, 913, 246, 364

Description : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of   (a) 250A (b) 50 A (c) 150 A (d) 350 A 

Last Answer : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of 250A

Description : The low voltage winding of a 400/230 V, 1-phase, 50 Hz transformer is to be connected to a 25 Hz, the supply voltage should be

Last Answer : The low voltage winding of a 400/230 V, 1-phase, 50 Hz transformer is to be connected to a 25 Hz, the supply voltage should be 115 V.

Description : The steady state stability limit as compared to the transient state stability limit is always

Last Answer : The steady state stability limit as compared to the transient state stability limit is always Greater

Description : What Happen If We Give 220 Volts Dc Supply To D Bulb R Tube Light?

Last Answer : Bulbs [devices] for AC are designed to operate such that it offers high impedance to AC supply. Normally they have low resistance. When DC supply is applied, due to low resistance, the current through lamp would be so high that it may damage the bulb element.

Description : The turns ratio of transforme 'A' shown in the illustration is four to one and all taps are evenly spaced. If 110 volts were applied to terminals 'X1' and 'X3', what would be indicated across 'H1' and 'H2'? EL-0082 A. 37.5 volts B. 55 volts C. 220 volts D. 440 volts

Last Answer : Answer: C

Description : The turns ratio of device 'B' shown in the illustration is two to one (total). If 220 volts were applied to terminals 'H1' & 'H2', what would be indicated across 'X1' & 'X4' with 'X2' & 'X3' connected and isolated? EL-0082 A. 55 volts B. 110 volts C. 220 volts D. 440 volts

Last Answer : Answer: B

Description : The turns ratio of device 'B' shown in the illustration is two to one (total). If 110 volts were applied to terminals 'X1,3' and 'X2,4', what would be indicated across 'H1' and 'H2'? EL-0082 A. 27.5 volts B. 55 volts C. 220 volts D. 440 volts

Last Answer : Answer: D

Description : The turns ratio of device 'B' shown in the illustration is two to one (total). If 440 volts were applied to terminals 'H1' & 'H2', what would be indicated across 'X1' & 'X4' with 'X2' & 'X3' connected and isolated? EL-0082 A. 110 volts B. 220 volts C. 880 volts D. 1760 volts

Last Answer : Answer: B