TYPES AND APPLICATIONS
Presently PVC and XLPE cables are being used in electrical installations. The discussion is
restricted to these two types only. The voltage ratings covered are up to and including 33 KV.
a) PVC INSULATED CABLES
PVC insulated cables, covered by IS 1554 are used where combination of ambient
temperature and temperature rise due to load results in conductor temperature not exceeding 70°C
under normal operation and 160°C under short circuit conditions.
b)XLPE INSULATED CABLES
XLPE insulated cables, covered by IS 7098 are used where combination of ambient
temperature and temperature rise due to load results in conductor temperature not exceeding 90°C
under normal operation and 250°C under short circuit conditions.
XLPE cables are particularly suitable in following situations.
• On vertical runs of unlimited difference in level,.
• At locations having severe vibration problems,
• At locations having higher ambient temperatures up to 70°C,
• At conditions demanding short time overload up to 120°C and,
• In systems having higher short circuit levels.