if the rated voltage from the power lines is applied to the primary of a single-phase transformer which is operated on no-load, then

1 Answer

Answer :

if the rated voltage from the power lines is applied to the primary of a single-phase transformer which is operated on no-load, then input voltage is sinusoidal and input current is non sinusoidal.

Related questions

Description : A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

Last Answer : 543A

Description : The voltage applied to the H.V. side of a transformer during S.C. test is 2% of the rated voltage. The core loss as the fraction of its rated core loss is (a) 4% (b) 0.4% (c) 0.25% (d) 0.04%

Last Answer : 0.04%

Description : A split-phase induction squirrel-cage motor will not come up to speed, even though the rated voltage, rated frequency, and rated load are applied. The suspected trouble could be due to _____________. A. a faulty centrifugal switch B. broken rotor bars C. worn bearings D. all of the above

Last Answer : Answer: D

Description : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m.

Last Answer : (D) 75 r.p.m.

Description : Why the earthing transformer primary voltage is 16.5 kV rated in main generator even though actual voltage during the E/F is root 3 times less?

Last Answer : The transformer should not saturate during E/F otherwise it will cause ferroresonance with the GT winding capacitance. Dangerous O/V and neutral shifting will occur. During loss of load or field ... saturation. Saturation can also occur due to point on wave of application causing flux doubling. 

Description : A 230 V/460 V single-phase transformer operating at 20 A and unity power factor has primary referred resistance of 0.2 Ω and reactance of 0.5 Ω. The approximate primary induced emf is (A) 216 V (B) 226 V (C) 234 V (D) 236 V

Last Answer : A 230 V/460 V single-phase transformer operating at 20 A and unity power factor has primary referred resistance of 0.2 Ω and reactance of 0.5 Ω. The approximate primary induced emf is 226 V

Description : A two -winding single phase transformer has a voltage regulation of 4.5% at full - load and unity power -factor. At full -load and 0.80 lagging power-factor, the voltage regulation will be: (A) 4.5% (B) less than 4.5% (C) more than 4.5% (D) none of the above

Last Answer : A two -winding single phase transformer has a voltage regulation of 4.5% at full - load and unity power -factor. At full -load and 0.80 lagging power-factor, the voltage regulation will be: more than 4.5%

Description : What is the supply rated o/p if two single phase transformer connect to give three phase o/p from a three phase I/p?

Last Answer : A. Each transformer is only capable of supplying 86.6%of its o/p rating

Description : The primary turns of a 444 V/222 V, 50 Hz single-phase transformer with a core cross-sectional area of 100 cm2, and a maximum flux density of 1.0 T is (A) 100 (B) 200 (C) 222 (D) 400

Last Answer : The primary turns of a 444 V/222 V, 50 Hz single-phase transformer with a core cross-sectional area of 100 cm2, and a maximum flux density of 1.0 T is 200

Description : Turn ratio of a transformer is 5. If 220 V AC is applied to its primary coil, voltage in the secondary coil will be: a. 44V b. 4.4 V c. 220V d. 1100V

Last Answer : c. 220V

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : Rated power of a bulb at V voltage is P. Now, same voltage V is applied in all conditions mentioned in Column I. Match this Column I with Column II in

Last Answer : Rated power of a bulb at V voltage is P. Now, same voltage V is applied in all conditions ... Column II in which actual total power consumed is given.

Description : A two-winding single phase transformer has a voltage regulation of 4.5% at full-load and unity power-factor. At full-load and 0.80 power-factor lagging load the voltage regulation will be (A) 4.5%. (B) less than 4.5%. (C) more than 4.5%. (D) 4.5% or more than 4.5%.

Last Answer : (C) more than 4.5%.

Description : In a three phase transformer, if the primary side is connected in star and secondary side is connected in delta, what is the angle difference between phase voltage in the two cases. (A) delta side lags by -30°. (B) star side lags by -30°. (C) delta side leads by 30°. (D) star side leads by -30°.

Last Answer : Ans: C This is vector group and has +30° displacement. Therefore, delta side leads by +30°.

Description : The rated voltage of a 3-phase power system is given as  A) rms phase voltage B) Peak phase voltage C) rms line to line voltage D) Peak line to line voltage

Last Answer : The rated voltage of a 3-phase power system is given as rms line to line voltage

Description : Periodic testing of circuit breakers is necessary to assure that a correctly rated and properly installed unit _________________. A. can trip faster as it increases in age B. will continue to provide ... not exceed its interrupting capacity D. be able to withstand at least 125% of applied voltage

Last Answer : Answer: B

Description : The torque produced by a motor when its shaft will not turn, even though rated voltage is applied to the stator, is known as _____________. A. locked-rotor torque B. pullout torque C. breakdown torque D. torque margin

Last Answer : Answer: A

Description : An unsaturated dc shunt motor runs at its rated speed when rated voltage is applied to it. If the supply voltage to the motor is reduced by 25%, the speed of the motor  (a) Increases by 25% (b) Remains the same (c) Decreases by 25% (d) Decrease only slightly by an amount less than 25% 

Last Answer : An unsaturated dc shunt motor runs at its rated speed when rated voltage is applied to it. If the supply voltage to the motor is reduced by 25%, the speed of the motor Remains the same

Description : In a single-phase induction motor when the rotor is stationary and voltage is applied to the stator, then (A) the flux is constant (B) the flux first decreases and then increases in ... increases and decreases in the opposite direction with the same magnitude (D) current flows through the rotor

Last Answer : In a single-phase induction motor when the rotor is stationary and voltage is applied to the stator, then the flux first decreases and then increases in the same direction

Description : A transformer at 25 Hz develops 20 W hysteresis loss and 50 W eddy current loss. If the applied voltage and frequency are doubled, the new core losses are (A) 140 W (B) 180 W (C) 240 W (D) 480 W

Last Answer : A transformer at 25 Hz develops 20 W hysteresis loss and 50 W eddy current loss. If the applied voltage and frequency are doubled, the new core losses are 240 W

Description : Why the open circuit test on a transformer is conducted at rated voltage?

Last Answer : A:The open circuit on a transformer is conducted at a rated voltage because core loss depends upon the voltage. This open circuit test gives only core loss or iron loss of the transformer.

Last Answer : When a given transformer is run at its rated voltage but reduced frequency, its core flux density is increased.

Description : If a transformer is switched on to a voltage more than the rated voltage?

Last Answer : If a transformer is switched on to a voltage more than the rated voltage its power factor will deteriorate.

Description : The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

Last Answer : 3500

Description : A single phase transformer is designed to operate from 50 Hz, 1100 V supply and to have an output voltage of 240 V at no load. The core has mean area of 30 cm2 and the flux density has not to exceed 1.3T. The number of secondary turns will be (a) 1270 (b) 1017 (c) 768 (d) 277  

Last Answer : E2=e2=4.44*flux*N2*f=240 V Flux=Flux density* Area Area=30 cm2  =30*10-4 m2 Flux= 1.3*30*10-4  Wb=39*10-4 Wb E=240= 4.44*39*10-4 *N2*50      N2=277.

Description : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he

Last Answer : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he 0.52

Description : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is: (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m

Last Answer : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is: 75 r.p.m

Description : A 3-phase induction motor is driving a constant torque load at rated voltage and frequency. If both voltage and frequency are halved, following statements relate to the new condition if stator resistance, leakage reactance and core loss are ... (A) All (B) 1, 2 and 3 (C) 2, 3 and 4 (D) 1 and 4

Last Answer : A 3-phase induction motor is driving a constant torque load at rated voltage and frequency. If both voltage and frequency are halved, following statements relate to the new condition if stator resistance, leakage reactance and core loss are ... A) All (B) 1, 2 and 3 (C) 2, 3 and 4 (D) 1 and 4

Description : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

Last Answer : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 15.79 kA

Description : A three-phase cage induction motor is started by direct-on-line (DOL) switching at the rated voltage. If the starting current drawn is 6 times the full load current, and the full load slip is 4%, then ratio of the ... load torque is approximately equal to (A) 0.24 (B) 1.44 (C) 2.40 (D) 6.00

Last Answer : A three-phase cage induction motor is started by direct-on-line (DOL) switching at the rated voltage. If the starting current drawn is 6 times the full load current, and the full load slip is 4%, then ratio of the starting developed torque to the full load torque is approximately equal to 1.44

Description : If a transformer primary is energised from a square wave voltage source, its output voltage will be a:  (A) square wave (B) sine wave (C) triangular wave (D) pulse wave

Last Answer : D

Description : An alternator is delivering rated current at rated voltage and 0.8 power-factor lagging. For delivering rated current at rated voltage and 0.8 poWer—factor leading, the required excitation will be:  (A) less  (B) more (C) more or less (D) the same

Last Answer : An alternator is delivering rated current at rated voltage and 0.8 power -factor lagging. For delivering rated current at rated voltage and 0.8 power -factor leading, the required excitation will be: more 

Description : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be :  (A) 34.64 kVA (B) 75 kVA (C) 20 kVA (D) None of the above

Last Answer : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be : 34.64 kVA

Description : A single-phase ac voltage source has 200 V rms and a system connected consumes an active power of 300 W. What is the reactive power consumed by the system if 2.5 A rms current is drawn ?  (a) 100 VAR (b) 200 VAR (c) 300 VAR (d) 400 VAR

Last Answer : A single-phase ac voltage source has 200 V rms and a system connected consumes an active power of 300 W. What is the reactive power consumed by the system if 2.5 A rms current is drawn ? 400 VAR

Description : A single-phase induction motor starts, comes up to about 75% rated speed, slows down to a lower speed, and accelerates again. The problem is most likely in the ____________. A. starting winding B. running winding C. starting capacitor D. running centrifugal switch

Last Answer : Answer: B

Description : A single phase wattmeter rated for 500 V; 5A is having full scale deflection of 1000 watt. What is multiplying factor of the wattmeter?

Last Answer : Answer :

Description : For a traction transformer circuit breaker state: 1) Rated current and rupturing capacity 2) Any two tests it should be capable of withstanding 3) Overall tripping time and relay time.

Last Answer : Ans: 1) Rated current --- 750 A and Rupturing capacity --- 500 MVA  2) Any two tests it should be capable of withstanding --- Breaking test , Reclosing test , Endurance test ( any two )  3) Overall tripping time --- 0.14 sec and Relay time --- 0.04 sec 

Description :  An AC supply of 230 V is applied to a half-wave rectifier circuit through a transformer having primary to secondary turn’s ratio 12:1. The peak inverse voltage is A) 8.62 V B) 12 V C) 19.17 V D) 27.11 V 

Last Answer :  An AC supply of 230 V is applied to a half-wave rectifier circuit through a transformer having primary to secondary turn’s ratio 12:1. The peak inverse voltage is A) 8.62 V B) 12 V C) 19.17 V D) 27.11 V 

Description : The leads to the primary and the high-voltage secondary windings of a power transformer usually are of what color?

Last Answer : Primary leads-black; secondary leads red.

Description : (a) Define permeability. (b) Define MMF. (c) Define form factor of an alternating quantity. (d) Define frequency and time period of an alternating quality. (e) Define transformation ratio of transformer. ... and state the meaning of each term used. (g) Give two applications of single phase motors. 

Last Answer : Permeability : It is the ability of a magnetic/Non magnetic material to allow setting up of flux in it.  MMF : The magneto motive force (MMF) is the force required to setup flux in a magnetic / ... applications of single phase motors : Water pumps, ceiling fan, lathe machine

Last Answer : Advantages of three phase transformer over bank of single phase transformers:  For identical magnitudes of power transformation, i) Saving in copper conductor. ii) Saving in electromagnetic core material. ... material such as insulating oil. v) Saving in overall cost. vi) Higher efficiency.

Description : The voltage at the reference electrode of the circuit shown in the illustration is applied to the input of a/an ______________. EL-0090 A. class A detector whose output drives an ... drives an 2-stage isolation transformer D. magnetic amplifier whose output controls a saturable reactor

Last Answer : Answer: D

Description : No load current in a transformer: (A) lags the applied voltage by 90° (B) lags the applied voltage by somewhat less than 90° (C) leads the applied voltage by 90° (D) leads the applied voltage by somewhat less than 90°

Last Answer : Ans: B The primary input current under no load conditions has to supply (i) iron losses in the core i.e hysteresis loss and eddy current loss (ii) a very small amount of Cu loss in the primary (there being no Cu loss in secondary as it is open)

Description : An AC supply of 230 V is applied to half wave rectifier circuit. A transformer turns ratio is 20 : 1. Find i) Output DC voltage (ii) Peak Inverse Voltage (PIV)

Last Answer : Solution:

Last Answer : The no load current in a transformer lags behind the applied voltage by an angle of about 75°.

Description : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are?

Last Answer : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are hysteresis and eddy current losses.

Description : [23] Transformers are rated in KVA instead of KW because A. load power factor is often not known B. KVA is fixed whereas KW depends on load power factor C. Total transformer loss depends on volt ampere D. It has become customary

Last Answer : C. Total transformer loss depends on volt ampere

Description : A single-phase, 230 V, 50 Hz ac mains fed step down transformer (4:1) is supplying power to a half-wave uncontrolled ac-dc converter used for charging a battery (12 V dc) with the series current limiting resistor being 19.04 Ohm. The charging current is  (A) 2.43 A (B) 1.65 A (C) 1.22 A (D) 1.0 A

Last Answer : A single-phase, 230 V, 50 Hz ac mains fed step down transformer (4:1) is supplying power to a half-wave uncontrolled ac-dc converter used for charging a battery (12 V dc) with the series current limiting resistor being 19.04 Ohm. The charging current is 1.0 A