A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited. 

(A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

2 Answers

Answer :

If the secondary is accidentally short circuited then AEs=0

image

Answer :

543A

Related questions

Description : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

Last Answer : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is 80 MJ

Description : A 60 Hz, 4 pole turbo generator rated 100 MVA, 13.8 KV has an inertia constant of 10 MJ/MVA. Find the stored energy in the rotor at synchronous speed.  (A) 10 MJ (B) 100 J (C) 1000 J (D) 1000 MJ 

Last Answer : c

Description : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of   (a) 250A (b) 50 A (c) 150 A (d) 350 A 

Last Answer : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of 250A

Description : A 220/440 V, 50 Hz, 5 KVA, single phase transformer operates on 220V, 40Hz supply with secondary winding open circuited. Then (A) Both eddy current and hysteresis losses decreases. (B) Both ... same but hysteresis loss increases. (D) Eddy current loss increases but hysteresis loss remains the same.

Last Answer : (A) Both eddy current and hysteresis losses decreases.

Description : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: (A) both the eddy current and the hysteresis losses will decrease ... losses will increase (D) eddy current losses will increase but the hysteresis losses will remain the same

Last Answer : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: both the eddy current and the hysteresis losses will decrease

Description : The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

Last Answer : 3500

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : A 1100 kVA, 11 kV/1.1 kV conventional two-winding transformer is connected as a 12.1 kV/11 kV step-down auto-transformer. The rating of the auto-transformer is (A) 1000 kVA (B) 1100 kVA (C) 11000 kVA (D) 12100 kVA

Last Answer : A 1100 kVA, 11 kV/1.1 kV conventional two-winding transformer is connected as a 12.1 kV/11 kV step-down auto-transformer. The rating of the auto-transformer is 12100 kVA

Description : [23] Transformers are rated in KVA instead of KW because A. load power factor is often not known B. KVA is fixed whereas KW depends on load power factor C. Total transformer loss depends on volt ampere D. It has become customary

Last Answer : C. Total transformer loss depends on volt ampere

Description : Why the earthing transformer primary voltage is 16.5 kV rated in main generator even though actual voltage during the E/F is root 3 times less?

Last Answer : The transformer should not saturate during E/F otherwise it will cause ferroresonance with the GT winding capacitance. Dangerous O/V and neutral shifting will occur. During loss of load or field ... saturation. Saturation can also occur due to point on wave of application causing flux doubling. 

Description : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the ... the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

Last Answer : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume ... the shaft. The accelerating torque in the generator in MNm at the time of fault will be 1.018 

Description : A single-phase, 50 kVA, 250 V/500 V two winding transformer has an efficiency of 95% at full load, unity power factor. If it is re-configured as a 500 V/750 V auto-transformer, its efficiency at its new rated load at unity power factor will be  (A) 95.752% (B) 97.851% (C) 98.276% (D) 99.241%

Last Answer : A

Description : A 3-phase circuit breaker is rated at 1250 A, 2000 MVA, 33 kV, 4s. Its making current capacity will be   (a) 35 kA (b) 89 kA (c) 79 kA (d) 69 kA

Last Answer : 89

Description : The primary turns of a 444 V/222 V, 50 Hz single-phase transformer with a core cross-sectional area of 100 cm2, and a maximum flux density of 1.0 T is (A) 100 (B) 200 (C) 222 (D) 400

Last Answer : The primary turns of a 444 V/222 V, 50 Hz single-phase transformer with a core cross-sectional area of 100 cm2, and a maximum flux density of 1.0 T is 200

Description : if the rated voltage from the power lines is applied to the primary of a single-phase transformer which is operated on no-load, then

Last Answer : if the rated voltage from the power lines is applied to the primary of a single-phase transformer which is operated on no-load, then input voltage is sinusoidal and input current is non sinusoidal.

Description : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Last Answer : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Description : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be :  (A) 34.64 kVA (B) 75 kVA (C) 20 kVA (D) None of the above

Last Answer : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be : 34.64 kVA

Description : What is the slip (as a percentage) when a 6 pole single phase induction motor operating on 220 V and 60 Hz is rotating at speed of 1140 rpm? A) 60% B) 5% C) 10% D) None of these

Last Answer : What is the slip (as a percentage) when a 6 pole single phase induction motor operating on 220 V and 60 Hz is rotating at speed of 1140 rpm? A) 60% B) 5% C) 10% D) None of these

Description : A single phase 60 Hz generator supplies an inductive load of 4500kW at a power factor of 0.80 lagging by means of a 20 km long overhead transmission line. The line resistance and inductance are 0.0195 ohm and 0.60 mH ... voltage regulation of the line.  (A) 12.59% (B) 16.34% (C) 32.68% (D) 41.15% 

Last Answer : Answer is C

Description : A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

Last Answer : 800

Description : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

Last Answer : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is 1.316.

Description : What is considered the threshold of audibility at 3000 Hz? A. 10-12 W/m2 B. 10-16 W/m2 C. 10-12 W/cm2 D. 10-15 W/cm2

Last Answer : A. 10-12 W/m2

Description : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

Last Answer : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is 35 kA 

Description : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

Last Answer : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 15.79 kA

Description : Why are generators rated in kVA not in kW ?

Last Answer : Because It's rating of generator kva is apparent power. Kw is active power which we use. And one is kvar reactive power.

Description : A single phase transformer is designed to operate from 50 Hz, 1100 V supply and to have an output voltage of 240 V at no load. The core has mean area of 30 cm2 and the flux density has not to exceed 1.3T. The number of secondary turns will be (a) 1270 (b) 1017 (c) 768 (d) 277  

Last Answer : E2=e2=4.44*flux*N2*f=240 V Flux=Flux density* Area Area=30 cm2  =30*10-4 m2 Flux= 1.3*30*10-4  Wb=39*10-4 Wb E=240= 4.44*39*10-4 *N2*50      N2=277.

Description : A single-phase, 230 V, 50 Hz ac mains fed step down transformer (4:1) is supplying power to a half-wave uncontrolled ac-dc converter used for charging a battery (12 V dc) with the series current limiting resistor being 19.04 Ohm. The charging current is  (A) 2.43 A (B) 1.65 A (C) 1.22 A (D) 1.0 A

Last Answer : A single-phase, 230 V, 50 Hz ac mains fed step down transformer (4:1) is supplying power to a half-wave uncontrolled ac-dc converter used for charging a battery (12 V dc) with the series current limiting resistor being 19.04 Ohm. The charging current is 1.0 A

Description : The hysteresis and eddy current losses of a single phase transformer working on 200 V, 50 Hz supply are Ph and Pe respectively. The percentage decrease in these when operated on a 160 V, 40 Hz supply are   (a) 32, 36 (b) 20, 36 (c) 25, 50 (d) 40, 80 

Last Answer : The hysteresis and eddy current losses of a single phase transformer working on 200 V, 50 Hz supply are Ph and Pe respectively. The percentage decrease in these when operated on a 160 V, 40 Hz supply are 20, 36

Description : Ten signals, each requiring 3000 Hz, are multiplexed on to a single channel using FDM. How much minimum bandwidth is required for the multiplexed channel ? Assume that the guard bands are 300 Hz wide. (A) 30,000 (B) 32,700 (C) 33,000 (D) None of the above

Last Answer : (B) 32,700

Description : What is the supply rated o/p if two single phase transformer connect to give three phase o/p from a three phase I/p?

Last Answer : A. Each transformer is only capable of supplying 86.6%of its o/p rating

Description : The corona loss of a 3-phase transmission line is 100 kW at 60 kV/phase and 25 kW at 50 kV/phase. The disruptive critical voltage is (A) 40 kV (B) 43.6 kV (C) 49.6 kV (D) 50 kV

Last Answer : The corona loss of a 3-phase transmission line is 100 kW at 60 kV/phase and 25 kW at 50 kV/phase. The disruptive critical voltage is 40 kV

Description : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is  (A) 50.0% (B) 70.7% (C) 141.4% (D) 200.0%

Last Answer : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is 70.7%

Description : The per unit impedance of a circuit element is 0.30. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be:  (A) 0.3 (B) 0.6 (C) 0.003 (D) 0.006 

Last Answer : 3

Description : The primary winding of a 220/6 V, 50 Hz transformer is energised from 110 V, 60 Hz supply. The secondary output voltage will be; (A) 3.6 (B) 2.5 V (C) 3.0 V (D) 6.0 V

Last Answer : The primary winding of a 220/6 V, 50 Hz transformer is energised from 110 V, 60 Hz supply. The secondary output voltage will be: 3.0 V

Description : A 3-phase, 400 votts, 50 Hz, 100 KW, 4 pole squirrel cage induction motor with a rated slip of 2% will have a rotor speed of (A) 1500 rpm (B) 1470 rpm (C) 1530 rpm (D) 1570 rpm

Last Answer : Ans: B N = NS (1-S) and NS =120 f / p =120 x 50 /4 = 1500 rpm ∴N= 1500 (1-0.02) =1470 rpm

Description : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m.

Last Answer : (D) 75 r.p.m.

Description : The locked rotor current in a 3-phase, star connected 15 , kW 4 , pole 230 V , 50 Hz induction motor at rated conditions is 50 A. Neglecting losses and magnetizing current, the approximate locked rotor line current drawn when the motor ... Hz supply is  (A) 58.5 A (B) 45.0 A (C) 42.7 A (D) 55.6 A

Last Answer : The locked rotor current in a 3-phase, star connected 15 , kW 4 , pole 230 V , 50 Hz induction motor at rated conditions is 50 A. Neglecting losses and magnetizing current, the approximate locked rotor line current drawn when the motor is connected to a 236 , V 57 Hz supply is 45.0 A 

Description : A 3 phase, 400 volts, 50 Hz, 100 kW, 4 pole squirrel cage induction motor with a rated slip of 2% will have a rotor speed of: (A) 1500 rpm (B) 1470 rpm (C) 1530 rpm (D) 1570 rpm

Last Answer : 1470rpm

Description : At full -load of a transformer, the iron loss and copper loss are 3000 W and 4000 W respectively. Then total loss at maximum efficiency is :  (A) 7000 W (B) 6000 W (C) 8000 W (D) 4000 W

Last Answer : At full -load of a transformer, the iron loss and copper loss are 3000 W and 4000 W respectively. Then total loss at maximum efficiency is : 6000 W

Description : A single core cable is designed to work for a single phase system with a peak voltage of 220 kV. The maximum permissible stress in the dielectric is not to exceed 20 kV/mm. For economical size, the overall core diameter of the cable is (A) 28.2 mm (B) 26.4 mm (C) 24.4 mm (D) 22.0 mm

Last Answer : A single core cable is designed to work for a single phase system with a peak voltage of 220 kV. The maximum permissible stress in the dielectric is not to exceed 20 kV/mm. For economical size, the overall core diameter of the cable is 22.0 mm

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Last Answer : D. Loading of the transformers not in proportion to their kVA ratings

Description : Why alternators are rated in KVA?

Last Answer : The KVA rating of ac machine depends on the power factor of the load. The power factor in turn depends on the operating conditions. The operating conditions differ from place to place. Therefore the KVA rating is specified for all ac machines.

Description : Why are Alternators rated in kVA and not in kW?

Last Answer : The continuous power rating of any machine is generally defined as the power the machine or apparatus can deliver for a continuous period so that the losses incurred in the machine gives rise to a ... generator , the Alternators have only their apparent power in VA/kVA/MVA as their power rating.

Description : why transformers are rated in kVA ?

Last Answer : A:Copper loss of a transformer depends on current and iron loss on voltage . Hence total losses depends on Volt- Ampere and not on the power factor. That is why the rating of transformers are in kVA and not in kW.

Description : A 100 kVA, 415 V(line), star-connected synchronous machine generates rated open circuit voltage of 415 V at a field current of 15 A. The short circuit armature current at a field current of 10 A is equal to the ... unit saturated synchronous reactance is  (A) 1.731 (B) 1.5 (C) 0.666 (D) 0.577

Last Answer : 0.6

Description : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is: A) 300 kVA B) 75 kVA C) 259 kVA D) 249 kVA

Last Answer : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is:  259 kVA

Description : KVA of an Auto-transformer of V1/V2 = 220/150 for a load of 100KVA is: a. 100KVA b. 50KVA c. 33.3KVA d. 20KVA 

Last Answer : KVA of an Auto-transformer of V1/V2 = 220/150 for a load of 100KVA is: a. 100KVA b. 50KVA c. 33.3KVA d. 20KVA 

Description : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: A. 4 kVA B. 0.25 kVA C. 16 kVA D. 8 kVA

Last Answer : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: 16 kVA

Description : One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

Last Answer : 100