The voltage at the two ends of a transmission line are 132 KV and its reactance is
40 ohm. The Capacity of the line is
 (A) 435.6 MW (B) 217.8 MW
 (C) 251.5 MW (D) 500 MW

1 Answer

Answer :

(A) 435.6 MW

Related questions

Description : If voltage at the two ends of a transmission line is 132 kV and its reactance is 40 Ohms, the capacity of the line will be: (A) 435.6 MW (B) 217.8 MW(C) 251.5 MW (D) 500 MW

Last Answer : If voltage at the two ends of a transmission line is 132 kV and its reactance is 40 Ohms, the capacity of the line will be: 435.6 MW

Description : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

Last Answer : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 15.79 kA

Description : A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be   (a) 240 (b) 132 (c) 416 (d) 720

Last Answer : A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be 240 

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : For transmission of power over a distance of 200 km, the transmission voltage should be (a) 132 kV (b) 66 kV (c) 33 kV (d) 11 kV

Last Answer : (a) 132 kV

Description : The generation voltage is usually (A) between 11 KV and 33 KV. (B) between 132 KV and 400 KV. (C) between 400 KV and 700 KV. (D) None of the above.

Last Answer : (A) between 11 KV and 33 KV.

Description : The operating voltage of extra high tension cables is upto (a) 6.6 kV (b) 11 kV (c) 33 kV (d) 66 kV (e) 132 kV

Last Answer : (d) 66 kV

Description : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

Last Answer : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is 0.01

Description : For transmission of power over a distance of 500 km, the transmission voltage should be in the range (a) 150 to 220 kV (b) 100 to 120 kV (c) 60 to 100 kV (d) 20 to 50 kV

Last Answer : (a) 150 to 220 kV

Description : cables are used for 132 kV lines. (a) High tension (b) Super tension (c) Extra high tension (d) Extra super voltage

Last Answer : (d) Extra super voltage

Description : The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

Last Answer : 3500

Description : Transmission voltage of ll kV is normally used for distances upto (a) 20—25 km (b) 40—50 km (c) 60—70 km (d) 80—100 km

Last Answer : (a) 20—25 km

Description : A three-phase synchronous motor has a terminal voltage of 460 V and a terminal current of 120 A at a power factor of 0.95 lagging, synchronous reactance of 1.68 ohm and the field current is 47 A. The field to armature mutual ... _____________.      (a). 20mH   (b). 16mH   (c). 24mH   (d). 22mH

Last Answer : 22

Description : An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately (A) P (B) 2P (C) P / 2 (D) P / 4

Last Answer : An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately P / 4

Description : A three phase transmission line delivers a load of 5 MW at 0.8 power factor lagging. Resistance of each conductor is 0.5 ohm / km. Receiving end voltage is 33 kV. If the line loss is not to exceed 10%, determine the length of the line.  (A) 7 km (B) 27.9 km (C) 56.8 km (D) 13.9 km

Last Answer : B

Description : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per ... 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

Last Answer : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained ... load to increase the line-to-line voltage at the load terminals to 11 kV is -10.1 MVAR

Description : How many insulator disc used for 33 kV transmission voltage line?

Last Answer : 5,As 33kv is Vrms

Description : A generating station has a maximum demand of 50 Mw, a load factor of 60%, a plant capacity factor of 45% and if the plant while running as per schedule, were fully loaded. The daily energy produced will be

Last Answer : A generating station has a maximum demand of 50 Mw, a load factor of 60%, a plant capacity factor of 45% and if the plant while running as per schedule, were fully loaded. The daily energy produced will be 720 MW.

Description : The first stage of a two-stage amplifier has a voltage gain of 10, a 600 Ω input resistor, a 1600Ω equivalent noise resistance and 27kΩ output resistor. For the second stage, these values are 25, 81kΩ, 19kΩ, and 1MΩ, ... this two stage amplifier. A. 2,518 kΩ B. 2,518 Ω C. 251.8 Ω D. 12,518 Ω

Last Answer : B. 2,518 Ω

Description : The dielectric strength of transformer oil should be (A) 100 V. (B) 5 KV. (C) 30 KV. (D) 132 KV.

Last Answer : (C) 30 KV.

Description : Pressure cables are generally not used beyond (a) 11 kV (b) 33 kV (c) 66 kV (d) 132 kV

Last Answer : (c) 66 kV

Description : High tension cables are generally used up to (a) 11kV (b) 33kV (c) 66 kV (d) 132 kV

Last Answer : (a) 11kV

Description : An AC circuit has capacitance arranged in series. If the line voltage remains constant, the capacitive reactance value can be varied by changing the _____________. A. line frequency B. resistance C. number of commutating poles D. number of interpoles

Last Answer : Answer: A

Description : An AC circuit has a capacitive reactance of 30 ohms in addition to an inductive reactance of 40 ohms connected in series. What is the reactance of the circuit? A. 8.37 ohms B. 10.00 ohms C. 50.00 ohms D. 70.00 ohms

Last Answer : Answer: B

Description : A loss less transmission line having Surge Impedance Loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30%. Then, SIL of the compensated transmission line will be (A) 1835 MW (B) 2280 MW (C) 2725 MW (D) 3257 MW

Last Answer : A loss less transmission line having Surge Impedance Loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30%. Then, SIL of the compensated transmission line will be 2280 MW

Description : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is (A) 2/15 p.u. (B) 5/6 p.u. (C) 1.0 p.u. (D) 1.2 p.u.

Last Answer : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is 5/6 p.u.

Description : What is the minimum voltage required for starting of 6.6 kV motors?

Last Answer : Minimum 80% of rated voltage.

Description : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 ... load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

Last Answer : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/ ... MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be 36 

Description : A series combination of resistance 100 ohm and capacitance 50µf is connected in series to a 230 V, 50HZ supply. Calculate (i) Capacitive reactance (ii) Current (iii) Power factor (iv) Power consumed 

Last Answer : For RC series circuit

Description : The reactance offered by a capacitor to an alternating current of frequency 50 Hz is 10 ohm. If frequency is increased to 100 Hz, the reactance will be (a) 2.5 ohm (b) 5.0 ohm (c) 20.0 ohm (d) 40.0 ohm 

Last Answer : Xc = 1/(2*pi*f*c) so when f is double .... Xc will be half ... Ans is 5ohm

Description : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of ... the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

Last Answer : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, ... line. The voltage of the alternator neutral with respect to ground during the fault is 642.2 V

Description : When a voltage of 132 VDC is applied to the illustrated circuit with a resistance of 10,230 ohms the current will be ________. EL-0018 A. 0.012 amps B. 77.5 milliamps C. 10,362 amps D. 0.792 amps

Last Answer : Answer: A

Description :  A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is?

Last Answer :  A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is 0.6 lagging.

Description : In an AC transmission line difference in phase of voltage at two ends of the line is due to (a) System voltage (b) Insulators (c) Resistance of line (d) Reactance of line

Last Answer : reactance of line

Description : When a voltage of 132 VDC is applied to the illustrated circuit with a resistance of 237 ohms the current will be ________. EL-0018 A. 1.236 amps B. 2.048 amps C. 0.557 amps D. 4.200 amps

Last Answer : Answer: C

Description : When a voltage of 132 VDC is applied to the illustrated circuit with a resistance of 470 ohms the current will be ________. EL-0018 A. 0.280 amps B. 3.560 amps C. 602 milliamps D. 1.673 amps

Last Answer : Answer: A

Description : When a voltage of 132 VDC is applied to the illustrated circuit with a resistance of 110 ohms the current will be ________. EL-0018 A. 0.833 amps B. 1.2 amps C. 2.2 amps D. 242 milliamps

Last Answer : Answer: B

Description : When a voltage of 132 VDC is applied to the illustrated circuit with a resistance of 32 ohms the current will be ________. EL-0018 A. 0.242 amps B. 4.125 amps C. 7.757 amps D. 1.64 amps

Last Answer : Answer: B

Description : If a voltage of 132 VDC is applied to the illustrated circuit where the resistance is 12 ohms, then current will be ___________. EL-0018 A. 0.090 amps B. 1.090 amps C. 11 amps D. 144 milliamps

Last Answer : Answer: C

Description : Why the earthing transformer primary voltage is 16.5 kV rated in main generator even though actual voltage during the E/F is root 3 times less?

Last Answer : The transformer should not saturate during E/F otherwise it will cause ferroresonance with the GT winding capacitance. Dangerous O/V and neutral shifting will occur. During loss of load or field ... saturation. Saturation can also occur due to point on wave of application causing flux doubling. 

Description : The component labeled 'CR1' in the circuit shown in the illustration __________________. EL-0085 A. varies its anode/cathode polarity depending on 'RL' current B. rectifies the varying voltage from the ... reactance to smooth ripple D. establishes a constant reference voltage for the base of 'Q1'

Last Answer : Answer: D

Description : A generating station has a maximum demand of 500 MW. The annual load factor is 50 percent. The energy generated per annum will be: A) 2.19 x 106 MWhr B) 600 MWhr C) 250 MWhr D) 7.50 x 106 MWhr

Last Answer : A generating station has a maximum demand of 500 MW. The annual load factor is 50 percent. The energy generated per annum will be: 2.19 x 106 MWhr 

Description : Three factors responsible for the change in voltage as load is applied to an AC generator are: 1) the drop in resistance in the armature circuit, 2) the change in flux, and 3) the ____________. A. armature winding speed B. inductance load drop C. coil pitch factor D. armature reactance voltage drop

Last Answer : Answer: D

Description : In an AC circuit, the inductive reactance of a coil varies with the _______________. A. resistance of the circuit B. frequency of the circuit C. voltage of the circuit D. current of the circuit

Last Answer : Answer: B

Description : Decreasing the frequency in a capacitive circuit while maintaining a constant circuit voltage, will result in a/an _____________. A. increase in apparent power B. decrease in circuit current C. decrease in capacitive reactance D. decrease in total impedance

Last Answer : Answer: B

Description : What Is Meant By Reactance Voltage?

Last Answer : An armature coil has certain self inductance. When coil undergoes commutation, there is change in current (di) in that coil and the commutation takes certain time(dt). Thus there is self-induced emf ... by L(di/dt). This EMF induced in the coil undergoing commutation is called reactance voltage.

Description : In series RLC circuit at resonant a) Voltage is in phase with current b) Current is maximum c) Inductive reactance = Capacitive reactance d) All of the above

Last Answer : Ans: All of the above

Description : The synchronous reactance of the synchronous machine is ______________. (A) Ratio between open circuit voltage and short circuit current at constant field current (B) Ratio between short circuit ... (D) Ratio between short circuit voltage and open circuit current at different field current

Last Answer : Ans. A The Synchronous reactance of a synchronous machine is a total steady state reactance, presented to applied voltage, when rotor is running synchronously without excitation. Therefore , XS = Ef / IS = Emf of OC for same If / short circuit current

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer : A. As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer :  As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps