5 The efficiency of a transformer is maximum when
A. It runs at half full load
B. it runs at full load
C. its Cu loss equal iron loss
D. it runs over load

1 Answer

Answer :

C. Its cu loss equal iron loss

Related questions

Description : 73 The full load copper loss of a transformer is 1600W. At half-load the copper loss will be A. 6400W B. 1600W C. 800W D. 400W

Last Answer : D. 400W

Description : A 50 KVA transformer has iron loss 2 kW on full load. Calculate its iron loss at 75% of full load.

Last Answer : Iron loss is dependent on voltage and independent of load. Hence iron loss at 75% of Load = Iron loss at full load = 2 kW

Description : 74)Power transformers are generally designed to have maximum efficiency around A. No load B. Half load C. Near full load D. 10% overload

Last Answer : C. Near full load

Description : [23] Transformers are rated in KVA instead of KW because A. load power factor is often not known B. KVA is fixed whereas KW depends on load power factor C. Total transformer loss depends on volt ampere D. It has become customary

Last Answer : C. Total transformer loss depends on volt ampere

Description : Define: (i) Commercial efficiency of a transformer and  (ii) All day efficiency of a transformer.

Last Answer : (i) Commercial Efficiency : It is the ratio of output power in watt to the input power in watt. (ii) All day efficiency of a transformer: It is the ratio of output energy in kWh to the input energy in kWh in the 24 hours of the day

Description : The efficiency of two identical transformers under load conditions can be determined by?

Last Answer : The efficiency of two identical transformers under load conditions can be determined by back-to-back test.

Last Answer : Distribution transformers are generally designed for maximum efficiency around 50% load.

Last Answer : Power transformers are generally designed to have maximum efficiency around near full-load.

Description : 78 Which type of winding is used in 3 phase shell type transformer? A. Circular type B. Sandwich type C. Cylindrical type D. Rectangular type

Last Answer : B. Sandwich type

Description : Why a transformer requires cooling. What are the methods of cooling transformers?

Last Answer : Ans. Transformers requires cooling as they get heated up due to various losses taking place in the transformer. (like iron of copper losses) Following are the methods of cooling of transformer. a. Natural ... . Forced oil air Natural Cooling (OFAN). d. Forced oil and forced Air cooling (OFAF).

Description : State any two conditions for parallel operation of 3-phase transformer.

Last Answer : Conditions for Parallel operation of 3 phase transformer 1) Voltage ratings of both the transformers must be identical. 2) Percentage or p.u. impedance should be equal in magnitude. 3) X/R ratio ... between primary & secondary voltages must be same. 6) Phase sequence on both sides must be same.

Description : Compare core type transformer and shell type transformer on the following parameters. (i) Types of winding used, (ii) Application

Last Answer : Ans:

Description : State any four properties of Ideal transformer.

Last Answer : Properties of Ideal transformer: 1) No losses (iron and copper losses), hence no temperature rise. 2) No magnetic leakage i.e (Coefficient of coupling between primary and secondary windings is unity) 3) Zero winding ... drop i.e. E1 = V1, E2 = V2 5) Efficiency 100 %. 6) Regulation 0 %.

Description : Why circuit breaker connect b)w two transformer  (same rating

Last Answer : Because two transformers connection is in parallel to share the load if any transformer is receives the surge current because of the fault so to protect the other transformer from the fault. 

Last Answer : A common method of cooling a power transformer is oil cooling.

Last Answer : Harmonics in transformer result in increased core losses, increased I2R losses, and magnetic interference with communication circuits.

Description : One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

Last Answer : 100

Description :  A transformer has maximum efficiency at 3/4 full load. The ratio of its iron losses and full load copper loss is : -  a) 16/9 b) 4 / 3 c) 3/4 d) 9 /16

Last Answer :  A transformer has maximum efficiency at 3/4 full load. The ratio of its iron losses and full load copper loss is : -  9 /16

Description : Two transformers A and B having equal outputs and voltage ratios but unequal percentage impedances of 4 and 2 are operating in parallel. The transformer A will be overloaded by 

Last Answer : Two transformers A and B having equal outputs and voltage ratios but unequal percentage impedances of 4 and 2 are operating in parallel. The transformer A will be overloaded by 33%

Description : Two transformers are connected in parallel. These transformers do not have equal percentage impedance. This is likely to result in?

Last Answer : Two transformers are connected in parallel. These transformers do not have equal percentage impedance. This is likely to result in loading of the transformers not in proportion to their kVA ratings.

Description : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that

Last Answer : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that the transformers should belong to the same vector group

Description : 48.During light loads, the transformer efficiency is low because A. Secondary output is low B. Transformer losses are high C. Fixed loss is high in proportion to the output D. Cu loss is small

Last Answer : C. Fixed loss is high in proportion to the output

Description : TRANSFORMERS MCQ

Last Answer : 101. A shell-type transformer has (a) high eddy current losses (b) reduced magnetic leakage (c) negligibly hysteresis losses (d) none of the above Ans: b 102. A transformer can have regulation closer to zero (a ... (6) much smaller (c) much higher (d) somewhat smaller (e) none of the above Ans: c

Description : What are the schedules of maintenance done on transformers?

Last Answer : Ans. Following are the schedules of maintenance on transformers. a. Daily maintenance. b. Monthly maintenance. c. Quarterly maintenance. d. Half yearly maintenance. e. Yearly maintenance. f. 5 Yearly maintenance.

Description : What are the loses in Transformers, Explain?

Last Answer : Ans. (1) Iron loses (2) Copper loses Iron Loss : Iron loss occurs in the transformers Iron core due to hysteresis and eddy currents taking place. They are almost fixed irrespective of ... losses in the primary and the secondary windings of the transformer which with the loading of transformer.

Description : State any two applications of single phase autotransformer.

Last Answer : Applications of single phase auto transformers: 1) Give small boost to distribution cable to correct the voltage drop. 2) As auto transformer starter for induction motors. 3) As furnace supply ... . 5) In control equipment for single phase locomotives. 6) As dimmer in lighting circuits.

Description : Define transformation ratio in terms of current and voltage.

Last Answer : (i) Transformation Ratio (K) is defined as the ratio of the primary current to the secondary current.  (ii) Transformation Ratio (K) is defined as the ratio of the secondary voltage to the primary voltage.

Description : Draw the connection diagram of long shunt differential D.C. compound generator.

Last Answer : Ans:

Description : Classify the transformers based on the construction, frequency and power.

Last Answer : Classification of Transformer Based On: i) Construction: Shell type, Core type, Berry type ii) Change in voltage level: Step-Up, Step-Down, iii) Number of phases: Single phase, Three phase iv) ... Control vi) Cooling: Self-cooled, Air-cooled, Forced-air cooled, Oil-cooled, Forced-oil cooled. 

Description : Which of the following connection of transformers will give highest value of secondary voltage ? (A) Delta primary delta secondary (B) Delta primary star secondary (C) Star primary star secondary (D) Star primary delta secondary

Last Answer : Which of the following connection of transformers will give highest value of secondary voltage ? (A) Delta primary delta secondary (B) Delta primary star secondary (C) Star primary star secondary (D) Star primary delta secondary

Description : Core type transformers are popular in___________.  (A) High voltage applications (B) Low voltage applications (C) All of the above (D) None of the above

Last Answer : Core type transformers are popular in High voltage applications

Description : In a transmission line if booster transformers are to be used, preferred location will be  (A) At the receiving end (B) At the sending end (C) At the intermediate point (D) Anywhere in the line 

Last Answer : In a transmission line if booster transformers are to be used, preferred location will be At the intermediate point

Description : The friction losses in Real Transformers are :  (A) 0% (B) 5% (C) 25% (D) 50%

Last Answer : A

Description : Two 3-phase transformers cannot be operated in parallel, if their :  (A) kVAs are different (B) phase sequences are different (C) % impedances are different (D) voltage ratios are different

Last Answer : Two 3-phase transformers cannot be operated in parallel, if their : phase sequences are different

Description : Which of the following is the advantage of using CRGO steel in transformers? A) High magnetic flux density B) Low permeability C) Both A and B D) None of these

Last Answer : It definitely High Magnetic Flux Density since a crgo steel has always a more around 3% of silicon proportion among the remaining ferrite which make cold rolled grain oriented steel having high flux magnetic ... for more about the crgo core you can learn here https://nicoreindia.com/crgo-core/

Last Answer : Instrument transformers are potential transformers, current transformers.

Last Answer : Natural oil cooling is used for transformers up to a rating of 3000 kVA.

Description : If the percentage impedances of the two transformers working in parallel are different, then?

Last Answer : If the percentage impedances of the two transformers working in parallel are different, then parallel operation will still be possible, but the power factors at which the two transformers operate will be different from the power factor of the common load.

Last Answer : Short circuit test on transformers is conducted to determine copper losses.

Last Answer : Necessary conditions required to be satisfied in order to ensure successful parallel operation of single phase transformers:  1. Only transformers having the same phase displacement between primary and secondary ... . 7. The phase sequence must be followed strictly on HV and LV side connection.

Last Answer : Natural air cooling is generally restricted for transformers up to 1.5 MVA .

Description : Losses which occur in rotating electric machines and do not occur in transformers are?

Last Answer : Friction losses windage losses 

Description : The efficiencies of transformers compared with that of electric motors of the same power are?

Last Answer : Transformers have high efficiency than the same ratted motors

Last Answer : Current transformers (CT) : Current transformer (CT) actually step down the high current to low current for the operation of relays. Current transformer is use for measurement of ... use for relay. This is about potential transformer.

Description : Why do transformers make noise?

Last Answer : Transformers make noise based on it out put if an transformer outputs is 400v maximum than a 398v be apply to that transformer it also make a noise because of that 

Description : [53] The iron loss of the transformer is negligible during short circuit test because A. The entire input is just sufficient to meet Cu losses only B. Flux produced is a small fraction of the normal flux C. Iron core becomes fully saturated D. Supply frequency is held constant

Last Answer : B. Flux produced is a small fraction of the normal flux

Description : A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is  (A) 86.7% (B) 88.26% (C) 88.9% (D) 87.8%

Last Answer : A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is 87.8%

Description : Full load copper loss in a transformer is 1600 watts. At half load the copper loss will be: A) 6400 watt B) 1600 watt C) 800 watt D) 400 watt

Last Answer :  Full load cupper loss in a transformer is 1600 watts. At half load the cupper loss will be: 400 watt

Last Answer : The full-load copper loss of a trans¬former is 1600 W. At half-load, the copper loss will be 400 W.