[23] Transformers are rated in KVA instead of KW because
A. load power factor is often not known
B. KVA is fixed whereas KW depends on load power factor
C. Total transformer loss depends on volt ampere
D. It has become customary

1 Answer

Answer :

C. Total transformer loss depends on volt ampere

Related questions

Description : A 50 KVA transformer has iron loss 2 kW on full load. Calculate its iron loss at 75% of full load.

Last Answer : Iron loss is dependent on voltage and independent of load. Hence iron loss at 75% of Load = Iron loss at full load = 2 kW

Description : 74)Power transformers are generally designed to have maximum efficiency around A. No load B. Half load C. Near full load D. 10% overload

Last Answer : C. Near full load

Description : Why a transformer requires cooling. What are the methods of cooling transformers?

Last Answer : Ans. Transformers requires cooling as they get heated up due to various losses taking place in the transformer. (like iron of copper losses) Following are the methods of cooling of transformer. a. Natural ... . Forced oil air Natural Cooling (OFAN). d. Forced oil and forced Air cooling (OFAF).

Description : 73 The full load copper loss of a transformer is 1600W. At half-load the copper loss will be A. 6400W B. 1600W C. 800W D. 400W

Last Answer : D. 400W

Description : 5 The efficiency of a transformer is maximum when A. It runs at half full load B. it runs at full load C. its Cu loss equal iron loss D. it runs over load

Last Answer : C. Its cu loss equal iron loss

Description : The efficiency of two identical transformers under load conditions can be determined by?

Last Answer : The efficiency of two identical transformers under load conditions can be determined by back-to-back test.

Description : Classify the transformers based on the construction, frequency and power.

Last Answer : Classification of Transformer Based On: i) Construction: Shell type, Core type, Berry type ii) Change in voltage level: Step-Up, Step-Down, iii) Number of phases: Single phase, Three phase iv) ... Control vi) Cooling: Self-cooled, Air-cooled, Forced-air cooled, Oil-cooled, Forced-oil cooled. 

Last Answer : Power transformers are generally designed to have maximum efficiency around near full-load.

Description : The efficiencies of transformers compared with that of electric motors of the same power are?

Last Answer : Transformers have high efficiency than the same ratted motors

Description : One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

Last Answer : 100

Description : TRANSFORMERS MCQ

Last Answer : 101. A shell-type transformer has (a) high eddy current losses (b) reduced magnetic leakage (c) negligibly hysteresis losses (d) none of the above Ans: b 102. A transformer can have regulation closer to zero (a ... (6) much smaller (c) much higher (d) somewhat smaller (e) none of the above Ans: c

Description : What are the schedules of maintenance done on transformers?

Last Answer : Ans. Following are the schedules of maintenance on transformers. a. Daily maintenance. b. Monthly maintenance. c. Quarterly maintenance. d. Half yearly maintenance. e. Yearly maintenance. f. 5 Yearly maintenance.

Description : What are the loses in Transformers, Explain?

Last Answer : Ans. (1) Iron loses (2) Copper loses Iron Loss : Iron loss occurs in the transformers Iron core due to hysteresis and eddy currents taking place. They are almost fixed irrespective of ... losses in the primary and the secondary windings of the transformer which with the loading of transformer.

Description : Which of the following connection of transformers will give highest value of secondary voltage ? (A) Delta primary delta secondary (B) Delta primary star secondary (C) Star primary star secondary (D) Star primary delta secondary

Last Answer : Which of the following connection of transformers will give highest value of secondary voltage ? (A) Delta primary delta secondary (B) Delta primary star secondary (C) Star primary star secondary (D) Star primary delta secondary

Description : Two transformers A and B having equal outputs and voltage ratios but unequal percentage impedances of 4 and 2 are operating in parallel. The transformer A will be overloaded by 

Last Answer : Two transformers A and B having equal outputs and voltage ratios but unequal percentage impedances of 4 and 2 are operating in parallel. The transformer A will be overloaded by 33%

Description : Core type transformers are popular in___________.  (A) High voltage applications (B) Low voltage applications (C) All of the above (D) None of the above

Last Answer : Core type transformers are popular in High voltage applications

Description : In a transmission line if booster transformers are to be used, preferred location will be  (A) At the receiving end (B) At the sending end (C) At the intermediate point (D) Anywhere in the line 

Last Answer : In a transmission line if booster transformers are to be used, preferred location will be At the intermediate point

Description : The friction losses in Real Transformers are :  (A) 0% (B) 5% (C) 25% (D) 50%

Last Answer : A

Description : Two 3-phase transformers cannot be operated in parallel, if their :  (A) kVAs are different (B) phase sequences are different (C) % impedances are different (D) voltage ratios are different

Last Answer : Two 3-phase transformers cannot be operated in parallel, if their : phase sequences are different

Description : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that

Last Answer : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that the transformers should belong to the same vector group

Description : Which of the following is the advantage of using CRGO steel in transformers? A) High magnetic flux density B) Low permeability C) Both A and B D) None of these

Last Answer : It definitely High Magnetic Flux Density since a crgo steel has always a more around 3% of silicon proportion among the remaining ferrite which make cold rolled grain oriented steel having high flux magnetic ... for more about the crgo core you can learn here https://nicoreindia.com/crgo-core/

Last Answer : Instrument transformers are potential transformers, current transformers.

Last Answer : Natural oil cooling is used for transformers up to a rating of 3000 kVA.

Description : If the percentage impedances of the two transformers working in parallel are different, then?

Last Answer : If the percentage impedances of the two transformers working in parallel are different, then parallel operation will still be possible, but the power factors at which the two transformers operate will be different from the power factor of the common load.

Last Answer : Distribution transformers are generally designed for maximum efficiency around 50% load.

Description : Two transformers are connected in parallel. These transformers do not have equal percentage impedance. This is likely to result in?

Last Answer : Two transformers are connected in parallel. These transformers do not have equal percentage impedance. This is likely to result in loading of the transformers not in proportion to their kVA ratings.

Last Answer : Short circuit test on transformers is conducted to determine copper losses.

Last Answer : Necessary conditions required to be satisfied in order to ensure successful parallel operation of single phase transformers:  1. Only transformers having the same phase displacement between primary and secondary ... . 7. The phase sequence must be followed strictly on HV and LV side connection.

Last Answer : Natural air cooling is generally restricted for transformers up to 1.5 MVA .

Description : Losses which occur in rotating electric machines and do not occur in transformers are?

Last Answer : Friction losses windage losses 

Last Answer : Current transformers (CT) : Current transformer (CT) actually step down the high current to low current for the operation of relays. Current transformer is use for measurement of ... use for relay. This is about potential transformer.

Description : Why do transformers make noise?

Last Answer : Transformers make noise based on it out put if an transformer outputs is 400v maximum than a 398v be apply to that transformer it also make a noise because of that 

Last Answer : A common method of cooling a power transformer is oil cooling.

Description : 78 Which type of winding is used in 3 phase shell type transformer? A. Circular type B. Sandwich type C. Cylindrical type D. Rectangular type

Last Answer : B. Sandwich type

Description : State any two conditions for parallel operation of 3-phase transformer.

Last Answer : Conditions for Parallel operation of 3 phase transformer 1) Voltage ratings of both the transformers must be identical. 2) Percentage or p.u. impedance should be equal in magnitude. 3) X/R ratio ... between primary & secondary voltages must be same. 6) Phase sequence on both sides must be same.

Description : Compare core type transformer and shell type transformer on the following parameters. (i) Types of winding used, (ii) Application

Last Answer : Ans:

Description : Define: (i) Commercial efficiency of a transformer and  (ii) All day efficiency of a transformer.

Last Answer : (i) Commercial Efficiency : It is the ratio of output power in watt to the input power in watt. (ii) All day efficiency of a transformer: It is the ratio of output energy in kWh to the input energy in kWh in the 24 hours of the day

Description : State any four properties of Ideal transformer.

Last Answer : Properties of Ideal transformer: 1) No losses (iron and copper losses), hence no temperature rise. 2) No magnetic leakage i.e (Coefficient of coupling between primary and secondary windings is unity) 3) Zero winding ... drop i.e. E1 = V1, E2 = V2 5) Efficiency 100 %. 6) Regulation 0 %.

Description : Why circuit breaker connect b)w two transformer  (same rating

Last Answer : Because two transformers connection is in parallel to share the load if any transformer is receives the surge current because of the fault so to protect the other transformer from the fault. 

Last Answer : Harmonics in transformer result in increased core losses, increased I2R losses, and magnetic interference with communication circuits.

Description : Why are Alternators rated in kVA and not in kW?

Last Answer : The continuous power rating of any machine is generally defined as the power the machine or apparatus can deliver for a continuous period so that the losses incurred in the machine gives rise to a ... generator , the Alternators have only their apparent power in VA/kVA/MVA as their power rating.

Description : Why are generators rated in kVA not in kW ?

Last Answer : Because It's rating of generator kva is apparent power. Kw is active power which we use. And one is kvar reactive power.

Description : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

Last Answer : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is 80 MJ

Description : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is: A) 300 kVA B) 75 kVA C) 259 kVA D) 249 kVA

Last Answer : Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is:  259 kVA

Description : Power transformers are rated in _____________. A. kilowatts B. ampere-turns C. kilowatt-volts D. kilovolt-amperes

Last Answer : Answer: D

Description : why transformers are rated in kVA ?

Last Answer : A:Copper loss of a transformer depends on current and iron loss on voltage . Hence total losses depends on Volt- Ampere and not on the power factor. That is why the rating of transformers are in kVA and not in kW.

Description : A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

Last Answer : 543A

Description : Which of the following statements are true? i) reactive current is necessary to build up the flux for the magnetic field of inductive devices ii) some portion of reactive current is converted into work iii) the cosine of angle ... called power factor a) i & iv b) ii & iii c) i & iii d) iii & iv

Last Answer : a) i & iv

Description : Why are motor ratings given in KW and that of alternator and transformer given in KVA?

Last Answer : kW is the output mechanical power of a motor and is expressed in kW. kVA is the net (apparent) power input to the transformer. This input power is the output + losses. kW = kVA x system power factor