[75] Two transformers are connected in parallel. These transformers do not have equal percentage
impedance which results
A. Short-circuiting of the secondaries
B. Power factor of one of the transformers is leading while that of the other lagging
C. Transformers having higher copper losses will have negligible core losses
D. Loading of the transformers not in proportion to their kVA ratings.

1 Answer

Answer :

D. Loading of the transformers not in proportion to their kVA ratings

Related questions

Description : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is 500 kVA and its pu ... its pu leakage impedance is  (A) 0.20 (B) 0.10 (C) 0.05 (D) 0.025

Last Answer : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is ... .05 pu. If the rating of second transformer is 250 kVA, its pu leakage impedance is 0.10

Description : [53] The iron loss of the transformer is negligible during short circuit test because A. The entire input is just sufficient to meet Cu losses only B. Flux produced is a small fraction of the normal flux C. Iron core becomes fully saturated D. Supply frequency is held constant

Last Answer : B. Flux produced is a small fraction of the normal flux

Description : 51 A transformer has negative voltage regulation when its load power factor is A. Zero B. Unity C. Leading D. Lagging

Last Answer : C. leading

Description : 7 The main advantage of auto transformer over a two winding transformer is A. Hysteresis losses are reduced B. Saving in winding material C. Copper losses are negligible D. Eddy losses are totally eliminated

Last Answer : A) hysteresis losses is reduced

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : During short circuit test iron losses are negligible because?

Last Answer : During short circuit test iron losses are negligible because the voltage applied on primary side is low.

Description : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is

Last Answer : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is 0.707

Description : The transformer ratings are usually expressed in terms of A. Volts B. Amperes C. kW D. kVA

Last Answer : D) KVA

Description : The heat dissipating capability of transformers of ratings higher than 30 kVA in increased by providing which of the following ? (a) Corrugations (b) Fins (c) Tubes (d) Radiator tanks (e) All of the above

Last Answer : (e) All of the above

Description : Can Transformers be Reconnected as Autotransformers to Increase Their KVA Rating?

Last Answer : ANSWER: Several of standard single phase transformers can be connected as autotransformers. The KVA capacity will be greatly increased when used as an Autotransformer, in comparison to the ... This voltage is normally used for operating fluorescent lamps or similar devices requiring 277 volts

Description : 64)During the short-circuit test on a small transformer the frequency is increased from 50-200Hz. The copper losses will increase by a factor of A. 16 B. 4 C. 1 D. 1/4

Last Answer : A) 16

Description : why transformers are rated in kVA ?

Last Answer : A:Copper loss of a transformer depends on current and iron loss on voltage . Hence total losses depends on Volt- Ampere and not on the power factor. That is why the rating of transformers are in kVA and not in kW.

Description : 47 Cross over windings are used in A. Low voltage side of high kVA rating transformers B. Current transformers C. High voltage side of high kVA rating transformers D. High voltage side of low kVA rating transformers

Last Answer : D. High voltage side of low kVA rating transformers

Description : 4 Helical coils can be used on A. Low voltage side of high kVA transformers B. High frequency transformers C. High voltage side of small capacity transformers D. High voltage side of high kVA rating transformers

Last Answer : A) low voltage side of high KVA transformer

Description : 4] In operating a 400hz transformer at 50Hz A. Only voltage is reduced in the same proportion as the frequency B. Only KVA rating is reduced in the same proportion as the frequency C. Both voltage and KVA rating are reduced in the same proportion as frequency D. None of the above

Last Answer : B. Only KVA rating is reduced in the same proportion as the frequency

Description : 45 The function of conservator in a transformer is A. To protect against internal fault B. To reduce copper as well as core losses C. To cool the transformer oil D. To take care of the expansion and contraction of transformer oil due to variation of temperature of surroundings

Last Answer : D. To take care of the expansion and contraction of transformer oil due to variation of temperature of surroundings

Description : 8 The transformer core is laminated to A. Reduce the copper losses B. Reduce the core losses C. Reduce the eddy current losses D. None of the above

Last Answer : C. Reduce the eddy current losses

Description : For a transmission line with negligible losses, the lagging reactive power (VAR) delivered at The receiving end, for a given receiving end voltage, is directly proportional to the?

Last Answer : For a transmission line with negligible losses, the lagging reactive power (VAR) delivered at The receiving end, for a given receiving end voltage, is directly proportional to the line voltage drop.

Description : What will happen if transformer in parallel connection have different percentage impedance or X/R ratio ?

Last Answer : A difference in the ratio of the reactance value to resistance value of the per unit impedance results in a different phase angle of the currents carried by the two paralleled transformers; one ... of the combined output. Hence, the real power will not be proportionally shared by the transformers.

Description : 76 The changes in volume of transformer cooling oil due to variation of atmospeheric temperature during day and night is taken care of by which part of transformer? A. Conservator B. Breather C. Bushings D. Buchholz relay

Last Answer : A. Conservator

Description : The input of an A.C. circuit having power factor of 0.8 lagging is 40 kVA The power drawn by the circuit is?

Last Answer : The input of an A.C. circuit having power factor of 0.8 lagging is 40 kVA The power drawn by the circuit is 32 kW.

Description : What is Meant by "Impedance" in Transformers?

Last Answer : ANSWER: Impedance is the current limiting characteristic of a transformer and is expressed in percentage.

Description : What is meant by “impedance” in transformers? Why is it important?

Last Answer : A. Impedance is the current limiting characteristic of a transformer and is expressed in percentage. It is used for determining the interrupting capacity of a circuit breaker or fuse employed to protect the primary of a transformer

Description : 1 Sumpner's test is conducted on transformers to find A. Temperature B. Stray losses C. All-day efficiency D. None of the above

Last Answer : A. Temperature

Description : 48.During light loads, the transformer efficiency is low because A. Secondary output is low B. Transformer losses are high C. Fixed loss is high in proportion to the output D. Cu loss is small

Last Answer : C. Fixed loss is high in proportion to the output

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : Two transformers having the same p.u. impedance connected in parallel share the connected load (A) equally (B) in proportion to the respective ratings (C) in proportion to the voltage ratio (D) in proportion to the zero phase displacement

Last Answer : Two transformers having the same p.u. impedance connected in parallel share the connected load in proportion to the respective ratings

Description : When two transformer of different kVA rating are connected in parallel they share the load in proportion to their respective kVA rating only when their:

Last Answer : When two transformer of different kVA rating are connected in parallel they share the load in proportion to their respective kVA rating only when their: P u impedance are equal

Description : If the excitation is increased to one of two alternators operating in parallel, the _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. kilowatt load will be greatly increased D. ampere load will be greatly decreased

Last Answer : Answer: A

Description : If the excitation of an alternator operating in parallel is decreased below normal, its _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. ampere load will be greatly increased D. kilowatt load will be greatly decreased

Last Answer : Answer: B

Description : In transformers, why the low voltage winding is placed near the core?

Last Answer : The winding & Core are both made of metals and so an insulation have to be placed in between them, the thickness of insulation depends on the voltage rating of the winding. In order to reduce the insulation requirement the low voltage winding place near the core.

Description : What are the advantages of shell type transformer over core type transformers?

Last Answer : In shell type transformers the coils are well supported on the all sides and so they can withstand higher mechanical stresses developed during short circuit conditions. Also the leakage reactance will be less in shell type transformers.

Description : Two transformers with identical voltage ratings are working in parallel to supply common load. The percentage impedance of one transformer is higher compared to that of other. The load sharing ... respective impedance (4) Depend on the resistance to leakage reactance ratio of each transformer

Last Answer : Two transformers with identical voltage ratings are working in parallel to supply common load. The percentage impedance of one transformer is higher compared to that of other. The load sharing between the two transformer will: Be inversely proportional of their respective impedance

Description : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is  (A) 50.0% (B) 70.7% (C) 141.4% (D) 200.0%

Last Answer : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is 70.7%

Description : Why the range of efficiency in transformers higher than those of other electrical machines?

Last Answer : Transformers operate at higher efficiency when compared to other electrical machines.This is due to the absence of mechanical losses which is due to the absence of moving parts

Description : 72 Harmonics in transformer result in A. Increased core losses B. Increased I2R losses C. Magnetic interference with communication circuits D. All of the above

Last Answer : D. All of the above

Description : 43 The purpose of providing an iron core in a transformer is to A.Provide support to windings B. Reduce hysteresis loss C. decrease the reluctance of the magnetic path D. reduce eddy current losses

Last Answer : C. Decrease the reluctance of the magnetic path

Description : 13) In an ideal transformer A. windings have no resistance B. core has no losses C. core has infinite permeability D. all of the above

Last Answer : D. All of the above

Description : Reduction in core losses and increase in permeability are obtained with transformer employing?

Last Answer : Reduction in core losses and increase in permeability are obtained with transformer employing core built-up of laminations of cold rolled grain oriented steel.

Description : 21.The ordinary two winding transformer's primary and secondary windings always have A. different no of turns B. same size of copper wire C. a common magnetic circuit D. separate magnetic circuits

Last Answer : C. A common magnetic circuit

Description : What are the conditions for parallel operation of two transformers ?

Last Answer : Transformers which are to be operated parallel should have to satisfy the following conditions: Polarities of both the transformers should be same else lead to short circuit Voltage rating of ... Phase displacement of transformers should be same Phase sequence of two transformers should be same

Description : What are the conditions for parallel operation of two transformers ?

Last Answer : Transformers which are to be operated parallel should have to satisfy the following conditions: Polarities of both the transformers should be same else lead to short circuit Voltage rating of ... Phase displacement of transformers should be same Phase sequence of two transformers should be same

Description : What are the Conditions for parallel operation of transformers?

Last Answer : A. a) Same voltage ratio of transformer: If two transformers of different voltage ratio, are connected in parallel with same primary supply voltage, there will be a difference in secondary voltages. If ... not in same phase sequence, during the cycle, each pair of phases will be short circuited.

Description : What are the advantages of parallel operation of transformers?

Last Answer : A. 1) To maximize electrical power system efficiency: Generally electrical power transformer gives the maximum efficiency at full load. If we run numbers of transformers in parallel, we can switch ... running in parallel can be removed from system to balance the capital investment and its return.

Description : Can transformers be used in parallel?

Last Answer : Single phase transformers can be used in parallel only when their impedances and voltages are equal. If unequal voltages are used, a circulating current exists in the closed network between ... listed above, plus the angular displacement and phasing between the two transformers must be identical.

Description : Can 60 Hz Transformers be Used at Higher Frequencies?

Last Answer : A: Transformers can be used at fre¬quencies above 50 Hz up through 400 Hz with no limitations provided nameplate voltages are not exceeded. However, 50 Hz transformers will have less voltage ... Where better regulation and smaller physical size are required, contact us for special 400 Hz designs.

Description : Can the transformers be used at higher frequencies than rated frequency?

Last Answer : A. Yes. Transformers can be used at higher frequencies than rated frequency. However as the frequency increases voltage regulation decreases.

Description : In testing a three-phase delta winding for an open circuit using a megohmmeter, you must ______________. A. test each phase with all connections intact B. measure the voltage across the open ... groups to avoid short circuiting D. open the delta-connections to avoid shunting the phase being tested

Last Answer : Answer: D

Description : 70] Silicon steel used in laminations mainly reduces A. Hysteresis loss B. Eddy current losses C. Copper loss D. All of the above

Last Answer : A. Hysteresis loss