Explain the tests on a single phase transformer and develop an equivalent from the above tests.
0 like 0 dislike

Please log in or register to answer this question.

1 Answer

1.Open Circuit Test on Transformer:  The connection diagram for open circuit test on transformer is shown in the figure. A voltmeter, wattmeter, and an ammeter are connected in LV side of the transformer as shown. The voltage at rated frequency is applied to that LV side with the help of a variac of variable ratio auto transformer.  The HV side of the transformer is kept open. Now with the help of variac, applied voltage gets slowly increased until the voltmeter gives reading equal to the rated voltage of the LV side. After reaching at rated LV side voltage, all three instruments reading (Voltmeter, Ammeter and Wattmeter readings) are recorded.  The ammeter reading gives the no load current Ie. As no load current Ie is quite small compared to rated current of the transformer, the voltage drops due to this current that can be taken as negligible. Since, voltmeter reading V1 can be considered equal to secondary induced voltage of the transformer, the input power during test is indicated by watt-meter reading.  As the transformer is open circuited, there is no output, hence the input power here consists of core losses in transformer and copper loss in transformer during no load condition. But as said earlier, the no load current in the transformer is quite small compared to full load current, so copper loss due to the small no load current can be neglected. Hence, the wattmeter reading can be taken as equal to core losses in transformer. Let us consider wattmeter reading is Po.

image

image

Therefore, if shunt branch reactance of transformer is Xm,

image 

2. Short Circuit Test on Transformer:  The connection diagram for short circuit test on transformer is shown in the figure. A voltmeter, wattmeter, and an ammeter are connected in HV side of the transformer as shown. The voltage at rated frequency is applied to that HV side with the help of a variac of variable ratio auto transformer.  The LV side of the transformer is short circuited. Now with the help of variac applied voltage is slowly increased until the ammeter gives reading equal to the rated current of the HV side.  After reaching at rated current of HV side, all three instruments reading (Voltmeter, Ammeter and Watt-meter readings) are recorded. The ammeter reading gives the primary equivalent of full load current IL. As the voltage applied for full load current in short circuit test on transformer is quite small compared to the rated primary voltage of the transformer, the core losses in transformer can be taken as negligible here. 

image


 Let’s say, voltmeter reading is Vsc. The input power during test is indicated by watt-meter reading. As the transformer is short circuited, there is no output; hence the input power here consists of copper losses in transformer.  Since, the applied voltage Vsc is short circuit voltage in the transformer and hence it is quite small compared to rated voltage, so core loss due to the small applied voltage can be neglected. Hence the wattmeter reading can be taken as equal to copper losses in transformer. Let us consider wattmeter reading is Psc.

image

 These values are referred to the HV side of transformer as because the test is conducted on HV side of transformer. These values could easily be referred to LV side by dividing these values with square of transformation ratio.  Therefore it is seen that the short circuit test on transformer is used to determine copper loss in transformer at full load and parameters of approximate equivalent circuit of transformer

0 like 0 dislike
Next Question ⇨⇦ Previous Question

Related questions

Describe the construction details of single phase transformer.
Last Answer : TRANSFORMER - INTRODUCTION   A TRANSFORMER is a device that transfers electrical energy from one circuit to another by electromagnetic induction (transformer action). The electrical energy is ... secondary winding. The primary is wound in layers directly on a rectangular cardboard form. ...

Show More
0 like 0 dislike
1 answer

Random Images

Comment on the working principle of operation of a single-phase transformer. 
Last Answer : Working principle of operation of a single-phase transformer can be explained as An AC supply passes through the primary winding, a current will start flowing in the primary winding. As ... is known as mutually induced voltage. Hence, transformer works on the principle of electromagnetic induction....

Show More
0 like 0 dislike
1 answer

Random Images

Explain the working principle of various types of single phase induction motor with neat circuit diagram.
Last Answer : The single phase induction motors are made self- starting by providing an additional flux by some additional means. Now depending upon these additional means the single phase induction motors are classified as ... maximum value. 3. When the flux decreases from maximum positive value to zero. ...

Show More
0 like 0 dislike
1 answer

Random Images

Explain the construction, working principle of single phase Induction motor.
Last Answer : Single phase motors are very widely used in home, offices, workshops etc. as power delivered to most of the houses and offices is single phase. In addition to this, single phase motors are ... rated speed. This behavior of a single phase motor can be explained by double-field revolving theory. ...

Show More
0 like 0 dislike
1 answer

Random Images

With a neat circuit diagram Explain the construction and principle of operation of DC Generator
Last Answer : DC Generator: A dc generator is an electrical machine which converts mechanical energy into direct current electricity. This energy conversion is based on the principle of production of dynamically ... current reversal occurs. And therefore, we get unidirectional current at the terminals. ...

Show More
0 like 0 dislike
1 answer

Random Images
...