If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

1 Answer

Answer :

A. As we know the Voltage & current relation for transformer-V1/V2 = I2/I1
We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps.
By putting these value on Relation540/11000= I2/2334
So,I2 = 114.5 Amps

Related questions

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer :  As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : 66 While conducting short-circuit test on a transformer the following side is short circuited A. High voltage side B. low voltage side C. primary side D. secondary side

Last Answer : B. Low voltage side

Description : In a Tap changing transformer on which side is the tap connected, primary side or secondary side?

Last Answer : A. Tapings are always connected to high voltage winding side, because of low current. If we connect tapings to low voltage side, sparks will produce while tap changing operation due to high current.

Description : 29.In transformer terminology, the ratio 20:1 indicates that A. there are 20 turns on primary one turn on secondary B. secondary voltage is 1/20th of the primary C. primary current is 20 times greater than the secondary current D. for every 0 turns on primary, there is one turn on secondary

Last Answer : A. there are 20 turns on primary one turn on secondary

Description : What current flows in the transformer primary when its secondary is open?

Last Answer : A. When the secondary is open, there is no current in the secondary of the transformer. The primary takes a small current I0) from the source called no-load current which has a magnetizing ... ) producing the magnetic flux and a working component (I0 cosθ0) supplying real power for iron losses.

Description : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 ... load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

Last Answer : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/ ... MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be 36 

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : 52 A transformer has 1000 primary turns, connected to 250V ac supply. To get 400V secondary voltage the no of secondary turns should be A. 1600 B. 250 C. 400 D. 1250

Last Answer : A. 1600

Description : The frequency of the secondary voltage of a transformer will be..... A. less than frequency of the primary voltage B. equal to the primary voltage C. greater than the frequency of the primary voltage D. much greater than the frequency of the primary voltage

Last Answer : B. Equal to the primary voltage

Description : 25 A step up transformer increases A. voltage B. current C. power D. frequency

Last Answer : A. Voltage

Description : 16.step-up transformer increases A. voltage B. current C. power D. frequency

Last Answer : A. Voltage

Description : A load with an impedance of 440 ohms is connected across the secondary of the transformer illustrated. If the input voltage is 110 VAC and the step-up ratio is 10 to 1, what will be the primary current? EL-0055 A. 2.5 amps B. 25 amps C. 250 amps D. current cannot be determined with information given

Last Answer : Answer: B

Description : A load is connected to the secondary of the transformer illustrated and the current through the load is 10 amps. If the step-up ratio is 10 to 1 and the input voltage is 110 VAC, what will be the current flow through the primary? EL-0055 A. 1 amp B. 10 amps C. 100 amps D. 1000 amps

Last Answer : Answer: C

Description : Step-down transformer converts high voltage and low current into:  (A) How voltage and high current (B) High voltage and low current (C) Low voltage and high current (D) None of the above

Last Answer : Step-down transformer converts high voltage and low current into: Low voltage and high current

Description : Why to calculate equivalent impedance referred to primary or secondary side?

Last Answer : Equivalent impedance is essential to be calculated because the electrical power transformer is an electric power system equipment, for estimating different parameters of electric power system ... referred to primary or equivalent circuit of transformer referred to secondary sides respectively.

Description : Does the transformer draw any current when its secondary is open?

Last Answer : Yes, no-load primary current.

Description : Does the transformer draw any current when secondary is open ? Why ?

Last Answer : Yes,it (primary) will draw the current from the main supply in order to magnetize the core and to supply iron and copper losses on no load . There will not be any current in the secondary since secondary is open

Description : Which of the following statements is true concerning stepdown transformer operation? A. The inductance on the primary side is the same as the inductance on the secondary side. B. The voltage to the primary ... . D. The voltage to the primary side is greater than the voltage from the secondary side.

Last Answer : Answer: D

Description : What are the applications of step-up & step-down transformer?

Last Answer : A:Step-up transformers are used in generating stations. Normally the generated voltage will be either 11kV. This voltage (11kV) is stepped up to 110kV or 220kV or ... and made available at consumer premises. The transformers used at generating stations are called power transformers.

Description : What is transformation ratio for step up, step down and isolation transformer?

Last Answer : K>1 for step up transformer K

Description : 59.An ideal transformer has infinite values of primary and secondary inductances. The statement is A. True B. False

Last Answer : B. False

Description : 57 In a transformer the resistance between its primary and secondary is A. Zero B. 1Ω C. 1000 Ω D. Infinite

Last Answer : D. Infinite

Description : 50 The equivalent resistance of the primary of the transformer having K = 5, R1 = 0.1 ohm when referred to secondary becomes .....ohm A. 0.5 B. 0.02 C. 0.004 D. 2.5

Last Answer : A. 0.5

Description : 38] In a transformer the energy is conveyed from primary to secondary? A. Through cooling coil B. Through air C. By the flux D. None of the above

Last Answer : C. By the flux

Description : 28.In a two winding transformer, the emf /turn in secondary winding is always......the induced emf power turn in primary A. equal to k times B. equal to 1/k times C. equal D. greater than

Last Answer : C. equal

Description : 6 In a two winding transformer, the primary and secondary induced emf E1 & E2 are always A. equal in magnitude B. anti phase with each other C. in phase with each other D. determined by load on transformer secondary

Last Answer : C. In phase with each other

Description : 12] Which is not the basic element of the transformer? A. core B. primary winding C. secondary winding D. mutual flux

Last Answer : D. Mutual flux

Description : A certain transformer has 200 turns in the primary winding, 50 turns in the secondary winding and 120 volts applied to the primary. What is the voltage across the secondary?  (A) 30 Volts (B) 480 Volts (C) 120 Volts (D) 60 Volts

Last Answer : A certain transformer has 200 turns in the primary winding, 50 turns in the secondary winding and 120 volts applied to the primary. What is the voltage across the secondary?  (A) 30 Volts (B) 480 Volts (C) 120 Volts (D) 60 Volts

Last Answer : An ideal transformer has infinite values of primary and secondary inductances. The statement is false.

Description : In a transformer the resistance between its primary and secondary should be?

Last Answer : In a transformer the resistance between its primary and secondary should be infinity.

Description : 63 The dielectric strength of transformer oil is expected to be A. 1kV B. 33kV C. 100kV D. 330 kV

Last Answer : B. 33kv

Description : When a transformer is used to step down voltage, the low voltage winding is _____________. A. part of the core B. the primary coil C. not insulated D. the secondary coil

Last Answer : Answer: D

Description : In the illustration, if the device in figure 'A' has a step-up ratio of 10 to 1, what voltage should be measured at the secondary shortly after the primary of the device is connected to 110 volts DC? EL-0059 A. 0 volts B. 110 volts C. 11 volts D. 1100 volts

Last Answer : Answer: A

Description : The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: A) 400 Mega Joule B) 400 Kilo Joule C) 25 Mega Joule D) 25 Kilo Joule

Last Answer : The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: 400 Mega Joule

Description : A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

Last Answer : 800

Description : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

Last Answer : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is 0.01

Description : A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

Last Answer : A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of 0.02 P.U

Description : A 1:5 step-up transformer has 120V across the primary and 600 ohms resistance across the secondary. Assuming 100% efficiency, the primary current equals (A) 0.2 Amp. (B) 5 Amps. (C) 10 Amps. (D) 20 Amps.

Last Answer : I1= V1 /R1 = 120/600 = 0.2 (η = 100%, losses are zero ∴V1 = VR = I1R1)

Description : What will happen if DC supply is given on the primary of a transformer?

Last Answer : A. Mainly transformer has high inductance and low resistance. In case of DC supply there is no inductance, only resistance will act in the electrical circuit. So, high electrical current will flow through primary side of the transformer. Due to this the coil and insulation will burn out.

Description : Why the earthing transformer primary voltage is 16.5 kV rated in main generator even though actual voltage during the E/F is root 3 times less?

Last Answer : The transformer should not saturate during E/F otherwise it will cause ferroresonance with the GT winding capacitance. Dangerous O/V and neutral shifting will occur. During loss of load or field ... saturation. Saturation can also occur due to point on wave of application causing flux doubling. 

Description : In a step-down transformer, there is a change of 15 A in the load current. This results in change of supply current of?

Last Answer : In a step-down transformer, there is a change of 15 A in the load current. This results in change of supply current of less than 15A.

Description : What is voltage ratio of a transformer?

Last Answer : A. Voltage ratio is the ratio of the voltage between the line terminals of one winding to that between the line terminals of another winding at no load.

Description : What will happen if transformer in parallel connection have different voltage ratio?

Last Answer : Two transformers in Parallel should have the same primary and secondary voltage ratings. Any error in the voltage ratio would cause heavy circulating currents to flow between the transformers. ... in overloading of one transformer. This circulating current will result in increased copper losses.

Description : Why the open circuit test on a transformer is conducted at rated voltage?

Last Answer : A:The open circuit on a transformer is conducted at a rated voltage because core loss depends upon the voltage. This open circuit test gives only core loss or iron loss of the transformer.

Description : What are the necessary tests to determine the efficiency, voltage regulation, and temperature rise of winding & insulation of transformer?

Last Answer : 1.Direct loading test 2.Open circuit test 3. Short circuit test 4. Sumpner's or back to back test

Description : When secondary of a current transformer is open-circuited its iron core will be?

Last Answer : When secondary of a current transformer is open-circuited its iron core will be hot because of heavy iron losses taking place in it due to high flux density.

Description : The secondary of a current transformer is always short-circuited under operating conditions because it?

Last Answer : The secondary of a current transformer is always short-circuited under operating conditions because it avoids core saturation and high voltage induction.

Description : 30 In performing the short circuit test of a transformer A. high voltage is usually short circuited B. low voltage side is usually short circuited C. any side is short circuited with preference D. none of the above

Last Answer : B. Low voltage side is usually short circuited