Why we do 2 types of earthing on transformer i.e.: body earthing & neutral earthing, what is function. I am going to install a 5oo kva transformer & 380 kva DG set what should the earthing value?

1 Answer

Answer :

The two types of earthing are Familiar as Equipment earthing and system earthing. In Equipment earthing: body (non conducting part) of the equipment should be earthed to safeguard the human beings. System Earthing: In this neutral of the supply source (Transformer or Generator) should be grounded. With this, in case of unbalanced loading neutral will not be shifted. So that unbalanced voltages will not arise. We can protect the equipment also. With size of the equipment (transformer or alternator) and selection of relying system earthing will be further classified into directly earthed, Impedance earthing, resistive (NGRs) earthing.

Related questions

Description : Why neutral breaker used in DG neutral grounding?

Last Answer : In case of high earth fault currents it is therefore normal practice to install a circuit breaker in the neutral of the generator in order to reduce the total fault clearance time. 

Description : What is the neutral point earthing and its advantages?

Last Answer : In substation all the neutrals of rotating machines, transformers, busbars and other equipment are connected to ground. Some of the advantages are: Earth fault protection is based on the method of ... , grounding of neutral helps to reduce the over-voltages which occur on the one healthy phases

Description : Why the neutral is earthed through earthing resistance in case of UT and SUT? 

Last Answer : This is done to limit the earth fault current.  

Description : Why the earthing transformer primary voltage is 16.5 kV rated in main generator even though actual voltage during the E/F is root 3 times less?

Last Answer : The transformer should not saturate during E/F otherwise it will cause ferroresonance with the GT winding capacitance. Dangerous O/V and neutral shifting will occur. During loss of load or field ... saturation. Saturation can also occur due to point on wave of application causing flux doubling. 

Description : What is the maximum current allowed to be drawn from the secondary of a 2 KVA step-down transformer with a turns ratio of four to one if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 22.7 amps

Last Answer : Answer: C

Description : What is the maximum allowable primary current of a 2 KVA step-down transformer with a four to one turns ratio if connected across a 440 volt line? A. 1.1 amps B. 4.5 amps C. 18.1 amps D. 27.7 amps

Last Answer : Answer: B

Description : A 220/440 V, 50 Hz, 5 KVA, single phase transformer operates on 220V, 40Hz supply with secondary winding open circuited. Then (A) Both eddy current and hysteresis losses decreases. (B) Both ... same but hysteresis loss increases. (D) Eddy current loss increases but hysteresis loss remains the same.

Last Answer : (A) Both eddy current and hysteresis losses decreases.

Description : Why in DG E/F protection, we do not open class IV CB’s or supply CB’s?

Last Answer : Delta of aux. Transformer prevents E/F currents from grid into DG neutral.  

Description : Write down difference between equipment earthing and neutral earthing. 

Last Answer : Sr. No. Equipment earthing Neutral earthing 1 Connection of the non-current carrying metallic parts of the electrical equipment to earth is called as equipment earthing. Connection of the neutral ... 6 It is an equipment earthing. It is a source or system earthing.

Description : State the methods of Neutral Grounding. State difference between Earthing and grounding. 

Last Answer : Neutral Grounding connections are of three types:  1. Solid earthing 2. Resistance earthing 3. Reactance earthing SR. NO. Earthing Grounding 1 Earthing means connecting the dead part ... earthing provides suitable means for earth fault protecting system.  10

Description : Explain types of Earthing.

Last Answer : A:The two types of earthing are Equipment earthing and system earthing. In Equipment earthing: body ( non conducting part) of the equipment should be earthed to safegaurd the human beings ... . This type of earthing is further classified into directly earthed, Impedance earthing, resistive earthing.

Description : State the various types of earthing.

Last Answer : Solid earthing, resistance earthing , reactance earthing , voltage transformer earthing and zig-zag transformer earthing.

Description : How do we select a cable for a machine as per standards? Is there is any standard to select a cable as per voltage, or as per KVA and as per amps ratings?

Last Answer : Cable size depends upon current carrying capacity and voltage to withstand, to select cable size we must have knowledge of load of machine and operating voltage

Description : For which of the following ratings of the transformer differential protection is recommended ? (a) above 30 kVA. (b) equal to and above 5 MVA (c) equal to and above 25 MVA (d) none of the above

Last Answer : (b) equal to and above 5 MVA

Description : Why are motor ratings given in KW and that of alternator and transformer given in KVA?

Last Answer : kW is the output mechanical power of a motor and is expressed in kW. kVA is the net (apparent) power input to the transformer. This input power is the output + losses. kW = kVA x system power factor

Description : 55 When a 400Hz transformer is operated at 50Hz its KVA rating is A. Reduced to 1/8 B. Increased 8 times C. Unaffected D. Increased 64 times

Last Answer : A. Reduced to 1/8

Description : 4] In operating a 400hz transformer at 50Hz A. Only voltage is reduced in the same proportion as the frequency B. Only KVA rating is reduced in the same proportion as the frequency C. Both voltage and KVA rating are reduced in the same proportion as frequency D. None of the above

Last Answer : B. Only KVA rating is reduced in the same proportion as the frequency

Description : [23] Transformers are rated in KVA instead of KW because A. load power factor is often not known B. KVA is fixed whereas KW depends on load power factor C. Total transformer loss depends on volt ampere D. It has become customary

Last Answer : C. Total transformer loss depends on volt ampere

Description : The transformer ratings are usually expressed in terms of A. Volts B. Amperes C. kW D. kVA

Last Answer : D) KVA

Description : A 50 KVA transformer has iron loss 2 kW on full load. Calculate its iron loss at 75% of full load.

Last Answer : Iron loss is dependent on voltage and independent of load. Hence iron loss at 75% of Load = Iron loss at full load = 2 kW

Description : KVA of an Auto-transformer of V1/V2 = 220/150 for a load of 100KVA is: a. 100KVA b. 50KVA c. 33.3KVA d. 20KVA 

Last Answer : KVA of an Auto-transformer of V1/V2 = 220/150 for a load of 100KVA is: a. 100KVA b. 50KVA c. 33.3KVA d. 20KVA 

Description : Why Transformer rating is given in kVA?

Last Answer : Because of core losses and iron losses as core losses are measured in amps and cu losses in voltage ....this is definatly reason for the rating Or kVA is the unit for apparent power. Apparent ... shift between voltage and current). So a transformer has to be rated (and selected) by apparent power.

Description : Define kVA rating of transformer.

Last Answer : kVA rating of transformer is defined as the product of voltage (V) and current (I) on primary side of transformer or secondary side of transformer divided by 1000. On both side the VA rating remains ... Mathematically kVA rating is given by, kVA rating of transformer = V1I1/1000 =V2I2/1000

Description : When two transformer of different kVA rating are connected in parallel they share the load in proportion to their respective kVA rating only when their:

Last Answer : When two transformer of different kVA rating are connected in parallel they share the load in proportion to their respective kVA rating only when their: P u impedance are equal

Description : A 400V/100 V, 10 KVA two-winding transformer is reconnected as an auto-transformer across a suitable voltage source. The maximum rating of such an arrangement could be  A) 50 KVA B) 15 KVA C) 12.5 KVA D) 8.75 KVA

Last Answer : A 400V/100 V, 10 KVA two-winding transformer is reconnected as an auto-transformer across a suitable voltage source. The maximum rating of such an arrangement could be 50 KVA

Description : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is  (A) 50.0% (B) 70.7% (C) 141.4% (D) 200.0%

Last Answer : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is 70.7%

Description : A single-phase, 50 kVA, 250 V/500 V two winding transformer has an efficiency of 95% at full load, unity power factor. If it is re-configured as a 500 V/750 V auto-transformer, its efficiency at its new rated load at unity power factor will be  (A) 95.752% (B) 97.851% (C) 98.276% (D) 99.241%

Last Answer : A

Description : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Last Answer : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Description : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is

Last Answer : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is 0.707

Description : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be :  (A) 34.64 kVA (B) 75 kVA (C) 20 kVA (D) None of the above

Last Answer : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be : 34.64 kVA

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : A 1100 kVA, 11 kV/1.1 kV conventional two-winding transformer is connected as a 12.1 kV/11 kV step-down auto-transformer. The rating of the auto-transformer is (A) 1000 kVA (B) 1100 kVA (C) 11000 kVA (D) 12100 kVA

Last Answer : A 1100 kVA, 11 kV/1.1 kV conventional two-winding transformer is connected as a 12.1 kV/11 kV step-down auto-transformer. The rating of the auto-transformer is 12100 kVA

Description : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: A. 4 kVA B. 0.25 kVA C. 16 kVA D. 8 kVA

Last Answer : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: 16 kVA

Description : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: (A) both the eddy current and the hysteresis losses will decrease ... losses will increase (D) eddy current losses will increase but the hysteresis losses will remain the same

Last Answer : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: both the eddy current and the hysteresis losses will decrease

Description : One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

Last Answer : 100

Description : A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

Last Answer : 543A

Description : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of   (a) 250A (b) 50 A (c) 150 A (d) 350 A 

Last Answer : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of 250A

Description : Transformer generally rated in KVA

Last Answer : The power of transformer is apparent power because it has no power factor and it is the product of voltage and current.

Description : What are the protections provided for DG?

Last Answer : 1. Differential protection (87). 2. Over speed of engine. 3. Reverse power protection (in LOCA condition time delay). 4. Low lubricating oil pressure. 5. Cooling water temperature high. 6. 6 ... 8. Emergency stops push button. In LOCA condition 4 - 8 protections are not permitted to operate. 

Description : What are stages of DG starting? 

Last Answer : 1. At start signal compressed air through solenoid valve passes over piston and rotates the shaft. 2. At speed >60-rpm ignition starts. 3. Closing of excitation starts at >800-rpm. 4. At speed of > 900-rpm rated speed and rated voltage signal starts. 5. Closing of over speed is at >1150-rpm. 

Description : What are the auxiliaries required for DG? 

Last Answer : 1. Starting air system. Components are compressor, air dryer, air receiver, solenoid valve for start control, pneumatic starting air valve, air distributor and injection valve at each cylinder. This system operates at ... one RTD each. 10. LCP is provided one each for each DG. 

Description : Why motoring should be prevented in TG and DG? 

Last Answer : In TG motoring prevented due to the turbine limitation otherwise last stage blade will fails. In DG motoring prevented, because of unburned fuel catches fire in DG. 

Description : What is the % overload allowed for TG and DG?

Last Answer : For TG nil For DG 110% for 2 hours. 

Description : The purpose of a governer in a DG set is • To regulate the speed. • To regulate the voltage • To regulate the power • To regulate the current.

Last Answer : The purpose of a governor in a DG set is To regulate the speed.

Description : 151.1% of 151.1 + 151.1 = ? a) 380 b) 400 c) 350 d) 420 e) 440

Last Answer : Answer: a)

Description : The division of the reactive KVA load between paralleled AC generators is initiated by the ______________. A. prime mover governors B. voltage regulators C. phase balance relay D. proportioner

Last Answer : Answer: B

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : The unit of apparent power in a purely inductive circuit is called the _____________. A. kva B. var C. emf D. watt

Last Answer : Answer: B