When two AC generators are being paralleled, the breaker should be closed with the synchroscope pointer rotating in the ____________. A. 'slow' direction, just before the 12 o'clock position B. 'fast' direction, just after the 12 o'clock position C. 'fast' direction, just before the 12 o'clock position D. 'slow' direction, just after the 12 o'clock position

1 Answer

Answer :

Answer: C

Related questions

Description : You are attempting to parallel two AC generators and the synchroscope pointer is revolving in the slow direction. This indicates that the frequency of the incoming machine is _____________. A. higher than ... same as the bus frequency, and the circuit breaker may be closed at any pointer position

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving fast in the clockwise direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... at any pointer position D. the same as the bus frequency but out of phase with it

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving in the fast direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... the same as the bus frequency and the circuit breaker may be closed at any pointer position

Last Answer : Answer: A

Description : As shown in the illustration, which of the listed actions of the synchroscope pointer is occurring? EL-0002 A. Revolving slowly in the slow direction. B. Revolving rapidly in the slow direction. C. ... stationary at the 12 o'clock position since the leading edges of the A phases are in phase.

Last Answer : Answer: C

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0° prior to closing the circuit breaker. This indicates ___________. A. the frequency of ... be closed after breaker has been reset D. there is an existing cross current between generators

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : You are paralleling two alternators. The synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates that the ____________. A. alternator ... be closed C. incoming alternator is running too slowly D. synchroscope is defective or broken

Last Answer : Answer: B

Description : An AC generator panel is fitted with both synchronizing lamps and a synchroscope. When the synchroscope pointer reaches the noon position, one synchronizing light is bright and the other is dark. This ... sequence is incorrect C. the phase sequence is correct D. the generator breaker may be closed

Last Answer : Answer: B

Description : Which of the synchroscope illustrations depicts the appropriate direction of rotation and position for closing the circuit breaker when paralleling AC generators? EL-0053 A. A B. B C. C D. D

Last Answer : Answer: D

Description : If the pointer of the synchroscope is rotating in the slow direction when you are preparing to parallel two alternators, the _____________. A. incoming machine is turning faster than the load alternator B ... alternator is ready to split D. incoming machine is beginning to pick up some of the load

Last Answer : Answer: B

Description : When paralleling two alternators the synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates the ____________. A. alternator voltages ... alternator is in phase with the bus voltage D. synchroscope pointer is defective or broken

Last Answer : Answer: C

Description : A shore power circuit breaker should be closed only _____________. A. when the ship's generators have been directly paralleled to those on shore B. in a shipyard C. if a quick disconnect coupling is used D. when the ship's generators have been removed from the bus

Last Answer : Answer: D

Description : When paralleling two AC generators, the frequency of the incoming machine immediately prior to closing its breaker should be ____________. A. controlled by placing the governor switch in the automatic ... regulator C. slightly greater than the bus frequency D. slightly less than the bus frequency

Last Answer : Answer: C

Description : An alternator is being paralleled with one on the line. At the INSTANT the circuit breaker is closed, the frequency of the incoming alternator will normally _____________. A. increase B. not change C. decrease D. be exactly 60 hertz

Last Answer : Answer: C

Description : When paralleling two AC generators, the frequency of the machine coming online, immediately prior to closing its breaker, should be ____________. A. slightly less than the oncoming generator frequency B. the ... bus frequency C. slightly greater than the bus frequency D. the same as the bus voltage

Last Answer : Answer: C

Description : When the operating handle of a molded-case circuit breaker is in the mid-position, the circuit breaker is indicated as being ____________. A. in the 'closed' position B. in the 'opened' position C. tripped D. reset

Last Answer : Answer: C

Description : The division of the reactive KVA load between paralleled AC generators is initiated by the ______________. A. prime mover governors B. voltage regulators C. phase balance relay D. proportioner

Last Answer : Answer: B

Description : When paralleled, AC generators must have the same _________. A. frequency B. number of phases C. phase rotation D. all of the above

Last Answer : Answer: D

Description : Why is it desirable to operate paralleled AC generators at the same power factor? A. Circulating currents are kept to a minimum. B. Field excitation losses are kept to a minimum. C. Generator ... will have a lesser tendency to hunt. D. Because a power factor increase will decrease kilowatt output.

Last Answer : Answer: A

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : When paralleling two alternators, the synchronizing lamps remain lit as the synchroscope pointer approaches the 0°. This indicates the _____________. A. incoming alternator is running too fast B. alternator ... apart C. synchroscope is defective or broken D. alternator power factors are in phase

Last Answer : Answer: C

Description : An equalizing connection between two compound-wound DC generators when paralleled, serves to _____________. A. reverse the polarity of the incoming generator as the series field weakens B. automatically ... the series field of the incoming generator D. parallel the series fields of the generators

Last Answer : Answer: D

Description : When paralleling two AC generators, the synchroscope selector switch and frequency meter switch should be set up to sense the frequency of the _____________. A. bus B. generator on the line C. oncoming generator D. bus transfer relay

Last Answer : Answer: C

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : When shore power is being connected to a ship in dry dock, _____________. A. the ship's generators are paralleled with the shore power to provide continuous power B. proper phase sequence must be ... 450 volts must be supplied from the shore D. exactly 60 Hz must be provided by the terminal

Last Answer : Answer: B

Description : When paralleling two AC generators, the frequency (cycles) of the incoming generator, just prior to closing the circuit breaker, should be _____________. A. slightly less than the frequency of the generator on ... C. slightly more than the frequency of the generator on the line D. all of the above

Last Answer : Answer: C

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : Prior to closing the breaker when paralleling two AC generators, the recommended practice is to have the frequency of the incoming machine _____________. A. slightly less than the line frequency B. the same as the line frequency C. slightly greater than the line frequency D. all of the above

Last Answer : Answer: C

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : An open occurring within the field rheostat of an AC generator can be detected by short circuiting its terminals and observing a ____________. A. negative deflection of the wattmeter pointer B. ... of the wattmeter pointer C. buildup of alternator voltage D. low, but constant alternator voltage

Last Answer : Answer: C

Description : If three AC generators are operating in parallel, and one of them were to 'pull out' of synchronism with the other two generators, the ____________. A. normally operating AC generators will ... AC generators will overspeed and unload D. AC generator pulling out of synchronism will become motorized

Last Answer : Answer: B

Description : While paralleling two (2) AC generators using synchronizing lamps only, both lamps will go dark when the generators are ____________. A. running at the same speed B. grounded C. of the same polarity D. in phase

Last Answer : Answer: D

Description : Voltage generated by most AC generators is fed from the machine to the bus by means of ____________. A. brushes on a commutator B. brushes on slip rings C. slip rings on a commutator D. direct connections from the stator

Last Answer : Answer: D

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : When an AC or a DC motor fails to start, the FIRST step in troubleshooting should be to check the ____________. A. motor windings for obvious opens B. motor controller leads for continuity C. fuse or circuit breaker D. motor controller leads for grounds

Last Answer : Answer: C

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : Hand-portable phase sequence indicators should be used when ____________. A. installing a new synchroscope B. preparing to make the shore power connection C. replacing a defective solenoid D. all of the above

Last Answer : Answer: B

Description : If a circuit breaker that utilizes built-in, current limiting fuses (CLF's) cannot be closed, the problem may be traced to __________. A. a blown CLF plunger holding the trip bar in the open position B. a missing CLF C. a misaligned limiter housing assembly D. all of the above

Last Answer : Answer: D

Description : When the operating handle of a molded case circuit breaker is in the mid-position, it indicates the circuit breaker is _____________. A. in the 'opened' position B. in the 'closed' position C. tripped D. reset

Last Answer : Answer: C

Description : The RPM of an AC generator can be measured with a/an _____________. A. ammeter B. voltmeter C. vibrating reed meter D. synchroscope

Last Answer : Answer: C

Description : When starting a DC propulsion motor the variable rheostat must FIRST be turned ____________. A. all the way to the run position then quickly back to slow B. to the slow position then gradually moved to full speed C. to the mid position D. quickly to the run position

Last Answer : Answer: B

Description : If fuse 'F-1' in the illustrated schematic diagram opens, ____________. EL-0017 A. the motor will run slowly B. 'A-1' and 'A-2' will open C. the motor will not start D. the start button will jam in the closed position

Last Answer : Answer: C

Description : When 'selector switch' 'SEL8' shown in the illustration is in the 'TEST' position, contacts '3,4' and '7,8' are respectively ____________. EL-0100 A. open; closed B. closed; open C. open; open D. closed; closed

Last Answer : Answer: B

Description : When 'selector switch' 'SEL8' shown in the illustration is in the 'OFF' position, contacts '3,4' and '7,8' are respectively ____________. EL-0100 A. open; closed B. closed; open C. open; open D. closed; closed

Last Answer : Answer: A

Description : What does different position of the synchroscope needle mean; what is the difference between 6 o clock and 12 clock?

Last Answer : 6 o’clock means that out of synchronisation. We cannot parallel the incoming generator. 12 o’clock means the perfect synchronised condition (voltage, frequency and phase sequence match).