Description : If reading the AC voltage from a typical wall outlet, the range switch of the device illustrated should be set to ___________. EL-0047 A. 1,000 V B. 250 V C. R X 10,000 D. 10 ma/amps
Last Answer : Answer: B
Description : If reading AC current with the illustrated device and unsure of the range as a precaution , the first step should be to _________. EL-0047 A. secure power and test for voltage B. disconnect the ... resistance and use Ohm's law to calculate current D. unable to safely measure current with the device
Last Answer : Answer: A
Description : When reading AC current with the multimeter shown in the illustration and you are unsure of the range, the range switch should be set to ___________. EL-0047 A. 10 MA/ 10 AMP with leads in the (-10 A ... leads in the (-COMMON) and (+10 A) jacks D. unable to measure AC current with this multimeter
Last Answer : Answer: D
Description : When attempting to measure AC current with the device shown and you are unsure of the range, the range switch should be set to __________. EL-0047 A. 10 MA / AMPS with leads in the (-10 A) and ... (-COMMON) and (+10 A) jacks D. unable to accurately measure AC current with this device as illustrated
Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown
Description : What is the resistance value indicated on the multimeter scale illustrated, if the range switch is set at R X 100, and the needle is at the position indicated by the letter 'R'? EL-0047 A. 6.0 ohms B. 162.5 ohms C. 600 ohms D. 16,250 ohms
Last Answer : Answer: C
Description : What is the resistance value indicated by the multimeter scale illustrated, if the range switch is set at R X 1, and the needle is at the position indicated by the letter 'A'? EL-0047 A. 10 ohms B. 100 ohms C. 200 ohms D. 1,000 ohms
Description : What is the resistance value indicated by the multimeter scale illustrated, if the range switch is set at R X 100, and the needle is at the position indicated by the letter 'Y'? EL-0047 A. 220 ohms B. 240 ohms C. 2,400 ohms D. 24,000 ohms
Description : A load with an impedance of 440 ohms is connected across the secondary of the transformer illustrated. If the input voltage is 110 VAC and the step-up ratio is 10 to 1, what will be the primary current? EL-0055 A. 2.5 amps B. 25 amps C. 250 amps D. current cannot be determined with information given
Description : A load with an impedance of 440 ohms is connected across the secondary of the device illustrated. If the input voltage is 110 VAC and the step-up ratio is 10 to 1, what will be the primary current? EL-0055 A. 2.5 amps B. 25 amps C. 250 amps D. current cannot be determined with information given
Description : The reading at 'X' while on the R X 100 meter scale illustrated would be ______. EL-0047 A. 8 ohms B. 150 ohms C. 800 ohms D. 80,000 ohms
Description : On the meter scale illustrated, while using the R X 100 scale, the reading at 'Z' is___________. EL-0047 A. 3,000 ohms B. 30,000 ohms C. 300,000 ohms D. 3,000,000 ohms
Description : On the meter scale illustrated, while using the R X 100 scale, the reading at 'A' will be ____________. EL-0047 A. 2,000 ohms B. 20 Kohms C. 200 Kohms D. 3 Megohms
Description : What is the resistance value indicated by the multimeter scale illustrated, if the range switch is set at R X 1, and the needle is at the position indicated by the letter 'F'? EL-0047 A. 0.6 ohms B. 6 ohms C. 9.6 ohms D. .38 ohms
Description : What is the resistance value indicated by the multimeter scale illustrated, if the range switch is set at R X 1, and the needle is at the position indicated by the letter 'D'? EL-0047 A. 7.8 ohms B. 8 ohms C. 3.6 ohms D. .36 ohms
Description : What is the resistance value indicated by the multimeter scale illustrated, if the range switch is set at R X 1, and the needle is at the position indicated by the letter 'R'? EL-0047 A. 6 ohms B. 6.8 ohms C. 1.7 ohms D. 167 ohms
Description : What is the resistance value indicated by the multimeter scale illustrated, if the range switch is set at R X 1, and the needle is at the position indicated by the letter 'X'? EL-0047 A. 8 ohms B. 6.2 ohms C. 1.57 ohms D. 150 ohms
Description : What is the resistance value indicated by the multimeter scale illustrated, if the range switch is set at R X 1, and the needle is at the position indicated by the letter 'C'? EL-0047 A. 1.3 ohms B. 4.8 ohms C. 13 ohms D. 121 ohms
Description : What is the resistance value indicated by the multimeter scale illustrated, if the range switch is set at R X 1, and the needle is at the position indicated by the letter 'B'? EL-0047 A. 1.45 ohms B. 7.2 ohms C. 37 ohms D. 70 ohms
Description : What is the resistance value indicated by the multimeter scale illustrated, if the range switch is set at R X 1 and the needle is at the position indicated by the letter 'Y'? EL-0047 A. 2.2 ohms B. 24 ohms C. 240 ohms D. 2,400 ohms
Description : On the meter scale illustrated, while using the R X 1 scale, the reading at 'E' will be ____________. EL-0047 A. 2.0 ohms B. 20 ohms C. 200 ohms D. none of the above
Description : On the meter scale illustrated, while using the R X 1 scale, the reading at 'F' will be ____________. EL-0047 A. 1.8 ohms B. 6.0 ohms C. 9.4 ohms D. 0.6 ohms
Description : On the meter scale illustrated, while using the R X 1 scale, the reading at 'Z' will be ____________. EL-0047 A. 30 ohms B. 72 ohms C. 720 ohms D. 7.2 Kohms
Description : On the meter scale illustrated, while using the R X 100 scale, the reading at 'F' will be ____________. EL-0047 A. 60 ohms B. 40 ohms C. 30 ohms D. 3 kohms
Description : On the meter scale illustrated, while using the R X 100 scale, the reading at 'B' will be ____________. EL-0047 A. 70 ohms B. 35 ohms C. 700 ohms D. 7 kohms
Description : On the meter scale illustrated, while using the R X 100 scale, the reading at 'C' will be ____________. EL-0047 A. 13 ohms B. 130 ohms C. 1.3 kohms D. 13 kohms
Description : On the meter scale illustrated, while using the R X 100 scale, the reading at 'D' will be ____________. EL-0047 A. 3.6 ohms B. 36 ohms C. 193 ohms D. 360 ohms
Description : When attempting to measure a current of less than 10 amps with the device shown, the range switch should be set to ___________. EL-0047 A. 500 MA B. 10 MA / AMPS with leads in the (-COMMON) and (+) jacks C. 10 MA ... ) and (+10 A) jacks D. 10 MA / AMPS with leads in the (-10 A) and (+10 A) jacks
Description : With the selector switches set for R X 10,000 and the leads placed in the proper receptacles, the needle settles on the '150' mark. What is the resistance value between the leads? EL-0047 A. 1500 ohms B. 150,000 ohms C. 1,500,000 ohms D. 1.5 ohms
Description : In the illustrated motor controller circuit, which statment is true? EL-0023 A. The high and low speed lights operate at less than line voltage with a resistor in series. B. This controller can be ... . The wattage of the high speed light must be greater than the wattage of the low speed light.
Description : A load is connected to the secondary of the transformer illustrated and the current through the load is 10 amps. If the step-up ratio is 10 to 1 and the input voltage is 110 VAC, what will be the current flow through the primary? EL-0055 A. 1 amp B. 10 amps C. 100 amps D. 1000 amps
Description : A load is connected to the secondary of the device illustrated and the current through the load is 10 amps. If the step-up ratio is 10 to 1 and the input voltage is 110 VAC, what will be the current flow through the primary? EL-0055 A. 1 amp B. 10 amps C. 100 amps D. 1000 amps
Description : If the supply voltage is 220 volts 60 Hz, what is the operating voltage of the motor controller circuitry illustrated? EL-0011 A. 110 volts DC B. 110 volts AC C. 220 volts DC D. 220 volts AC
Description : If the line voltage to the controller shown in the illustration is 440 volts, what is applied across the control circuit? EL-0080 A. 110 volts B. 220 volts C. 440 volts D. 660 volts
Description : If the line voltage to the controller shown in the illustration is 440 volts, what voltage is applied across the motor when contacts 'S' close? EL-0080 A. 110 volts B. 220 volts C. 440 volts D. 660 volts
Description : Federal Regulations (46 CFR) require the circuit in the illustration to _________. EL-0009 A. be at the vessel's ship's service generator distribution switchboard for normal power, normal lighting ... ground will interfere with the operation of electronic equipment D. All the above are correct
Description : The illustrated circuit is a wheatstone bridge. If the meter 'G' reads 0 with the switch closed then ________. EL-0024 A. the current through R1 - R2 is equal to the current through R3 - Rx B. the voltage ... of E C. the resistance of Rx is equal to the resistance of R2 D. all the above are true
Description : The 'reset' contacts of the master switch shown in the illustration provides the winch controller with ___________. EL-0102 A. low voltage release B. overload protection C. low voltage protection D. high power factor correction
Description : In the illustrated three phase alternator, line voltage is _________. EL-0074 A. 1.73 times the phase voltage B. equal to the phase voltage C. phase voltage divided by 1.73 D. unable to answer this question without knowing the line current
Description : In the illustrated test, if the lamp fails to light on any of the three windings then _________. EL-0027 A. all three windings are grounded and the motor should be sent out for repair B. ... the motor controller and the controller should be checked D. the test should be redone at a higher voltage
Description : In the illustrated 450 VAC system, what should be provided between the bus and the device labeled 'F'? EL-0003 A. a potential transformer B. a current transformer C. an emergency disconnect device D. an audible alarm and indicating light
Description : In the illustrated circuit, what is the phase relationship of the amplifier output compared to the input? EL-0022 A. 0° in-phase B. 180° out of phase C. phase angle of the input divided by power factor D. unable to determine without the value of the bias voltage
Description : Which of the following statments is true of the illustrated motor controller? EL-0023 A. The low speed is used for starting the motor and when the controller automaticly shifts to High speed. B. The HOL relay ... D. If the overload relay opens for high speed the motor can still be run in low speed.
Description : If the motor fails to start and a voltmeter reading between 1 and 6, as illustrated, indicates line voltage, your next step should be to ________. EL-0007 A. replace fuse '10a' B. replace or repair contact 'Ma' C. reset and determine the cause of the overload D. check line voltage between L1 and L3
Description : Which of the following statements is true about the illustrated circuit? EL-0030 A. The field rheostat is used for manual voltage control. B. if the generator is flat compounded then the field rheostat ... to act like a series motor and overspeed with the controller in the full raise position.
Description : The illustrated motor controller _________. EL-0023 A. is a low voltage release controller because the motor will stop when voltage falls below a certain value and automaticly start when normal voltage ... with a generator or transformer bank that is 'wye' wound with T2 connected to the neutral
Description : In the illustrated ground detection system with a ground on phase A, if the switch is opened __________. EL-0009 A. lamp A will dim or go out depending on the severity of the ground B. all three ... lamp A will be brighter D. lamp A will start flickering if the ground is in an AC induction motor
Description : In the illustrated circuit, what is the voltage of the battery if the resistance of R1 is 150 ohms, the total resistance is 250 ohms and the current though R2 is 25 milliamps? EL-0036 A. 12 volts B. 24 volts C. 1.5 volts D. 6.25 volts
Description : The reading at 'M' on the megger scale illustrated, is ____. EL-0044 A. 7.1 meg ohms B. 71 meg ohms C. .71 meg ohms D. 200,000,000 ohms
Description : The reading at 'C' on the megger scale illustrated, is ________. EL-0044 A. 200,000 ohms B. 2,000,000 ohms C. 20,000,000 ohms D. 200,000,000 ohms