Bus coupler is very essential in arrangement
(a) single bus
(b) double bus, double breaker
(c) main and transfer bus
(d) all of the above

1 Answer

Answer :

(c) main and transfer bus

Related questions

Description : For an Resistive Load and Inductive load considered for switching operation of circuit breaker, Switching of which load is difficult and Why?

Last Answer : In case of switching resistive load, current and voltage will be in phase i.e,when during current zero voltage also will be zero in case of resistive load. Hence the voltage at the ... maximum. This results in re-striking of arc once again. Therefore switching inductive load will be difficult

Description : What is recovery voltage in circuit breaker?

Last Answer : Recovery voltage in circuit breakers is defined as the power frequency rms voltage which appears across the breaker contacts after the transient oscillations die out and the final extinction of the arc ... poles of the circuit breaker. It is the voltage developed after the arc extinction is competed

Description : Why asymmetrical breaking current is higher than the symmetrical breaking current in a circuit breaker?

Last Answer : Asymmetrical breaking current is the rms value of the combined sum of the dc and ac components of the short circuit current at the instant of separation of the breaker contacts while ... the ac component alone. Thus asymmetrical breaking current is higher than the symmetrical breaking current.

Description : Arc in a circuit breaker is interrupted at (a) zero current (b) maximum current (c) minimum voltage (d) maximum voltage

Last Answer : (a) zero current

Description : Which of the following circuit breakers has high reliability and minimum maintenance ? (a) Air blast circuit breakers (b) Circuit breaker with SF6 gas (c) Vacuum circuit breakers (d) Oil circuit breakers

Last Answer : (b) Circuit breaker with SF6 gas

Description : Which of the following is the least expensive protection for overcurrent is low voltage system ? (a) Rewireable fuse (b) Isolator (c) Oil circuit breaker (d) Air break circuit breaker (e) None of the above

Last Answer : (a) Rewireable fuse

Description : The arc voltage produced in A.C. circuit breaker is always (a) in phase with the arc current (b) lagging the arc current by 90" (c) leading the arc current by 90° (d) none of the above

Last Answer : (a) in phase with the arc current

Description : In a circuit breaker the basic problem is to (a) maintain the arc (b) extinguish the arc (c) transmit large power (d) emit the ionizing electrons

Last Answer : (c) transmit large power

Description : Ionization in circuit breaker is facilitated by (a) high temperature (b) increase of mean free path (c) increasing field strength (d) all of the above

Last Answer : (d) all of the above

Description : The voltage appearing across the contacts after opening of the circuit breaker is called______voltage. (a) recovery (b) surge (c) operating (d) arc (e) none of the above

Last Answer : (a) recovery

Description : Burden of a protective relay is the power (a) required to operate the circuit breaker (b) absorbed by the circuit of relay (c) developed by the relay circuit (d) none of the above

Last Answer : (b) absorbed by the circuit of relay

Description : Air blast circuit breaker is used for (a) over currents (b) short duty (c) intermittant duty (d) repeated duty

Last Answer : (d) repeated duty

Description : Magnetic circuit breaker has ______ trip action. (a) delayed (b) instantaneous (c) both of the above (d) none of the above

Last Answer : (b) instantaneous

Description : Thermal circuit breaker has (a) delayed trip action (b) instantaneous trip action (c) both of the above (d) none of the above

Last Answer : (a) delayed trip action

Description : With which of the following, a circuit breaker must be equipped for remote operation ? (a) Inverse time trip (b) Time-delay trip (c) Shunt trip (d) None of the above (e) All of the above

Last Answer : (c) Shunt trip

Description : Which of the following medium is employed for extinction of arc in air circuit breaker ? (a) Water (b) Oil (c) Air (d) SF6

Last Answer : (c) Air

Description : The arcing contacts in a circuit breaker are made of (a) copper tungsten alloy (b) porcelain (c) electrolytic copper (d) aluminium alloy

Last Answer : (a) copper tungsten alloy

Description : Which of the following busbar arrangement is generally employed in distribution system: a) One-and-half breaker arrangement b) Main and transfer arrangement c) Ring main distribution system d) Single busbar arrangement system

Last Answer : Ans: C

Description : Which of the following bus-bar schemes has the lowest cost ? (a) Ring bus-bar scheme (b) Single bus-bar scheme (c) Breaker and a half scheme (d) Main and transfer scheme

Last Answer : (b) Single bus-bar scheme

Description : The single phasing relays are used for the protection of (a) single phase motors only (b) two phase motors only (c) two single phase motors running in parallel (d) three phase motors

Last Answer : (d) three phase motors

Description : Short-circuit currents are due to (a) single phase to ground faults (b) phase to phase faults (c) two phase to ground faults (d) three phase faults (e) any of these

Last Answer : (e) any of these

Description : Discrimination between main and back up protection is provided by the use of relays which are (a) fact (b) sensitive (c) slow (d) none of the above

Last Answer : (c) slow

Description : The contacts of high voltage switches used in power system are submerged in oil. The main purpose of the oil is to (a) lubricate the contacts (b) insulate the contacts from switch body (c) extinguish the arc (d) all of the above (e) none of the above

Last Answer : (c) extinguish the arc

Description : The main function of a fuse is to (a) protect the line (b) open the circuit (c) protect the appliance (d) prevent excessive currents (e) none of the above

Last Answer : (d) prevent excessive currents

Description : Fortransmission-line loadmatchingover a range offrequencies,itisbesttouse a a. balun b. broadband directional coupler c. double stub d. single stub of adjustable position

Last Answer : c. double stub

Description : What is re-striking voltage?

Last Answer : The Re-striking voltage may be defined as the resultant transient voltage which appears across the breaker contacts at the instant of arc extinction

Description : When does an arc extincts?

Last Answer : If the rate of rise of re-striking voltage (RRRV) is less than rate of rise of dielectric strength between the breaker contacts arc will not sustain and extincts

Description : Why Isolation switches are provided along with the circuit breakers?

Last Answer : Isolation switches are provided for separating the disconnected element from the live portion of the system for the purpose of safety

Description : What is meant by Current Chopping?

Last Answer : Current Chopping is a phenomenon of current interruption before the natural current zero is reached.

Description : Air Blast Circuit Breakers Advantages Disadvantages

Last Answer : Air Blast Circuit Breakers Advantages Disadvantages In air blast circuit breakers, compressed air at a pressure of 20-30 kg/cm2 is employed as an arc quenching medium. Air blast circuit breakers ... air blast circuit breaker current chopping problem exists There is a problem of re-striking voltage

Description : The material used for fuse must have (a) low melting point and high specific resistance (b) low melting point and -low specific resistance (c) high melting point and low specific resistance (d) low melting point and any specific resistance

Last Answer : (a) low melting point and high specific resistance

Description : Admittance relay is _______ relay. (a) impedance (b) directional (c) non-directional (d) none of the above

Last Answer : (b) directional

Description : Series capacitors are used to (a) compensate for line inductive reactance (b) compensate for line capacitive reactance (c) improve line voltage (d) none of the above

Last Answer : (a) compensate for line inductive reactance

Description : Overfluxing protection is recommended for (a) distribution transformer (b) generator transformer of the power plant (c) auto-transformer of the power plant (d) station transformer of the power plant

Last Answer : (b) generator transformer of the power plant

Description : Air blast circuit breakers for 400 kV power system are designed to operate in (a) 100 microsecond (b) 50 millisecond (c) 0.5 sec (d) 0.1 sec

Last Answer : (b) 50 millisecond

Description : Over voltage protection is recommended for (a) hydro-electric generators (b) steam turbine generators (c) gas turbine generators (d) all of the above (e) none of the above

Last Answer : (d) all of the above

Description : The inverse definite mean time relays are used for over current and earth fault protection of transformer against (a) heavy loads (b) internal short-circuits (c) external short-circuits (d) all of the above

Last Answer : (b) internal short-circuits

Description : What will be the reflection coefficient of the wave of load connected to transmission line if surge impedance of the line is equal to load ? (a) Zero (b) Unity (c) Infinity (d) None of the above

Last Answer : (a) Zero

Description : transmission line has reflection coefficient as one. (a) Open circuit (b) Short-circuit (e) Long (d) None of the above

Last Answer : (a) Open circuit

Description : Series reactors should have (a) low resistance (b) high resistance (c) low impedance (d) high impedance

Last Answer : (a) low resistance

Description : Which of the following parameter can be neglected for a short line ? (a) Inductance (b) Capacitance (c) Resistance (d) Reactance

Last Answer : (b) Capacitance

Description : Which of the following devices will receive voltage surge first travelling on the transmission line ? (a) Lightning arresters (b) Relays (c) Step-down transformer (d) Switchgear

Last Answer : (a) Lightning arresters

Description : The relay with inverse time characteristic will operate within (a) 1.5 sec (b) 5 to 10 sec (c) 5 to 20 sec (d) 20 to 30 sec (e) none of the above

Last Answer : (b) 5 to 10 sec

Description : The under voltage relay can be used for (a) generators (b) busbars (c) transformers (d) motors (e) all of the above

Last Answer : (e) all of the above

Description : A _______ is used to measure the stator % winding temperature of the generator. (a) thermocouple (b) pyrometer (c) resistance thermometer (d) thermometer

Last Answer : (c) resistance thermometer

Description : For which of the following ratings of the transformer differential protection is recommended ? (a) above 30 kVA. (b) equal to and above 5 MVA (c) equal to and above 25 MVA (d) none of the above

Last Answer : (b) equal to and above 5 MVA

Description : Distance relays are generally (a) split-phase relays (b) reactance relays (c) impedance relays (d) none of the above

Last Answer : (d) none of the above

Description : relay is preferred for phase fault on short transmission line. (a) Induction type (b) Reactance (c) Impedance (d) None of the above

Last Answer : (b) Reactance

Description : For which of the following protection from negative sequence currents is provided ? (a) Generators (b) Motors (c) Transmission line (d) Transformers

Last Answer : (a) Generators