For which of the following ratings of the transformer differential protection is recommended ? (a) above 30 kVA. (b) equal to and above 5 MVA (c) equal to and above 25 MVA (d) none of the above

1 Answer

Answer :

(b) equal to and above 5 MVA

Related questions

Description : Overfluxing protection is recommended for (a) distribution transformer (b) generator transformer of the power plant (c) auto-transformer of the power plant (d) station transformer of the power plant

Last Answer : (b) generator transformer of the power plant

Description : Which of the following statements is incorrect ? (a) Lightning arrestors are used before the switchgear (b) Shunt reactors are used as compensation reactors (c) The peak short current is (1.8 xV2) ... component (d) The MVA at fault is equal to base MVA divided by per unit equivalent fault reactance

Last Answer : (a) Lightning arrestors are used before the switchgear

Description : Large internal faults are protected by (a) merz price percentage differential protection (b) mho and ohm relays (c) horn gaps and temperature relays (d) earth fault and positive sequence relays

Last Answer : (a) merz price percentage differential protection

Description : Over voltage protection is recommended for (a) hydro-electric generators (b) steam turbine generators (c) gas turbine generators (d) all of the above (e) none of the above

Last Answer : (d) all of the above

Description : The inverse definite mean time relays are used for over current and earth fault protection of transformer against (a) heavy loads (b) internal short-circuits (c) external short-circuits (d) all of the above

Last Answer : (b) internal short-circuits

Description : A differential relay measures the vector difference between (a) two currents (b) two voltages (c) two or more similar electrical quantities (d) none of the above

Last Answer : (c) two or more similar electrical quantities

Description : Ungrounded neutral transmission system is not recommended because of system (a) insulation being overstressed due to over voltages (b) insulation overstress may lead to failure and subsequent phase to phase faults (c) being inadequately protected against ground fault (d) all of the above

Last Answer : (d) all of the above

Description : Why are motor ratings given in KW and that of alternator and transformer given in KVA?

Last Answer : kW is the output mechanical power of a motor and is expressed in kW. kVA is the net (apparent) power input to the transformer. This input power is the output + losses. kW = kVA x system power factor

Description : The transformer ratings are usually expressed in terms of A. Volts B. Amperes C. kW D. kVA

Last Answer : D) KVA

Description : The single phasing relays are used for the protection of (a) single phase motors only (b) two phase motors only (c) two single phase motors running in parallel (d) three phase motors

Last Answer : (d) three phase motors

Description : For which of the following protection from negative sequence currents is provided ? (a) Generators (b) Motors (c) Transmission line (d) Transformers

Last Answer : (a) Generators

Description : Discrimination between main and back up protection is provided by the use of relays which are (a) fact (b) sensitive (c) slow (d) none of the above

Last Answer : (c) slow

Description : For the protection of power station buildings against direct strokes the requirements are (a) interception (b) interception and conduction (c) interception, conduction and dissipation (d) interception, conduction, dissipation and reflection (e) none of the above

Last Answer : (c) interception, conduction and dissipation

Description : Which of the following is the least expensive protection for overcurrent is low voltage system ? (a) Rewireable fuse (b) Isolator (c) Oil circuit breaker (d) Air break circuit breaker (e) None of the above

Last Answer : (a) Rewireable fuse

Description : The delay fuses are used for the protection of ________ . (a) motors (b) power outlet circuits (c) fluorescent lamps (d) light circuits

Last Answer : (a) motors

Description : H.R.C. fuses provide best protection against (a) overload (b) reverse current (c) open-circuits (d) short-circuits

Last Answer : (d) short-circuits

Description : A transmission line is protected by (a) inrush protection (b) distance protection (c) time graded and current graded over current protection (d) both (b) and (c) (e) none of the above

Last Answer : (d) both (b) and (c)

Description : A thermal protection switch can protect against (a) short-circuit (b) temperature (c) overload (d) over voltage

Last Answer : (c) overload

Description : Which of the following devices will receive voltage surge first travelling on the transmission line ? (a) Lightning arresters (b) Relays (c) Step-down transformer (d) Switchgear

Last Answer : (a) Lightning arresters

Description : The short circuit in any winding of the transformer is the result of (a) mechanical vibration (b) insulation failure (c) loose connection (d) impulse voltage

Last Answer : (d) impulse voltage

Description : Wave trap is used to trap waves of (a) power frequencies (b) higher frequencies entering generator or transformer units (c) either of the above (d) none of the above

Last Answer : (b) higher frequencies entering generator or transformer units

Description : The heat dissipating capability of transformers of ratings higher than 30 kVA in increased by providing which of the following ? (a) Corrugations (b) Fins (c) Tubes (d) Radiator tanks (e) All of the above

Last Answer : (e) All of the above

Description : The relay with inverse time characteristic will operate within (a) 1.5 sec (b) 5 to 10 sec (c) 5 to 20 sec (d) 20 to 30 sec (e) none of the above

Last Answer : (b) 5 to 10 sec

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Last Answer : D. Loading of the transformers not in proportion to their kVA ratings

Description : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

Last Answer : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is 80 MJ

Description : What will be the reflection coefficient of the wave of load connected to transmission line if surge impedance of the line is equal to load ? (a) Zero (b) Unity (c) Infinity (d) None of the above

Last Answer : (a) Zero

Description : How do we select a cable for a machine as per standards? Is there is any standard to select a cable as per voltage, or as per KVA and as per amps ratings?

Last Answer : Cable size depends upon current carrying capacity and voltage to withstand, to select cable size we must have knowledge of load of machine and operating voltage

Description : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is 500 kVA and its pu ... its pu leakage impedance is  (A) 0.20 (B) 0.10 (C) 0.05 (D) 0.025

Last Answer : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is ... .05 pu. If the rating of second transformer is 250 kVA, its pu leakage impedance is 0.10

Description : Air blast circuit breakers for 400 kV power system are designed to operate in (a) 100 microsecond (b) 50 millisecond (c) 0.5 sec (d) 0.1 sec

Last Answer : (b) 50 millisecond

Description : For an Resistive Load and Inductive load considered for switching operation of circuit breaker, Switching of which load is difficult and Why?

Last Answer : In case of switching resistive load, current and voltage will be in phase i.e,when during current zero voltage also will be zero in case of resistive load. Hence the voltage at the ... maximum. This results in re-striking of arc once again. Therefore switching inductive load will be difficult

Description : What is re-striking voltage?

Last Answer : The Re-striking voltage may be defined as the resultant transient voltage which appears across the breaker contacts at the instant of arc extinction

Description : When does an arc extincts?

Last Answer : If the rate of rise of re-striking voltage (RRRV) is less than rate of rise of dielectric strength between the breaker contacts arc will not sustain and extincts

Description : What is recovery voltage in circuit breaker?

Last Answer : Recovery voltage in circuit breakers is defined as the power frequency rms voltage which appears across the breaker contacts after the transient oscillations die out and the final extinction of the arc ... poles of the circuit breaker. It is the voltage developed after the arc extinction is competed

Description : Why asymmetrical breaking current is higher than the symmetrical breaking current in a circuit breaker?

Last Answer : Asymmetrical breaking current is the rms value of the combined sum of the dc and ac components of the short circuit current at the instant of separation of the breaker contacts while ... the ac component alone. Thus asymmetrical breaking current is higher than the symmetrical breaking current.

Description : Why Isolation switches are provided along with the circuit breakers?

Last Answer : Isolation switches are provided for separating the disconnected element from the live portion of the system for the purpose of safety

Description : What is meant by Current Chopping?

Last Answer : Current Chopping is a phenomenon of current interruption before the natural current zero is reached.

Description : Air Blast Circuit Breakers Advantages Disadvantages

Last Answer : Air Blast Circuit Breakers Advantages Disadvantages In air blast circuit breakers, compressed air at a pressure of 20-30 kg/cm2 is employed as an arc quenching medium. Air blast circuit breakers ... air blast circuit breaker current chopping problem exists There is a problem of re-striking voltage

Description : The material used for fuse must have (a) low melting point and high specific resistance (b) low melting point and -low specific resistance (c) high melting point and low specific resistance (d) low melting point and any specific resistance

Last Answer : (a) low melting point and high specific resistance

Description : Admittance relay is _______ relay. (a) impedance (b) directional (c) non-directional (d) none of the above

Last Answer : (b) directional

Description : Series capacitors are used to (a) compensate for line inductive reactance (b) compensate for line capacitive reactance (c) improve line voltage (d) none of the above

Last Answer : (a) compensate for line inductive reactance

Description : transmission line has reflection coefficient as one. (a) Open circuit (b) Short-circuit (e) Long (d) None of the above

Last Answer : (a) Open circuit

Description : Arc in a circuit breaker is interrupted at (a) zero current (b) maximum current (c) minimum voltage (d) maximum voltage

Last Answer : (a) zero current

Description : Which of the following circuit breakers has high reliability and minimum maintenance ? (a) Air blast circuit breakers (b) Circuit breaker with SF6 gas (c) Vacuum circuit breakers (d) Oil circuit breakers

Last Answer : (b) Circuit breaker with SF6 gas

Description : Series reactors should have (a) low resistance (b) high resistance (c) low impedance (d) high impedance

Last Answer : (a) low resistance

Description : Which of the following parameter can be neglected for a short line ? (a) Inductance (b) Capacitance (c) Resistance (d) Reactance

Last Answer : (b) Capacitance

Description : The under voltage relay can be used for (a) generators (b) busbars (c) transformers (d) motors (e) all of the above

Last Answer : (e) all of the above

Description : A _______ is used to measure the stator % winding temperature of the generator. (a) thermocouple (b) pyrometer (c) resistance thermometer (d) thermometer

Last Answer : (c) resistance thermometer

Description : Distance relays are generally (a) split-phase relays (b) reactance relays (c) impedance relays (d) none of the above

Last Answer : (d) none of the above

Description : relay is preferred for phase fault on short transmission line. (a) Induction type (b) Reactance (c) Impedance (d) None of the above

Last Answer : (b) Reactance

Description : relays are used for phase faults on long line. (a) Impedance (b) Reactance (c) Either of the above (d) None of the above

Last Answer : (a) Impedance