What will happen if transformer in parallel connection have different percentage impedance or X/R ratio ?

1 Answer

Answer :

A difference in the ratio of the reactance value to resistance value of the per unit impedance results in a different phase angle of the currents carried by the two paralleled transformers; one transformer will be working with a higher power factor and the other with a lower power factor than that of the combined output. Hence, the real power will not be proportionally shared by the transformers.

Related questions

Description : What will happen if transformer in parallel connection have different voltage ratio?

Last Answer : Two transformers in Parallel should have the same primary and secondary voltage ratings. Any error in the voltage ratio would cause heavy circulating currents to flow between the transformers. ... in overloading of one transformer. This circulating current will result in increased copper losses.

Description : What will happen if transformer in parallel connection have different phase sequence ?

Last Answer : If the phase sequence is in an incorrect manner, in every cycle each pair of phases will get short-circuited.

Description : What will happen if transformer in parallel connection have opposite polarity?

Last Answer : Connecting transformers with wrong polarity can result in circulating currents or short circuits

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Last Answer : D. Loading of the transformers not in proportion to their kVA ratings

Description : Which type of connection is used in distribution transformer?

Last Answer : Distribution transformers are connected in delta-star. This arrangement requires 3 conductors in the high voltage side and 4 in the low voltage side, as well as it provides the star point conductor as a neutral point. This can serve single phase as well as three phase loads.

Description : What are the conditions for parallel operation of transformer?

Last Answer : -Equal polarity -Equal turn ratio -percentage impedance should be same -Equal X/R ratio -Equal KVA rating -Equal phase sequence

Description : What is the need for parallel operation of transformer?

Last Answer : -Non availability of single large transformer to meet the load -Increased power demand -To improve reliability -If many smaller transformer is used one can be used as spare -Transportation problem for large transformer.

Description : What happen when Transformer is given DC supply ?

Last Answer : When DC supply is given to the transformer primary winding no back emf is induced in the transformer. Importance of Back emf is that it limits the current drawn by the machine. In the absence ... in burning down of primary winding. So when dc supply is given to transformer primary windings will burn

Description : What will happen if DC supply is given on the primary of a transformer?

Last Answer : A. Mainly transformer has high inductance and low resistance. In case of DC supply there is no inductance, only resistance will act in the electrical circuit. So, high electrical current will flow through primary side of the transformer. Due to this the coil and insulation will burn out.

Description : Two transformers of identical voltages but different capacities are operated in parallel, for satisfactory load sharing: a) Impedances should be equal b) Per unit impedance must be equal c) per unit impedance and X/R ratio must be equal d) Impedance and X/R ratio must be equal

Last Answer : Ans: C

Description : What is voltage ratio of a transformer?

Last Answer : A. Voltage ratio is the ratio of the voltage between the line terminals of one winding to that between the line terminals of another winding at no load.

Description : What is transformation ratio for step up, step down and isolation transformer?

Last Answer : K>1 for step up transformer K

Description : Why is Impedance Important?

Last Answer : ANSWER: It is used for determining the interrupting capacity of a circuit breaker or fuse employed to protect the primary of a transformer

Description : What is Meant by "Impedance" in Transformers?

Last Answer : ANSWER: Impedance is the current limiting characteristic of a transformer and is expressed in percentage.

Description : What is meant by “impedance” in transformers? Why is it important?

Last Answer : A. Impedance is the current limiting characteristic of a transformer and is expressed in percentage. It is used for determining the interrupting capacity of a circuit breaker or fuse employed to protect the primary of a transformer

Description : Why to calculate equivalent impedance referred to primary or secondary side?

Last Answer : Equivalent impedance is essential to be calculated because the electrical power transformer is an electric power system equipment, for estimating different parameters of electric power system ... referred to primary or equivalent circuit of transformer referred to secondary sides respectively.

Description : Give equivalent resistance, reactance and impedance referred to secondary circuit.

Last Answer : Req = R2 +R1' = R2+ R1'/a² Xeq = X2 +X1' = X2+ X1'/a² Zeq = Z2 + Z1' = Z2+ Z1'/a² where a=T1/T2

Description : Give equivalent resistance, reactance and impedance referred to primary circuit.

Last Answer : Req = R1 +R2' = R1+a² R2' Xeq = X1 +X2' = X1+a² X2' Zeq = Z1 +Z2' = Z1+a² Z2' where a=T1/T2

Description : Which of the following 3-phase connection of a transformer causes interference with the neighbouring communication lines:  (A) Delta-Star (B) Star-Delta (C) Delta-Delta (D) Star-Star

Last Answer : Which of the following 3-phase connection of a transformer causes interference with the neighbouring communication lines: Star-Star

Description : To protect the power transformer (Y-Y with neutral grounded) against fault, what type of connection do the CTs have ?

Last Answer : To protect the power transformer (Y-Y with neutral grounded) against fault, what type of connection do the CTs have ? Δ-Δ connection

Description : What will happen if the primary of a transformer is connected to D.C. supply?  (A) Transformer will operate with low efficiency (B) Transformer will operate with high efficiency (C) No effect (D) Transformer may start to smoke and burn 

Last Answer : What will happen if the primary of a transformer is connected to D.C. supply?  (A) Transformer will operate with low efficiency (B) Transformer will operate with high efficiency (C) No effect (D) Transformer may start to smoke and burn 

Description : What would happen if a power transformer designed for operation on 50 Hz (frequency) were connected to a 500 Hz (frequency) source of the same voltage:  (A) Eddy Current and Hysteresis losses will be ... Current will be too much high  (C) Transformer may start to smoke and burn  (D) No effect

Last Answer : What would happen if a power transformer designed for operation on 50 Hz (frequency) were connected to a 500 Hz (frequency) source of the same voltage:  (A) Eddy Current and Hysteresis losses will be ... will be too much high  (C) Transformer may start to smoke and burn  (D) No effect

Description : What advantage has the star connection over the delta connection ?

Last Answer : A. Each star connection transformer is wound for only 57.7% of line voltage . In hv transmission, this admits of much smaller transformer being built for high voltage than possible with delta connection, because of less insulation.

Description : What is the advantage is obtained in the delta connection ?

Last Answer : A. When three transformer are obtained in delta, one may be removed and two remaining unit will carry 57.7% of the original three phase load and thus maintain the continuity of supply.

Description : What are the transformer losses?

Last Answer : Answer: TRANSFORMER LOSSES - There are mainly two kinds of losses in a transformer namely 1. Copper loss (ohmic loss) and 2.magnetic loss (core loss). Copper losses are caused by the ... ohmic loss the following two losses are also present in the transformer stray load loss and dielectric loss.

Description : At what power maximum efficiency of power transformer and distribution transformer is designed

Last Answer : Maximum efficiency of the transformer is attained at certain load factor (α) when core losses of transformer is equal to the copper losses. PCore loss = α ^2 X PCopper loss From the ... the day. Hence distribution transformers are designed to have maximum efficiency at 50% of the rated full load

Description : During No load why the power factor of the transformer is very low ?

Last Answer : Current flowing through the transformer consists of two components. Magnetizing current (Im) which is in quadrature (90 0 ) to the applied voltage and in phase current which is in phase to the applied voltage ... power factor of transformer during no load condition will by in the order of 0.1 to 0.2

Description : What is the supply rated o/p if two single phase transformer connect to give three phase o/p from a three phase I/p?

Last Answer : A. Each transformer is only capable of supplying 86.6%of its o/p rating

Description : How to connect two single phase transformer to give three phase o/p from a three phase I/p ?

Last Answer : A. They would have to connect in an open-delta.

Description : What is the 3 ph transformer ?

Last Answer : A. A 3ph transformer is that transformer which is equivalent to three single phase transformer but wound on one core and enclosed within one common case.

Description : What parameters or technical particulars are important to be considered while designing protection scheme of the transformer?

Last Answer : 1.Network Diagram showing the position of the transformer in the system 2.kVA or MVA rating of the transformer 3.Fault Level at the transformer 4.Voltage Ratio 5.Winding Connections 6.Per Unit ... Oil Filled 11.Length and area of cross section of the connecting leads between CTs and Relay Panel

Description : What can be the reasons for the failure of the transformer?

Last Answer : Answer: Transformer is one of the most expensive equipments in the Power System. Failure of the transformer can cause outage of power supply for even days. However, multiple things can go wrong with ... relays. 3.Short Circuits 4.Open Circuits 5.Earth Faults 6.Over Voltage 7.Reduced system frequency

Description : How Transformer Protection provided for internal faults?

Last Answer : 1.Bucholz Relay (1st Stage Alarm and 2nd Stage Trip) 2.Sudden Pressure Relay (1st Stage Alarm and 2nd Stage Trip) 3.Pressure Relief Valve (1st Stage Alarm and 2nd Stage Trip) 4.Pressure Switch ... 8.Gas Temperature Indicator (Alarm) 9.Silicon Breather (Passive - no alarm) 10.Smoke Detector (Alarm)

Description : How does change in frequency affect the operation of a given transformer?

Last Answer : a) Iron loss .........increases with a decrease in frequency. A 60-Hz transformer will have nearly 11% higher losses when worked on 50Hz instead of 60 Hz. However, when a 25-Hz ... ....since total loss is greater at a lower frequency, the temperature is increased with decrease in frequency.

Description : Does the transformer draw any current when its secondary is open?

Last Answer : Yes, no-load primary current.

Description : WHAT is ZIG ZAG Grounding Transformer

Last Answer : ANSWER: Three Single Phase Transformers can be connected to have a three phase Zig Zag Transformer. This system can be used for either grounding or developing a fourth WIRE from a three phase neutral. An example ... - three phase - three wire system to a 480Y/277 V - three phase - four wire system

Description : What is Meant by Temperature Rise in a Transformer?

Last Answer : ANSWER: Temperature rise in a transformer is the temper¬ature of the windings and insulation above the existing ambi¬ent or surrounding temperature, and is determined by the insulation class used in the transformer coils.

Description : What is Meant by Regulation in a Transformer?

Last Answer : ANSWER: Voltage regulation in transformers is the difference between the no load voltage and the full load voltage. This is usually expressed in terms of percentage. For example: A transformer delivers 100 ... from 2% to 4%, depending on the size and the application for which they are used

Description : What is Polarity, When Associated With a Transformer?

Last Answer : A: Polarity is the instantaneous voltage obtained from the primary winding in relation to the secondary winding. Transformers 600 volts and below are normally connected in additive polarity - that ... parallel for three phase operations. Polarity is a term used only with single phase transformers

Description : During No load why the power factor of the transformer is very low ?

Last Answer : A. Current flowing through the transformer consists of two components. Magnetizing current (Im) which is in quadrature (900) to the applied voltage and in phase current which is in phase to the applied voltage ... factor of transformer during no load condition will by in the order of 0.1 to 0.2

Description : Explain about auto transformer?

Last Answer : A. It is type of transformer with only one winding a portion of which is shared by both primary and secondary. Advantages: It is used where transformation ratio differs little from unity. As ... voltage as per out requirements and can smoothly increase or decrease its value as per our requirement.

Description : Explain about the open and short circuit tests on transformer?

Last Answer : A. Open circuit test (No load test) and short circuit test (full load test) are performed on a transformer to determine (i) Equivalent circuit of transformer (ii) Voltage ... determine copper loss in transformer at full load and parameters of approximate equivalent circuit of transformer.

Description : EMF equation of the transformer?

Last Answer : A. E = 4.44ΦmfN Volts. If E1 & E2 are primary and secondary emf’s and N1 & N2 are primary and secondary turns then, Voltage ratio= E1/E2 and Turns ratio of transformer = N1/N2 E1/E2 = N1/N2

Description : What is tertiary winding? What is Three Winding Transformer? What are its advantages?

Last Answer : A. In some high rating transformers, one winding, in addition to the primary and secondary winding, is used. This is known as Tertiary Winding of Transformer. Because of this third winding, the ... it assists in limitation of fault current in the event of a short circuit from line to neutral.

Description : What is polarity, when associated with a transformer?

Last Answer : A. Polarity is the instantaneous voltage obtained from the primary winding in relation to the secondary winding. Transformers 600 volts and below are normally connected in additive polarity - that ... parallel for three phase operations. Polarity is a term used only with single phase transformers.

Description : Can a Single Phase Transformer be used on a Three Phase source?

Last Answer : A. Any single phase transformer can be used on a three phase source by connecting the primary leads to any two wires of a three phase system, regardless of whether the source is three phase 3-wire or three phase 4 wire. The transformer output will be single phase.

Description : What is meant by regulation in a transformer?

Last Answer : A. Voltage regulation in transformers is the difference between the no load voltage and the full load voltage. This is usually expressed in terms of percentage. Example: A Transformer delivers 100 ... The regulation capacity varies depending on the size and the application for which they are used.

Description : Explain the operation of variable frequency transformer?

Last Answer : A. A variable frequency transformer is used to transmit electricity between two asynchronous alternating current domains. It is a double fed electric machine resembling a vertical shaft hydroelectric ... adjustable phase shifting transformer. It allows control of the power flow between two networks.

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer : A. As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : What is the function of transformer oil?

Last Answer : A. Transformer Oil serves mainly two purposes 1. It acts as liquid insulation in electrical power transformer 2. It dissipates heat of the transformer i.e acts as coolant. In addition to these ... acid (C7, C8) esters are also becoming increasingly common as alternatives to naphthenic mineral oil.