Which of the listed battery charging circuits is used to maintain a wet-cell, lead-acid, storage battery in a fully charged state during long periods of disuse? A. Normal charging circuit B. Quick charging circuit C. Trickle charging circuit D. High ampere charging circuit

1 Answer

Answer :

Answer: C

Related questions

Description : Trickle charger of a storage battery helps to A. Maintain proper electrolyte level B. Increase its reverse capacity C. Prevent sulphation D. Keep it fresh and fully charged

Last Answer : D. Keep it fresh and fully charged

Description : Under normal conditions, storage batteries used for starting the emergency diesel generator are maintained in a charged state by which of the following methods? A. Trickle charging B. Fast charging C. Equalizing charge D. Reverse charging

Last Answer : Answer: A

Description : Which of the processes listed occurs during the charging of a lead-acid storage battery? A. Negative plates change to lead peroxide. B. Positive plates change to lead peroxide. C. Both plates change to lead peroxide. D. Both plates change to lead sulfate.

Last Answer : Answer: B

Description : Which of the listed ranges represents specific gravity corrected for temperature for the electrolyte of a fully charged portable lead-acid battery? A. 1.100 to 1.150 B. 1.180 to 1.200 C. 1.280 to 1.300 D. 1.750 to 2.000

Last Answer : Answer: C

Description : The open-circuit voltage of a fully charged lead-acid battery cell is _____________. A. 1.5 volts B. 1.8 volts C. 2.0 volts D. 2.3 volts

Last Answer : Answer: C

Description : Which of the following statements concerning nickel-cadmium batteries is true? A. When mixing electrolyte always add acid to the water. B. Nickel-cadmium batteries can be charged and ... The electrolyte of an idle nickel-cadmium battery must be replaced monthly to maintain battery condition.

Last Answer : Answer: C

Description : The state of charge of a lead acid storage battery is best indicated by the _____________. A. testing of the individual cell voltages B. ampere hour capacity of the battery C. specific gravity of the electrolyte D. total cell voltages

Last Answer : Answer: C

Description : Which of the listed safety features should be provided in small rooms or lockers where batteries are stored? A. Installation of a fixed CO2 system. B. An exhaust duct is to be provided and led from within ... An exhaust duct is to be provided and led from the top of the locker to the open air.

Last Answer : Answer: D

Description : A lead-acid battery may become hotter than normal during a charge if the _________. A. battery has a shorted cell B. charging voltage is too low C. specific gravity is too high D. battery room door is secured

Last Answer : Answer: A

Description : In accordance with Coast Guard Regulations (46 CFR), each battery operated relay-controlled lantern must _____________. A. be readily portable B. contain a dry cell battery having a minimum capacity of ... automatic battery charger to maintain the battery in a fully charged state D. all of the above

Last Answer : Answer: C

Description : In the illustration, the chemical reaction depicted indicates that the _________. EL-0061 A. battery is being charged at a high rate B. cell is short circuited C. cell is discharging D. battery is attached to a trickle charger

Last Answer : Answer: C

Description : Violent gassing from a lead-acid battery while it is being charged, indicates that the _____________. A. plate separators are grounded B. battery compartment ventilation is inadequate C. electrolyte specific gravity is too low D. charging rate is too high

Last Answer : Answer: D

Description : Which of the following procedures represents the best method to prevent the freezing of batteries continuously exposed to low temperatures? A. The battery caps should be removed. B. The battery cap ... in a fully charged condition. D. The battery should be disconnected from its charging source.

Last Answer : Answer: C

Description : Which of the following problems is indicated if a lead-acid battery begins to gas violently when it is first placed on charge? A. Insufficient compartment ventilation is being provided. B. A short ... undergoing its normal charging rate. D. An excessive charging rate is being applied to the battery.

Last Answer : Answer: D

Description : Which of the following activities occurs during the charging process of a lead-acid storage battery? A. The specific gravity of the acid increases. B. Both plates change chemically to lead sulfate. C. The specific gravity of the acid decreases. D. Hydrogen gas is absorbed.

Last Answer : Answer: A

Description : Local action in a nickel-cadmium battery is offset by _____________. A. separating the positive and negative plates with plastic spacers B. separating the positive and negative plates with resin impregnated spacers C. adding a small amount of lithium hydroxide to the electrolyte D. trickle charging

Last Answer : Answer: D

Description : If violent gassing occurs when a lead-acid storage battery is first placed on charge, the _____________. A. battery must be given an emergency charge B. charging rate is too low C. charging rate is too high D. specific gravity of the electrolyte solution is too low

Last Answer : Answer: C

Description : A lead-acid battery is considered fully charged when the ______________. A. electrolyte gasses freely B. battery charger ammeter indicates a positive reading C. terminal voltage reaches a constant value at a ... cells reaches the correct value and no longer increases over a period of 1 to 4 hours

Last Answer : Answer: D

Description : The freezing point of the electrolyte in a fully charged lead-acid battery will be _____________. A. higher than in a discharged battery B. lower than in a discharged battery C. the same as in a discharged battery D. higher than in a discharged battery, but the specific gravity will be less

Last Answer : Answer: B

Description : Define specific gravity and mention the specific gravity of a fully charged lead acid battery?

Last Answer : Specific gravity of a substance is the comparison of density of the substance with the density of pure water. Specific gravity = Density of the substance / density of pure water.    ... - 27°C)*0.0007. Indicated specific gravity = 1.205 and t' means electrolyte temperature.   

Description : A lead-acid battery cell sustaining a short circuit _______. A. will be indicated by lime accumulation on the terminal posts B. will have unusually high cell voltage C. will become excessively heated while being charged D. cannot be completely discharged under load

Last Answer : Answer: C

Description : The state of charge of a lead-acid battery is best indicated by the ____________. A. individual cell voltage B. ampere-hour capacity C. electrolyte specific gravity D. total cell voltage

Last Answer : Answer: C

Description : Violent gassing developed by a lead-acid battery during charging indicates that the ____________. A. plate separators are grounded B. cell voltages are excessive C. specific gravity in insufficient D. charging rate is excessive

Last Answer : Answer: D

Description : Maintenance of alkaline batteries should include _________. A. checking the electrolyte weekly using a hydrometer B. replacing the electrolyte every 5 years C. trickle charging D. replacment when the volts per cell drops below 1.8 VDC

Last Answer : Answer: C

Description : A slow continual loss of electrolyte level from one cell of a storage battery could be due to _______________. A. a cracked casing B. too low a charging rate C. the specific gravity being higher than normal D. one filler cap installed too tightly

Last Answer : Answer: A

Description : When a lead-acid battery begins gassing freely while receiving a normal charge, the charging current should _____________. A. be increased B. remain unchanged C. be decreased D. shut off

Last Answer : Answer: C

Description : When a lead-acid battery begins gassing freely while receiving a normal charge, the charging current should be _____________. A. increased B. shut off C. decreased D. unchanged

Last Answer : Answer: C

Description : The specific gravity of the electrolyte solution in a lead acid battery _____________. A. is not effected during charging B. remains the same during discharge C. would read close to 1.830 when discharged D. gives an indication of the state of charge of the battery

Last Answer : Answer: D

Description : When troubleshooting a lead-acid storage battery, a weak or dead cell is best detected by _________________. A. measuring and comparing all cells' specific gravity B. taking an open circuit ... electrolyte levels of each cell D. taking each cell's temperature with a calibrated mercury thermometer

Last Answer : Answer: A

Description : When a nickel-cadium battery begins gassing while connected to the battery charging circuit, you should _____________. A. do nothing as this is a normal condition when charging B. add distilled water ... to each cell to increase the specific gravity of the electrolyte D. decrease the charging rate

Last Answer : Answer: A

Description : When charging a 100 amp-hour lead-acid battery, ___________. A. the temperature of the electrolyte should not be allowed to exceed 90°F B. the charging rate should be no greater than 125% of the ... nearing full charge and it will be necessary to reduce the charging current to a low finishing rate

Last Answer : Answer: C

Description : When charging lead-acid batteries, the charging rate should be reduced as the battery nears its full charge to ____________. A. prevent damaging battery plates B. allow equalization of cell voltages C. reduce lead sulfate deposits D. increase lead peroxide formation

Last Answer : Answer: A

Description : When charging lead-acid batteries, you should reduce the charging rate as the battery nears its full charge capacity to ______________. A. prevent excessive gassing and overheating B. allow equalization of cell voltages C. reduce lead sulfate deposits D. increase lead peroxide formation

Last Answer : Answer: A

Description : Caution must be exercised during the charging of lead-acid storage batteries as _____________. A. the acid will become weaker B. hydrogen gas is being continuously liberated C. both plates are changing chemically to lead sulfate D. lead peroxide in the negative plate is poisonous

Last Answer : Answer: B

Description : If the values of 'C' and 'R' shown in the illustration were 1 microfarad and 100 kOhms respectively, at what listed time would 'C' be considered fully charged? EL-0086 A. 0.1 second B. 0.2 second C. 0.5 second D. 5 seconds

Last Answer : Answer: C

Description : If the values of 'C' and 'R' shown in the illustration were 1 microfarad and 3 Megohms respectively, at what listed time would 'C' be considered fully charged? EL-0086 A. 0.33 second B. 3 seconds C. 6 seconds D. 15 seconds

Last Answer : Answer: D

Description : A lead-acid battery can deliver 20 amperes continuously for 10 hours with an ampere-hour rating of ____________. A. 20 B. 40 C. 200 D. 400

Last Answer : Answer: C

Description : When you check the specific gravity of the battery electrolyte with a hydrometer, it should be kept in mind that ____________. A. the battery is fully charged when the indicator floats low in ... taken immediately after water is added to the cell D. temperature has no effect on hydrometer readings

Last Answer : Answer: C

Description : When checking the specific gravity of the battery electrolyte with a hydrometer, you should be aware that ________________. A. the battery is fully charged when the float sinks deepest into the ... is added to the cell D. warm temperatures will lower the specific gravity of the electrolyte

Last Answer : Answer: D

Description : Loss of or weak residual magnetism in an alternator or generator can be corrected for by _________________. A. running the rotor in the opposite direction for 5 minutes B. allowing the generator ... rheostat fully counterclockwise D. using a storage battery or battery charger to 'flash' the field

Last Answer : Answer: D

Description : Which of the problems listed will occur if a lead-acid battery is allowed to remain in a discharged condition for a long period of time? A. The battery may be unable to accept a full charge ... . C. The concentrated sulfuric acid will attack the lead peroxide plates. D. The separators will harden.

Last Answer : Answer: A

Description : Routine maintenance of lead acid batteries should include _____________. A. keeping the terminals clean B. coating cable connections with petroleum jelly C. maintaining a trickle charge D. all of the above

Last Answer : Answer: D

Description : When the electrolyte level of a lead-acid storage battery has decreased due to normal evaporation, the level should be reestablished by adding _____________. A. distilled water only B. sulfuric acid ... of sulfuric acid and distilled water D. a strong solution of sulfuric acid and distilled water

Last Answer : Answer: A

Description : Why lead acid battery requires so much large initial charging?  

Last Answer : Initially for a new battery, negative plate will be PbO instead of Pb. To convert all of them back to Pb, we need so much prolonged initial charging.  

Description : The charging of lead-acid storage batteries will always result in __________. A. dangerous acid burns B. a dangerously explosive gas being liberated C. the danger of lead poisoning D. all of the above

Last Answer : Answer: B

Description : pecific gravity of fully charged storage battery is ∙ 1.15 ∙ 1.50 ∙ 1.28 ∙ 2.15

Last Answer : ∙ 1.28

Description : Which of the following conditions indicates that a lead-acid battery is being charged too rapidly? A. Sparks occurring at the positive terminal. B. Unusually high electrolyte specific gravity. C. Low plate potentials being developed. D. Excessively high temperatures and gassing rates.

Last Answer : Answer: D

Description : At high discharge rates, nickel-cadmium storage batteries are superior to lead-acid batteries because they __________. A. require fewer cells for the same voltage and less mounting space B. are able to ... times without much damage D. have no individual cells to replace at the end of useful life

Last Answer : Answer: C

Description : During the charging process of storage batteries, the charging rooms should be well ventilated because __________. A. without ventilation excessive gassing will occur B. highly poisonous gases are ... gases will otherwise accumulate D. without ventilation the battery will not take a full charge

Last Answer : Answer: C