Last Answer : Do you perchance mean role-playing games rather than Dungeons & Dragons specifically? If so, then, maybe you mean what is generally called lifepath character generation? That is, systems where you ... they enter play? If so, then yes. Perhaps the first such published RPG system was Traveller.

Description : How do you play a lv 10 diviner in Dungeons & Dragons?

Last Answer : D&D isn’t always about battle. Sometimes it’s about politics. Or adventure. There’s much more to it than just stat grinding and dungeon crawls.

Description : What is the full form of LV ?

Last Answer : Full Variety of LV.

Description : As shown in the illustration, once the "LV" relay is energized for operation, what contacts must remain closed to maintain the "LV" relay energized when the control lever is moved away from the "off" or "stop" ... . B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : As shown in the illustration, what is responsible for maintaining the "LV" relay energized when the master switch handle is moved away from the "off" position? EL-0102 A. "DBa" contact. B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : When the master switch for the winch shown in the illustration is in the 'off' position, and the line & safe switches are closed, which of the listed relays should be energized? EL-0102 A. 'DB' & '2T' B. 'DB' & '4M' C. 'FR-B.O.' & 'LV' D. '1M' & '1A'

Last Answer : Answer: C

Description : Why OC test is generally performed on LV side of a transformer?

Last Answer : The high-voltage side is generally kept open because the current in high-voltage winding is less compared to that on low-voltage winding.The LV side has higher current so that maximum no load current can be measured.

Description : What are the protections used in Class III & Class IV 415 V LV side?  

Last Answer : Class III 415 V LV side 1. 51 (inverse over current) 2. 50 (instantaneous over current) 3. 27 (under voltage) 4. 51N (earth fault) 5. 64 (REF)  Class IV 415 V LV side 1. 51 RYB (inverse over current) 2. 51N (earth fault) 

Description : Why REF is provided in the LV side of SUT and UT? 

Last Answer : The LV sides of the two transformers are earthed through the resistance. This will limit the flow of current in case of LV earth fault. Hence the differential protection may not act for a LV earth fault. Hence ref protection is provided. 

Description : Why in transformer the LV CB also be tripped along with HV CB for a primary side fault?

Last Answer : Auxiliary transformer 415v delta star transformer, if HV CB alone tripped then back feeding from LV side (say DG runs parallel with transformer)—arcing voltage at the fault on primary—fault fed for more time – more damage.  

Description : For LV applications (below 1 kV), ______________ cables are used. (A) Paper insulated. (B) Plastic. (C) Single core cables. (D) Oil filled.

Last Answer : Ans: C For low voltage applications single core cables are suitable.