The interaction between a transmission line and communication line is minimized by (a) transposing transmission as well as communication lines (b) increasing the height of the transmission line tower (c) increasing the distance between the two lines (d) all of the above

1 Answer

Answer :

(d) all of the above

Related questions

Last Answer : The interaction between a transmission line and communication line is minimized by transposing transmission as well as communication lines, increasing the height of the transmission line tower, increasing the distance between the two lines.

Description : Shunt capacitance is neglected while considering (a) short transmission line (b) medium transmission line (c) long transmission line (d) medium and long transmission lines

Last Answer : (a) short transmission line

Description : A transmission line is protected by (a) inrush protection (b) distance protection (c) time graded and current graded over current protection (d) both (b) and (c) (e) none of the above

Last Answer : (d) both (b) and (c)

Description : What will be the reflection coefficient of the wave of load connected to transmission line if surge impedance of the line is equal to load ? (a) Zero (b) Unity (c) Infinity (d) None of the above

Last Answer : (a) Zero

Description : transmission line has reflection coefficient as one. (a) Open circuit (b) Short-circuit (e) Long (d) None of the above

Last Answer : (a) Open circuit

Description : Which of the following devices will receive voltage surge first travelling on the transmission line ? (a) Lightning arresters (b) Relays (c) Step-down transformer (d) Switchgear

Last Answer : (a) Lightning arresters

Description : relay is preferred for phase fault on short transmission line. (a) Induction type (b) Reactance (c) Impedance (d) None of the above

Last Answer : (b) Reactance

Description : For which of the following protection from negative sequence currents is provided ? (a) Generators (b) Motors (c) Transmission line (d) Transformers

Last Answer : (a) Generators

Description : When a wave propagates on a transmission line, it suffers reflection several times at (a) tapping (b) load end (c) sending end (d) sending and other end (e) all of the above

Last Answer : (d) sending and other end

Description : The reflection co-efficient at the open circuited end of a transmission line. (a) zero (b) infinity (c) unity (d) none of the above

Last Answer : (c) unity

Description : When a transmission line is energized, the wave that propagates on it is (a) current wave only (b) voltage wave only (c) both (a) and (b) (d) power factor wave only

Last Answer : (c) both (a) and (b)

Description : Ionization in circuit breaker is facilitated by (a) high temperature (b) increase of mean free path (c) increasing field strength (d) all of the above

Last Answer : (d) all of the above

Description : Arc in a circuit behaves as (a) a capackive reactance (b) an inductive reactance (c) a resistance increasing with voltage rise across the arc (d) a resistance decreasing with voltage rise across the arc

Last Answer : (d) a resistance decreasing with voltage rise across the arc

Description : Ungrounded neutral transmission system is not recommended because of system (a) insulation being overstressed due to over voltages (b) insulation overstress may lead to failure and subsequent phase to phase faults (c) being inadequately protected against ground fault (d) all of the above

Last Answer : (d) all of the above

Description : Distance relays are generally (a) split-phase relays (b) reactance relays (c) impedance relays (d) none of the above

Last Answer : (d) none of the above

Description : An efficient and a well designed protective relaying should have (a) good selectivity and reliability (b) economy and simplicity (c) high speed and selectivity (d) all of the above

Last Answer : (d) all of the above

Description : Series capacitors are used to (a) compensate for line inductive reactance (b) compensate for line capacitive reactance (c) improve line voltage (d) none of the above

Last Answer : (a) compensate for line inductive reactance

Description : Which of the following parameter can be neglected for a short line ? (a) Inductance (b) Capacitance (c) Resistance (d) Reactance

Last Answer : (b) Capacitance

Description : relays are used for phase faults on long line. (a) Impedance (b) Reactance (c) Either of the above (d) None of the above

Last Answer : (a) Impedance

Description : The line insulation is the insulation level of the station equipment. (a) less than (b) same as (c) more than (d) proportional to (e) not directly related with

Last Answer : (e) not directly related with

Description : The main function of a fuse is to (a) protect the line (b) open the circuit (c) protect the appliance (d) prevent excessive currents (e) none of the above

Last Answer : (d) prevent excessive currents

Last Answer : The inductive interference between power and communication line can be minimized by transposition of the power line, transposition of the communication line.

Description : The single phasing relays are used for the protection of (a) single phase motors only (b) two phase motors only (c) two single phase motors running in parallel (d) three phase motors

Last Answer : (d) three phase motors

Description : Short-circuit currents are due to (a) single phase to ground faults (b) phase to phase faults (c) two phase to ground faults (d) three phase faults (e) any of these

Last Answer : (e) any of these

Description : A differential relay measures the vector difference between (a) two currents (b) two voltages (c) two or more similar electrical quantities (d) none of the above

Last Answer : (c) two or more similar electrical quantities

Description : Circuit breakers are essentially (a) current carrying contacts called electrodes (b) arc extinguishers (c) circuits to break the system (d) transformers to isolate the two systems (e) any of the above

Last Answer : (a) current carrying contacts called electrodes

Description : For an Resistive Load and Inductive load considered for switching operation of circuit breaker, Switching of which load is difficult and Why?

Last Answer : In case of switching resistive load, current and voltage will be in phase i.e,when during current zero voltage also will be zero in case of resistive load. Hence the voltage at the ... maximum. This results in re-striking of arc once again. Therefore switching inductive load will be difficult

Description : What is re-striking voltage?

Last Answer : The Re-striking voltage may be defined as the resultant transient voltage which appears across the breaker contacts at the instant of arc extinction

Description : When does an arc extincts?

Last Answer : If the rate of rise of re-striking voltage (RRRV) is less than rate of rise of dielectric strength between the breaker contacts arc will not sustain and extincts

Description : What is recovery voltage in circuit breaker?

Last Answer : Recovery voltage in circuit breakers is defined as the power frequency rms voltage which appears across the breaker contacts after the transient oscillations die out and the final extinction of the arc ... poles of the circuit breaker. It is the voltage developed after the arc extinction is competed

Description : Why asymmetrical breaking current is higher than the symmetrical breaking current in a circuit breaker?

Last Answer : Asymmetrical breaking current is the rms value of the combined sum of the dc and ac components of the short circuit current at the instant of separation of the breaker contacts while ... the ac component alone. Thus asymmetrical breaking current is higher than the symmetrical breaking current.

Description : Why Isolation switches are provided along with the circuit breakers?

Last Answer : Isolation switches are provided for separating the disconnected element from the live portion of the system for the purpose of safety

Description : What is meant by Current Chopping?

Last Answer : Current Chopping is a phenomenon of current interruption before the natural current zero is reached.

Description : Air Blast Circuit Breakers Advantages Disadvantages

Last Answer : Air Blast Circuit Breakers Advantages Disadvantages In air blast circuit breakers, compressed air at a pressure of 20-30 kg/cm2 is employed as an arc quenching medium. Air blast circuit breakers ... air blast circuit breaker current chopping problem exists There is a problem of re-striking voltage

Description : The material used for fuse must have (a) low melting point and high specific resistance (b) low melting point and -low specific resistance (c) high melting point and low specific resistance (d) low melting point and any specific resistance

Last Answer : (a) low melting point and high specific resistance

Description : Admittance relay is _______ relay. (a) impedance (b) directional (c) non-directional (d) none of the above

Last Answer : (b) directional

Description : Overfluxing protection is recommended for (a) distribution transformer (b) generator transformer of the power plant (c) auto-transformer of the power plant (d) station transformer of the power plant

Last Answer : (b) generator transformer of the power plant

Description : Air blast circuit breakers for 400 kV power system are designed to operate in (a) 100 microsecond (b) 50 millisecond (c) 0.5 sec (d) 0.1 sec

Last Answer : (b) 50 millisecond

Description : Over voltage protection is recommended for (a) hydro-electric generators (b) steam turbine generators (c) gas turbine generators (d) all of the above (e) none of the above

Last Answer : (d) all of the above

Description : The inverse definite mean time relays are used for over current and earth fault protection of transformer against (a) heavy loads (b) internal short-circuits (c) external short-circuits (d) all of the above

Last Answer : (b) internal short-circuits

Description : Arc in a circuit breaker is interrupted at (a) zero current (b) maximum current (c) minimum voltage (d) maximum voltage

Last Answer : (a) zero current

Description : Which of the following circuit breakers has high reliability and minimum maintenance ? (a) Air blast circuit breakers (b) Circuit breaker with SF6 gas (c) Vacuum circuit breakers (d) Oil circuit breakers

Last Answer : (b) Circuit breaker with SF6 gas

Description : Series reactors should have (a) low resistance (b) high resistance (c) low impedance (d) high impedance

Last Answer : (a) low resistance

Description : The relay with inverse time characteristic will operate within (a) 1.5 sec (b) 5 to 10 sec (c) 5 to 20 sec (d) 20 to 30 sec (e) none of the above

Last Answer : (b) 5 to 10 sec

Description : The under voltage relay can be used for (a) generators (b) busbars (c) transformers (d) motors (e) all of the above

Last Answer : (e) all of the above

Description : A _______ is used to measure the stator % winding temperature of the generator. (a) thermocouple (b) pyrometer (c) resistance thermometer (d) thermometer

Last Answer : (c) resistance thermometer

Description : For which of the following ratings of the transformer differential protection is recommended ? (a) above 30 kVA. (b) equal to and above 5 MVA (c) equal to and above 25 MVA (d) none of the above

Last Answer : (b) equal to and above 5 MVA

Description : The short circuit in any winding of the transformer is the result of (a) mechanical vibration (b) insulation failure (c) loose connection (d) impulse voltage

Last Answer : (d) impulse voltage

Description : For cost and safety, the outdoor substations are installed for voltages above (a) 11 kV (b) 33 kV (c) 60kV (d) 110kV

Last Answer : (b) 33 kV

Description : Bus coupler is very essential in arrangement (a) single bus (b) double bus, double breaker (c) main and transfer bus (d) all of the above

Last Answer : (c) main and transfer bus