How Do You Calibrate A D. P. Transmitter?

1 Answer

Answer :

The following steps are to be taken which claribrating :
1. Adjust zero of the Xmtrs.
2. Static preasure test: Give equal pressure on both sides of the transmitter. Zero
should not shift. If it is shifting carry out static alignment.
3. Vaccum test: Apply equal vaccum to both the sides. The zero should not shift.
Calibration Procedure:
 Give 20 psi air supply to the transmitter.
 Vent the L.P. side to atmosphere.
 Connect output of the Instrument to a standard test gauge. Adjust zero.
 Apply required pressure to high pressure side of the transmitter and adjust the span.
 Adjust zero again if necessary.

Related questions

Description : How Do You Do A Zero Check On A D.p. Transmitter?

Last Answer : Close one of the valve either H.P. or L.P. open the equalizing valve. The O/P should read zero.

Description : How Do You Carry Out Piping For A Different Pressure Flow Transmitter On Liquids, Gas And Steam Services? Why?

Last Answer : Liquid lines: On liquid lines the transmitter is mounted below the orifice plate. Since liquids have a property of self draining. Gas Service: On gas service the transmitter is mounted above the orifice ... mounted below the orifice plate with condenlate pots. The pots should be at the same level.

Description : How Will You Vent Air In The D.p. Cell? What If Seal Pots Are Used?

Last Answer : 1. Air is vented by opening the vent plugs on a liquid service transmitter. 2. On services where seal pots are used isolate the primary isolation valves and open the vent valves. Fill the line from the transmitter drain plug with a pump.

Description : How Do You Identify The H. P. Side Or Inlet Of An Orifice Plate In Line?

Last Answer : The marking is always done H. P. side of the orifice tab which gives an indication of the H.P.side.

Description : Why Is Flow Measured In Square Root?

Last Answer :  Flow varies directly as the square root of different pressure F = K square root of ΔP.  Since this flow varies as the square root of differential pressure the pen does not directly indicate flow.  The flow can be determined by taking the square root of the pen. Say the pen reads 50% of chart.

Description : How Do You Calculate New Factor From New Range Using Old Factor And Old Range?

Last Answer : New Factor = _!New Range Old Factor = _IOld Range Flow = K_!Range Q = Factor X Unit Flow New Factor = Old Factor I _IOld Range X _/New Range.

Description : How Would You Do Glycol Filling Or Fill Seal Liquids In Seal Pots 7 Draw And Explain?

Last Answer : The procedure for glycol filling is : 1. Close the primary isolation valves. 2. Open the vent on the seal pots. 3. Drain the use glycol if present. 4. Connect a hand pump on L.P. side while ... 9. Close the seal pot vent valves. 10. Close equalizer valve. 11. Open both the primary isolation valves.

Description : An Operator Tells You That Flow Indication Is More? How Would You Start Checking?

Last Answer : 1. First flushing the transmitter. Flush both the impulse lines. Adjust the zero by equalizing if necessary. If still the indication is more then. 2. Check L.P. side for choke. If that is clean then. 3. Check the leaks on L.P. side. If not. 4. Calibrate the transmitter.

Description : What Is The Seal Liquid Used For Filling Impulse Lines On Crude And Viscous Liquid?

Last Answer : Glycol.

Description : What Is Bernoulli’s Theoram And Where It Is Applicable?

Last Answer : Bernoulli’s theoram states the “total energy of a liquid flowing from one point to another remains constant.” It is applicable for non compressible liquids.

Description : Why Is The Orifice Tab Provided?

Last Answer : The orifice tab is provided due to the following reasons: 1. Indication of an orifice plate in a line. 2. The orifice diameter is marked on it. 3. The material of the orifice plate. 4. The tag no. of the orifice plate. 5. The mark the inlet of an orifice.

Description : How Do You Identify An Orifice In The Pipe Line?

Last Answer : An orifice tab is welded on the orifice plate which extends our of the line giving an indication of the orifice plate.

Description : What Are The Different Types Of Orifice Plates And State Their Uses?

Last Answer : The different types of orifice plates are: 1. Concentric. 2. Segmental. 3. Eccentric. CONCENTRIC: The concentric orifice plate is used for ideal liquid as well as gases and steam service. This orifice ... hole in the form segment of a circle. This is used for colloidal and sherry flow measurement.

Description : What Are The Primary Elements Usedfor Flow Measurement?

Last Answer : The primary elements used for flow measurement are: 1. Orifice Plate. 2. Venturi tube. 3. Pitot tube. 4. Annubars. 5. Flow Nozzle. 6. Weir & Flumes.

Description : Define All The Process Variable And State Their Unit Of Measurement?

Last Answer : 1. FLOW: Kg I hr, Litter I min, Gallon I min. M3 I NM3 I HR. (GASES) 2. PRESSURE: Force acting per unit Area. P = F/A Units: Bar I Pascals I Kg I CM I, Pounds 3. LEVEL: ... Degree Farenheit, Degree Kelvin, Degree Rankin. 5. QUALITY: It deals with analysis PH, % C02, % 02, Conductivity, Viscosity.

Description : What Are The Process Variable?

Last Answer : The process Variable are: 1. Flow 2. Pressure 3. Temperature 4. Level 5. Quality i. e. % D2, C02, PH etc.

Description : How do you calibrate a D. P. transmitter?

Last Answer : The following steps are to be taken which calibrating: 1. Adjust zero of the Tx'r. 2. Static pressure test : Give equal pressure on both sides of the transmitter. Zero should not shift. If ... pressure to high pressure side of the transmitter and adjust the span. 6. Adjust zero again if necessary.

Description : How will you calibrate an absolute pressure transmitter using vacuum manometer. Range 0-400mm abs ?

Last Answer : The procedure for calibration is as follows : Connect air supply to the transmitter. Connect a test gauge of 0-1.4 Kg/cm2 to the output. Connect Vacuum pump with tee off to the manometer. Apply 760 ... nearest ) and adjust zero. Apply 360 mm Vacuum adjust span. ( 760 - 360 = 400 mm abs. )

Description : The iPhone's M7 processor (specifically its step counting): any way at all to calibrate it?

Last Answer : I can't answer this, but if it were me I'd ask the question on the London Hackspace mailing list here: https://groups.google.com/forum/#!forum/london-hack-space . They've got a festival ... answers for the next week and a half, but certainly someone will have some decent input during normal times.

Description : What is the best way to calibrate your monitor for a web designer?

Last Answer : I’m struggling with this one too. This page has some advice.

Description : Can I calibrate my Macbooks screen?

Last Answer : You calibrate a notebook the same way you calibrate a desktop. I haven't calibrated my macbook, but I know others who have used my old photography professor's spyder. He used to calibrate the desktops in the ... if you happened to be about with your laptop he'd do that for, you, too - same process.

Description : How to calibrate pH meter ?

Last Answer : The pH meter is calibrated to accurately measure pH . Three standard buffers ( 7, 4, 10) are used for this purpose. First the pH prov has to be cleaned with distilled water. The pH meter ... . This is how the pH meter is calibrated with the help of buffer solution and prepared for reading.

Description : How to Calibrate and Use a pH Meter?

Last Answer : A pH meter is normally something that an environmentalist or chemist would use, but some gardeners also make use of it. This meter is used to measure the acidity and alkalinity of a specific liquid. pH ... , you should rinse it off with distilled water. To help calibrate it, it will be placed int

Description : How can I calibrate a ph meter?

Last Answer : The proper method of calibrating a pH Meter requires distilled water. As the water is pure you should read 7 or neutral when you read it's pH. If you don't then you need to adjust it until you do.

Description : How do I calibrate a frequency converter?

Last Answer : There are several frequency calibration converter and repair stores. The steps are complicated and you can find several sites that offer step by step directions.

Description : Before using an all-purpose electric measuring instrument (multimeter) utilizing internal batteries to supply power for resistance measurements, you should FIRST ____________. A. remove one of the ... batteries C. calibrate using a known external resistance D. select the proper resistance range

Last Answer : Answer: D

Description : When using a multimeter for resistance measurements, it should be calibrated by clipping the loose ends of the leads together and _____________. A. setting the instrument pointer at 'zero' ohms B. ... the plus and minus terminals D. using a special purpose resistance measuring instrument (a bridge)

Last Answer : Answer: A

Description : If the approximate voltage to be measured in a circuit is not known, you should _____________. A. use the lowest voltage range on the voltmeter B. connect the meter in series with the circuit C. only have to calibrate the meter before using it D. use the highest voltage range on the voltmeter

Last Answer : Answer: D

Description : Before measuring an unknown resistance with an ohmmeter, you should _____________. A. adjust the meter's pointers to mid-scale B. change the meter's batteries C. center the meter's pointer at infinity D. short the test leads and calibrate the meter

Last Answer : Answer: D

Description : Before measuring an unknown resistance with an ohmmeter, you should _____________. A. adjust the meter's pointer to mid-scale B. short the test leads and calibrate the meter reading to 'zero' C. change the meter's batteries D. center the meter's pointer at infinity

Last Answer : Answer: B

Description : To properly use a hook-on-type volt/ammeter to check current flow, you must FIRST _____________. A. de-energize the circuit to allow connection of the instrument in series B. hook the jaws ... test leads to the appropriate terminals D. short the test leads and calibrate the instrument to zero

Last Answer : Answer: B

Description : How Can We Calibrate A Positioner?

Last Answer : A positioner is a device put into a valve to ensure that it is at a correct position of opening as per the control signal. An I/P converter only sends the opening/closing request to valve ... is used in a valve when valve operating signal range is different from I/P converter output range.

Description : How will you calibrate a temp. recorder using a potentiometer ?

Last Answer : Connect the potentiometer output to the input of temp. recorder. 1. Connect the ( +ve ) to the ( +ve ) and ( -ve ) to the ( -ve ). 2. If ambient compensation is provided ... ambient temp. millvolts to the corr. input millvolts measured. Find out from the chart for the corresponding temperature. 

Description : How will you calibrate a leveltrol in the field ?

Last Answer : Calculation # 1 If the calibrating liquid is water: Process Liquid Density / 1* Displacer height = mm of H2O. Calculation # 2 If the calibrating liquid is Other liquid: Process Liquid Density / ... gravity or span adjustment ( Electronic Level ). 6. Fill it up to 50 %, check linearity.  

Description : How to Calibrate a Scale

Last Answer : How to Calibrate a Scale Weighing scales are used for various tasks, but for it to be kept in top working condition, calibrating it on a regular basis is very important. Most scales usually come with ... accurate all the time. As long as you stick to these steps, calibrating them will be very easy.

Description : need of calibration and explain the procedure to calibrate the instrument.

Last Answer : Need of calibration: Every measuring device degrades over time due to normal wear and tear. These changes can be caused by various reasons such as electric or mechanical shock or a hazardous manufacturing ... different magnitude are used to calculate the resistance based on ohm's law.

Description : Do You Know How D.p. Transmitter Can Be Applied To Close Tank?

Last Answer : In closed tank, bottom of the tank is connected to the high pressure side of the transmitter. Top of tank is connected to the lower pressure side of the transmitter. In this way vessel pressure can be measured.

Description : Explain How D.p. Transmitter Can Be Applied To Open Tank?

Last Answer : In open tank the lower pressure side is vented to the atmosphere. All pressure is applied to the high pressure side. This vessel pressure is measured through high pressure side.

Description : Explain How Can A D.p. Transmitter Be Calibrated?

Last Answer : D.P. transmitter can be calibrated using following steps: 1. Adjust zero of Xmtrs. 2. Perform static pressure test: Give equal pressure on both sides of transmitter. Zero should not shift either ... Apply required pressure to the high pressure side and adjust the span. Adjust zero gain if necessary.

Description : How D.p. Transmitter Can Be Applied To Open Tank?

Last Answer : In open tank the lower pressure side is vented to the atmosphere. All pressure is applied to the high pressure side. This vessel pressure is measured through high pressure side.

Description : How D.p. Transmitter Can Be Applied To Close Tank?

Last Answer : In closed tank, bottom of the tank is connected to the high pressure side of the transmitter. Top of tank is connected to the lower pressure side of the transmitter. In this way vessel pressure can be measured.

Description : How Can A D.p. Transmitter Be Calibrated?

Last Answer : D.P. transmitter can be calibrated using following steps: 1. Adjust zero of Transmitter. 2. Perform static pressure test: Give equal pressure on both sides of transmitter. Zero should not ... Apply required pressure to the high pressure side and adjust the span. Adjust zero gain if necessary.

Description : Why are two plugs provided on a D.P transmitter? 

Last Answer : 1.The top plug is a vent plug for venting the air entrapped inside the cell. 2.The bottom plug is a drain plug for draining the liquid accumulated inside the cell.  

Description : How will you check zero of a level D.P. transmitter while is line ? 

Last Answer : ١. Close both the isolation valves. ٢. Open the vent valve on L.P. leg and H.P. leg drain. ٣. Check and adjust zero if necessary. 

Description : How will you commission D.P. transmitter in field in pressurized vessel.

Last Answer : ١. Close both the isolation valves, Vent the H.P. side. ٢. Fill it with the sealing liquid. ٣. Open the L.P. side vent valve. ٤. Adjust zero with suppression spring. ٥. Close the L.P. side vent valve. ٦. Open both the isolation valves.  

Description : How is D.P. transmitter applied to a close tank ?

Last Answer : In close tank the bottom of the tank is connected to the high pressure side of the transmitter and top of the tank in connected to L.P. side of the transmitter. In this way the vessel pressure is balanced.

Description : How do you do a zero check on a D.P. transmitter ?

Last Answer : Close one of the valve either H.P. or L.P. open the equalizing valve. The O/P should read zero.