What happens if excitation of alternator is changed keeping speed of prime mover constant?

1 Answer

Answer :

The emf induced will be changed and hence terminal voltage will also change. The terminal voltage will increase with increase in excitation and vise versa.

Related questions

Description : What happens if speed of prime mover is changed keeping excitation of alternator constant?

Last Answer : If speed of prime mover is changed, the speed of alternator also changes hence frequency also changes. The frequency increase with increase in steam input and hence speed and vise versa.

Description : How does increase in excitation of the Alternator connected to infinite bus-bars affect this operation?

Last Answer : Increase in excitation level of the synchronous generator will effectively increase the reactive power supplied by the generator keeping steam input constant.

Description : The standard method of controlling the output voltage of a 440 volt, 60 Hz, AC generator is accomplished by adjusting the ____________. A. prime mover speed droop B. number of poles C. alternator field excitation D. load on the alternator

Last Answer : Answer: C

Description : What are the prime movers used for a) Salient pole alternator, b) Non- salient pole alternator.

Last Answer : The prime movers used for salient pole alternators are water wheels likeKaplan turbine, Francis turbine, Pelton wheel etc., and diesel or petrol engines. The prime movers used for non-salient pole alternators are steam turbines and gas turbines.

Description : Discuss how the ventilation and cooling of large high speed alternator is carried out.

Last Answer : For high speed alternator two cooling methods are available and they are conventional cooling and direct cooling. In conventional cooling methods, radial and axial ventilating ducts are provided in the ... oil or hydrogen are circulated in the ducts to remove the heat directly from the conductors.

Description : As load is added to an AC generator provided with constant field excitation, the prime mover slows down with the effect of ____________. A. lowering frequency and lowering generated ... C. increasing frequency and lowering generated voltage D. lowering frequency and increasing generated voltage

Last Answer : Answer: A

Description : How does increase in steam input of the Alternator connected to infinite bus-bars affect this operation?

Last Answer : KW output power of alternator increase with increase in steam input keeping excitation constant.

Description : What steps are to be taken before disconnecting one Alternator from parallel operation?

Last Answer : The following steps are to be taken before disconnecting one Alternator from parallel operation · The prime-mover input of the outgoing generator has to be decreased and that of other generators ... delivered by the outgoing generator is zero, it has to be disconnected from parallel operation.

Description : What are the test data required for predetermining the voltage regulation of an Alternator by MMF method?

Last Answer : Data required for MMF method are : · Effective resistance per phase of the 3-phase winding R · Open circuit characteristic (OCC) at rated speed/frequency · Short circuit characteristic (SCC) at rated speed/frequency

Description : What are the advantages and disadvantages of estimating the voltage regulation of an Alternator by EMF method?

Last Answer : Advantages: · Simple no load tests (for obtaining OCC and SCC) are to be conducted · Calculation procedure is much simpler Disadvantages: · The value of voltage regulation obtained by this method is always higher than the actual value

Description : Name the various methods for predetermining the voltage regulation of 3-phase Alternator.

Last Answer : The following are the three methods which are used to predetermine the voltage regulation of smooth cylindrical type Alternators · Synchronous impedance / EMF method · Ampere-turn / MMF method · Potier / ZPF method

Description : Define the term voltage regulation of Alternator.

Last Answer : The voltage regulation of an Alternator is defined as the change in terminal voltage from no-load to load condition expressed as a fraction or percentage of terminal voltage at load condition ; the speed and excitation conditions remaining same.

Description : An Alternator is found to have its terminal voltage on load condition more than that on no load. What is the nature of the load connected?

Last Answer : The nature of the load is of leading power factor , load consisting of resistance and capacitive reactance.

Description : What is meant by load angle of an Alternator?

Last Answer : The phase angle introduced between the induced emf phasor, E and terminal voltage phasor , U during the load condition of an Alternator is called load angle.

Description : What is meant by synchronous impedance of an Alternator?

Last Answer : The combination of armature resistance and synchronous reactance is known as synchronous impedance

Description : Explain armature reaction of an alternator and its effect on main flux at various power factor.

Last Answer : 1. zero lagging pf: armature flux lags main flux by 180 . Hence effect is demagnetizing i.e the main flux is reduced 2. lagging pf: it has 2 components demagnetizing and cross magnetizing ... 5. zero leading pf: Armature flux is in phase with main flux. Effect is completely magnetizing.

Description : Which type of winding is preferred for armature windings of alternator? Why?

Last Answer : Double layer, short pitched and distributed type of armature winding. It eliminates high frequency harmonics hence it makes induced emf more sinusoidal.

Description : Why is the stator core of Alternator laminated?

Last Answer : The stator core of Alternator is laminated to reduce eddy current loss.

Description : State three important features of turbo alternator rotors.

Last Answer : 1. The rotors of turbo alternators have large axial length and small diameters. 2. Damping torque is provided by the rotor itself and so there is no necessity for additional damper winding. 3. They are suitable for high speed operations and so number of poles is usually 2 or 4.

Description : Why Alternator is called Synchronous generator?

Last Answer : Because it rotates at a constant (i.e.synchronous speed ) no matter what the load on alternator is.For instance if its a 2 pole machine it will rotate at 3000 rpm to produce a frequency of 50 Hz in India.

Description : Why AC generator is called Alternator?

Last Answer : An alternator is such a machine which produces alternation electricity. It is a kind of generator which converts mechanical energy into alternating electrical energy.

Description : The voltage developed by an AC generator is controlled by varying the ____________. A. speed of the prime mover B. AC excitation to the field C. DC excitation to the field D. DC excitation of the voltage regulator

Last Answer : Answer: C

Description : Automatic voltage regulators provided on switchboards function to _____________. A. regulate the AC load on the generator B. protect the switchboard from high voltage C. govern prime mover speed to control voltage D. vary the field excitation to the generators

Last Answer : Answer: D

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : To increase the frequency of an operating AC generator, you should ____________. A. increase the field excitation B. decrease the field excitation C. increase the number of magnetic poles D. increase the speed of the prime mover

Last Answer : Answer: D

Description : In the illustration, the signal from the device connected to terminals 18 and 19 is __________. EL-0046 A. prime mover speed feedback B. loss of control alarm when comparing with the input signal ... slip between the prime mover and the alternator D. to shut down the prime mover if overspeeding

Last Answer : Answer: A

Description : The output voltage of a 440 volt, 60 Hz AC generator is controlled by the ______________. A. load on the alternator B. load on the prime mover C. speed of the prime mover D. exciter output voltage

Last Answer : Answer: D

Description : The output voltage of a 440 volt, 60 hertz, AC generator is controlled by the _____________. A. prime mover speed B. exciter output voltage C. load on the alternator D. number of poles

Last Answer : Answer: B

Description : Kilowatt load is divided between two AC generators operating in parallel by _____________. A. adjusting the governor controls B. varying the excitation voltage C. increasing both prime mover speeds simultaneously D. decreasing both prime mover speeds simultaneously

Last Answer : Answer: A

Description : What happens in all dark lamp method ?

Last Answer : If frequency and phase difference of incoming alternator and busbar are not same then lamps connected across incoming alternator will flicker. The flickering decreases as frequency will become near to each other by adjusting the speed by prime mover.

Description : If the energy input is significantly reduced to the prime mover of one shipboard alternator operating in parallel with others, that alternator will _____________. A. continue to operate at no load B. lose ... overspeed C. begin to motorize and then trip out D. slow down and operate at reduced load

Last Answer : Answer: C

Description : The frequency of an AC generator is adjusted by means of the ____________. A. main alternator field rheostat B. exciter field rheostat C. prime mover governor control D. equalizing reactor

Last Answer : Answer: C

Description : While keeping the excitation constant, if the steam supply of an alternator running in parallel with another identical alternator is increased, then (A) It would over-run the other alternator (B) Its rotor ... (C) Its portion of share in load will increase (D) Its power factor would be decreased.

Last Answer : While keeping the excitation constant, if the steam supply of an alternator running in parallel with another identical alternator is increased, then Its portion of share in load will increase

Description : Why a 3-phase synchronous machine will always run at synchronous speed?

Last Answer : Because of the magnetic coupling between the stator poles and rotor poles the motor runs exactly at synchronous speed.

Description : What type of prime mover requires a specially designed high-speed alternator?

Last Answer : Steam turbine.

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : In the illustrated electronic governor, the circuit card connected to the potential and current transformers is for ________. EL-0046 A. increasing the signal strength to the governor to ... from motorization D. conditioning the load through the use of a magnetic amplifier current transformer

Last Answer : Answer: A

Description : If air gap readings for an electical generating machine have changed significantly from the last reading, you should check _________. A. the bearings B. insulation readings and machine cleanliness C. the prime mover thrust bearing D. the field coil bolts for the proper torque values

Last Answer : Answer: A

Description : RC time constant characteristics, as shown in the illustration, are important in _____________. EL-0086 A. bridge rectifiers for alternator excitation B. timing and pulse shaping circuits C. transistor power amplifier biasing D. motor controller overload protection

Last Answer : Answer: B

Description : List the factors that affect the load sharing in parallel operating generators?

Last Answer : The total active and reactive power delivered to the load, connected across the common bus-bars, are shared among Synchronous generators, operating in parallel, based on the following three factors ... characteristic/input · Excitation level and · Percentage synchronous impedance and its R/X ratio

Description : Why synchroscope method is more better compared to others?

Last Answer : It is very accurate as it doesnot require personal judgement

Description : How synchronoscope is used for synchronizing Alternators?

Last Answer : Synchronoscope can be used for permanently connected Alternators where the correctness of phase sequence is already checked by other means. The rotation of pointer is proportional to the difference in ... alternator is running slow. If the difference in frequency is large the pointer will oscillate

Description : What is a synchroscope?

Last Answer : Synchroscope is an instrument, which shows the phase relationship of emf of the incoming alternator. It also indicates whether the incoming alternator is running slow or fast.

Description : What are the advantages and disadvantages of three dark lamps method of synchronizing?

Last Answer : Advantages: · The synchronous switch using lamps is inexpensive · Checking for correctness of the phase sequence can be obtained in a simple manner which is essential especially when the Alternator ... The frequency of the incoming Alternator in relation to the bus-bar frequency is not available.

Description : What is synchronizing?

Last Answer : The operation of connecting an alternator in parallel with another alternator or with common bus bars is known as synchronizing.

Description : What are the methods of checking the phase difference?

Last Answer : 1. All Dark lamp method 2. Two bright one dark lamp method 3. Synchroscope

Description : What is meant by infinite bus-bars?

Last Answer : The source or supply lines with non-variable voltage and frequency are called infinite bus-bars. The source lines are said to have zero source impedance and infinite rotational inertia.

Description : State the condition to be satisfied before connecting two alternators in parallel

Last Answer : The following are the three conditions to be satisfied by synchronizing the additional Alternator with the existing one or the common bus-bars. · The terminal voltage magnitude of the incoming ... incoming Alternator voltage must be the same as the bus-bar voltage. . Zero phase difference