Kilowatt load is divided between two AC generators operating in parallel by _____________. A. adjusting the governor controls  B. varying the excitation voltage C. increasing both prime mover speeds simultaneously D. decreasing both prime mover speeds simultaneously

1 Answer

Answer :

Answer: A

Related questions

Description : The division of the kilowatt load between two AC generators operating in parallel is controlled by the settings and characteristics of the _____________. A. voltage regulators B. field rheostats C. reverse power relays D. prime mover governors

Last Answer : Answer: D

Description : If two AC generators have just been placed in parallel, the true power load is initially distributed evenly by _____________. A. a balance coil B. changing field excitation C. adjusting the governor control settings D. a rheostat

Last Answer : Answer: C

Description : Automatic voltage regulators provided on switchboards function to _____________. A. regulate the AC load on the generator B. protect the switchboard from high voltage C. govern prime mover speed to control voltage D. vary the field excitation to the generators

Last Answer : Answer: D

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : The standard method of controlling the output voltage of a 440 volt, 60 Hz, AC generator is accomplished by adjusting the ____________. A. prime mover speed droop B. number of poles C. alternator field excitation D. load on the alternator

Last Answer : Answer: C

Description : As load is added to an AC generator provided with constant field excitation, the prime mover slows down with the effect of ____________. A. lowering frequency and lowering generated ... C. increasing frequency and lowering generated voltage D. lowering frequency and increasing generated voltage

Last Answer : Answer: A

Description : The voltage of an operating AC turbogenerator is raised or lowered by adjusting the _____________. A. exciter generator governor controls B. synchronizing switch C. phase sequence switch D. generator field exciter

Last Answer : Answer: D

Description : The voltage developed by an AC generator is controlled by varying the ____________. A. speed of the prime mover B. AC excitation to the field C. DC excitation to the field D. DC excitation of the voltage regulator

Last Answer : Answer: C

Description : In the illustrated electronic governor, the circuit card connected to the potential and current transformers is for ________. EL-0046 A. increasing the signal strength to the governor to ... from motorization D. conditioning the load through the use of a magnetic amplifier current transformer

Last Answer : Answer: A

Description : Equalization of the power factors of two alternators operating in parallel is accomplished _____________. A. manually, by adjusting the governor controls B. automatically, by automatic voltage regulators ... the output of current transformers D. automatically, by the designed action of the governors

Last Answer : Answer: B

Description : A change in field excitation of an alternator operating in parallel will cause a change in its _____________. A. alternator frequency B. kilowatt load C. voltage output D. all of the above

Last Answer : Answer: C

Description : The KW load is evenly distributed between two alternators just placed in parallel by adjusting _____________. A. a balance coil B. the governor settings C. the field excitation D. a rheostat

Last Answer : Answer: B

Description : The voltage output of an AC generator is accurately controlled by _____________. A. changing the sensitivity of the prime mover to large changes in voltage B. varying the reluctance of the air gap C. varying the DC exciter voltage D. shorting out part of the armature windings

Last Answer : Answer: C

Description : Two AC generators of the same capacity are operating in parallel. One with a zero speed droop setting and the other with a 5% speed droop. If its capacity is not exceeded, the unit whose ... B. maintain the frequency of the system C. have poor sensitivity characteristics D. have poor power response

Last Answer : Answer: B

Description : If the excitation is increased to one of two alternators operating in parallel, the _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. kilowatt load will be greatly increased D. ampere load will be greatly decreased

Last Answer : Answer: A

Description : If the excitation of an alternator operating in parallel is decreased below normal, its _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. ampere load will be greatly increased D. kilowatt load will be greatly decreased

Last Answer : Answer: B

Description : To equalize the power factor of two alternators operating in parallel, the ____________. A. field excitation of both units is adjusted B. governors of both units are adjusted C. phase sequence is altered D. kilowatt load is evenly divided

Last Answer : Answer: A

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : A constant output voltage from an AC generator is maintained by the _____________. A. prime mover governor B. exciter generator C. voltage regulator D. reverse power relay

Last Answer : Answer: C

Description : The division of the reactive KVA load between paralleled AC generators is initiated by the ______________. A. prime mover governors B. voltage regulators C. phase balance relay D. proportioner

Last Answer : Answer: B

Description : In an AC synchronous motor electric propulsion plant, propeller speed is controlled by varying the _____________. A. prime mover speed B. electric coupling field strength C. number of energized main motor poles D. propulsion generator field strength

Last Answer : Answer: A

Description : To increase the frequency of an operating AC generator, you should ____________. A. increase the field excitation B. decrease the field excitation C. increase the number of magnetic poles D. increase the speed of the prime mover

Last Answer : Answer: D

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : The frequency of voltage generated, in case of generators, can be increased by (a) using reactors (b) increasing the load (c) adjusting the governor (d) reducing the terminal voltage (e) none of the above

Last Answer : (c) adjusting the governor

Description : If the energy input is significantly reduced to the prime mover of one shipboard alternator operating in parallel with others, that alternator will _____________. A. continue to operate at no load B. lose ... overspeed C. begin to motorize and then trip out D. slow down and operate at reduced load

Last Answer : Answer: C

Description : AC and DC generators are similar in that they _____________. A. both generate alternating voltages B. both rectify the voltage before delivery C. are constructed at the same physical size for the same kilowatt rating D. both supply three-phase power

Last Answer : Answer: A

Description : The output voltage of a 440 volt, 60 hertz, AC generator is controlled by the _____________. A. prime mover speed B. exciter output voltage C. load on the alternator D. number of poles

Last Answer : Answer: B

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : Why is it desirable to operate paralleled AC generators at the same power factor? A. Circulating currents are kept to a minimum. B. Field excitation losses are kept to a minimum. C. Generator ... will have a lesser tendency to hunt. D. Because a power factor increase will decrease kilowatt output.

Last Answer : Answer: A

Description : If field excitation is suddenly lost to an alternator operating in parallel, that alternator will _____________. A. supply excessive current to the bus B. operate at the same load, but with reduced voltage C. lose its load and tend to overspeed D. become overloaded and slow down

Last Answer : Answer: C

Description : The kilowatt load can be adjusted on a paralleled generator by using the _____________. A. field rheostat B. governor control C. automatic voltage regulators D. hand tachometer

Last Answer : Answer: B

Description : On some diesel-electric ships, the DC propulsion motor will only attain half speed when the generator fields are fully excited. Speeds above this are obtained by _____________. A. rotating brush ... B. raising the generator engine speed C. lowering the generator engine speed D. decreasing excitation

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : Which is a function of the voltage regulators used with AC generators? A. To cut out generators when they are no longer required. B. To cut in additional generators automatically as ... between generators operating in parallel. D. To divide reactive current between generators operating in parallel.

Last Answer : Answer: D

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation of the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. type of alternator

Last Answer : Answer: B

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation to the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. number of field poles per alternator

Last Answer : Answer: B

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : The output voltage of a 440 volt, 60 Hz AC generator is controlled by the ______________. A. load on the alternator B. load on the prime mover C. speed of the prime mover D. exciter output voltage

Last Answer : Answer: D

Description : On electrical generators one of the bearings is isolated from the bedplate. This insulating block should not be painted and must be kept clean to ___________. A. protect operating personnel from shock ... the prime mover as it warms up D. eliminate shaft currents to prevent damaging the bearings

Last Answer : Answer: D

Description : After closing the circuit breaker to place two similar alternators in parallel, the NEXT step is to balance the _____________. A. power factor B. voltage load C. kilowatt load D. ampere load

Last Answer : Answer: C

Description : The frequency of an AC generator is adjusted by means of the ____________. A. main alternator field rheostat B. exciter field rheostat C. prime mover governor control D. equalizing reactor

Last Answer : Answer: C

Description : The load sharing characteristics of two diesel generators operating in parallel are mostly dependent on their governor ____________. A. load limit settings B. idle speed settings C. speed limit settings D. speed droop settings

Last Answer : Answer: D

Description : The frequency of an alternator is controlled from the main switchboard by adjusting the _____________. A. frequency meter B. voltage regulator C. governor control D. sychroscope switch

Last Answer : Answer: C

Description : When two generators are on the line and are sharing the load equally, they are said to be operating in _____________. A. frequency B. series C. parallel D. resonance

Last Answer : Answer: C

Description : In a diesel electric plant, raising the generator's field excitation will cause the DC propulsion motor to ________. A. increase in speed B. decrease in speed C. affect generator speed only D. affect main motor speed if done in conjunction with higher generator engine speeds

Last Answer : Answer: A

Description : What happens if speed of prime mover is changed keeping excitation of alternator constant?

Last Answer : If speed of prime mover is changed, the speed of alternator also changes hence frequency also changes. The frequency increase with increase in steam input and hence speed and vise versa.

Description : What happens if excitation of alternator is changed keeping speed of prime mover constant?

Last Answer : The emf induced will be changed and hence terminal voltage will also change. The terminal voltage will increase with increase in excitation and vise versa.