In order to safely carry out repairs to a generator circuit breaker, it must be isolated from the bus. This is accomplished by opening the _____________. A. reverse power relay B. bus disconnect link C. generator bus fuse connections D. power directional relay

1 Answer

Answer :

Answer: B

Related questions

Description : A bus disconnect link is used to isolate _____________. A. one bus bar from another B. the generator circuit breaker from the bus C. different phases from the equalizer connection D. positive and negative buses from the neutral

Last Answer : Answer: B

Description : A shore power circuit breaker should be closed only _____________. A. when the ship's generators have been directly paralleled to those on shore B. in a shipyard C. if a quick disconnect coupling is used D. when the ship's generators have been removed from the bus

Last Answer : Answer: D

Description : The schematic diagram shown in the illustration uses symbol 'A' to represent a/an _________. EL-0011 A. non-renewable fuse link B. circuit breaker coil C. overload relay coil D. thermal overload heater

Last Answer : Answer: D

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : In an emergency, the fastest way to interrupt power and stop the winch shown in the illustration is for the ____________. EL-0102 A. mate to open the disconnect switch at 'L1' and 'L2' B. ... watch engineer to open the winch circuit breaker D. electrician to open the test link at the controller

Last Answer : Answer: B

Description : A circuit breaker differs from a fuse in that a circuit breaker _____________. A. melts and must be replaced B. is enclosed in a tube of insulating material with metal ferrules at each end C. gives no visual indication of having opened the circuit D. trips to break the circuit and may be reset

Last Answer : Answer: D

Description : The timer element found in a reverse power relay obtains its operating torque via _____________. A. line voltage B. the main bus C. electromagnets D. a separate battery source

Last Answer : Answer: C

Description : The timer element of a reverse power relay cannot be energized unless _____________. A. the power flow is the same as the tripping direction B. the power flow is the opposite to the tripping direction C. the movement of the disk is damped by a permanent magnet D. one generator is motorized

Last Answer : Answer: A

Description : The timer element of a reverse power relay cannot be energized unless _____________. A. one generator is fully motorized B. the movement of the disk is damped by a permanent magnet C. the power flow is the same as the tripping direction D. the power flow is the opposite to the tripping direction

Last Answer : Answer: C

Description : A generator is prevented from becoming motorized by the use of a/an _____________. A. overspeed trip B. reverse power relay C. back pressure trip D. governor controls

Last Answer : Answer: B

Description : A constant output voltage from an AC generator is maintained by the _____________. A. prime mover governor B. exciter generator C. voltage regulator D. reverse power relay

Last Answer : Answer: C

Description : The part of the shipboard electrical system used to control the distribution of power to the branch circuits, is the _____________. A. bridge control panel B. disconnect links C. governor relay box D. main switchboard

Last Answer : Answer: D

Description : The purpose of a main switchboard circuit breaker's reverse-power trip is to _____________. A. prevent main circuit overload B. protect the circuit breaker blowout coil C. prevent alternator motorization D. prevent low voltage tripout

Last Answer : Answer: C

Description : A circuit breaker and a fuse have a basic similarity in that they both _____________. A. can be reset to energize the circuit B. should open the circuit when overloaded C. will burn out when an over current flow develops D. all of the above

Last Answer : Answer: B

Description : If an electric motor fails to start, you should FIRST check the _____________. A. phase sequence B. ampere load C. fuse or circuit breaker D. line frequency

Last Answer : Answer: C

Description : When paralleling two AC generators, the synchroscope selector switch and frequency meter switch should be set up to sense the frequency of the _____________. A. bus B. generator on the line C. oncoming generator D. bus transfer relay

Last Answer : Answer: C

Description : In the illustration, if one of the devices labeled 'TURB' should fail the ___________. EL-0003 A. device labeled 'EXC' will drive the alternator B. device labeled 'BKR' for that ... -alternator D. emergency generator should automatically start and be placed on line to supply emergency load centers

Last Answer : Answer: B

Description : The purpose of the reverse power relay, provided on a ship's service alternator panel, is to trip the circuit in the event of ______________. A. main circuit overload B. high power transfer C. generator overspeeding D. alternator motorization

Last Answer : Answer: D

Description : The conversion of the throttle command voltage to the signal necessary to achieve the desired shaft RPM is accomplished by the _____________. A. ahead or astern function generator of the ... circuit C. operational amplifiers in the autorotation circuit D. long time constant amplifier circuit

Last Answer : Answer: A

Description : When using a megohmmeter to determine which shunt field coil is grounded in a DC machine, you must ____________. A. insulate the field frame from the ship's hull B. disconnect each shunt ... C. use a motor driven high capacity megohmmeter D. remove all main line lead connections before testing

Last Answer : Answer: B

Description : In order to prevent the winch shown in the illustration from turning while troubleshooting the controller circuit, _________________. EL-0102 A. set the dynamic brake by clamping contact 'DB' closed B. set the ... at 'B1' and 'B2' D. open the test link preventing current flow to the armature

Last Answer : Answer: D

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving fast in the clockwise direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... at any pointer position D. the same as the bus frequency but out of phase with it

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving in the fast direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... the same as the bus frequency and the circuit breaker may be closed at any pointer position

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer is revolving in the slow direction. This indicates that the frequency of the incoming machine is _____________. A. higher than ... same as the bus frequency, and the circuit breaker may be closed at any pointer position

Last Answer : Answer: B

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : Coast Guard Regulations (46 CFR) require that each alternating current generator arranged for parallel operation shall be provided with _____________. A. more than one means of excitation B. individual circuit fuses C. a high back-pressure trip D. a reverse-power trip

Last Answer : Answer: D

Description : To remove an alternator operating in parallel with another unit from the main electrical bus, you must FIRST _________. A. adjust the power factor on both units B. set the desired voltage on ... C. open the circuit breaker on the outgoing alternator D. remove the load from the outgoing alternator

Last Answer : Answer: D

Description : An alternator will fail to produce line voltage as a result of _____________. A. a closed circuit breaker B. oxidized slip rings C. improperly staggered brushes D. exciter generator failure

Last Answer : Answer: D

Description : When paralleling two AC generators, the frequency (cycles) of the incoming generator, just prior to closing the circuit breaker, should be _____________. A. slightly less than the frequency of the generator on ... C. slightly more than the frequency of the generator on the line D. all of the above

Last Answer : Answer: C

Description : Capacitors can be used in electric distribution systems to improve power factor. This is accomplished by seesawing energy between the capacitor and the _____________. A. generator B. inductive loads C. resistive loads D. all of the above

Last Answer : Answer: B

Description : 30°, 60° and 90° connections are made in a directional relay to render the relay (A) Sufficient torque under fault conditions (B) Zero torque under fault conditions (C) Current grading (D) Time grading

Last Answer : 30°, 60° and 90° connections are made in a directional relay to render the relay Sufficient torque under fault conditions

Description : In a logic circuit, the NOT gate function _____________. A. does not alter a logical input B. serves to amplify a given signal level C. must be accomplished with a common collector transistor arrangement D. reverses an input logic condition

Last Answer : Answer: D

Description : If reading AC current with the illustrated device and unsure of the range as a precaution , the first step should be to _________. EL-0047 A. secure power and test for voltage B. disconnect the ... resistance and use Ohm's law to calculate current D. unable to safely measure current with the device

Last Answer : Answer: A

Description : The operating torque of the upper induction disc-type element, or timer element, of an AC reverse power relay is obtained from ____________. A. the main bus B. a separate battery source C. line voltage D. electromagnets

Last Answer : Answer: D

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : When an alternator is to remain idle for even a few days _________________. A. lift the brushes and disconnect the pigtails B. insulate the collector rings with strips of cardboard C. energize the heater circuit D. open the equalizing bus disconnect switch

Last Answer : Answer: C

Description : Diesel generators #1 and #2 are operating in parallel at near full load capacity. Diesel generator #1 suddenly trips out mechanically due to low lube oil pressure. The reverse power relay functions ... all nonvital circuits. D. Secure alarms, reset reverse power relay, and restart #1 engine.

Last Answer : Answer: C

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : If you reverse both the field and the armature connections to a DC propulsion motor, _____________. A. the direction of motor rotation will change B. the brushes will become overheated C. a magnetic lock will occur in the motor D. the direction of motor rotation will remain the same

Last Answer : Answer: D

Description : Regarding an AC generator connected to the main electrical bus; as the electric load and power factor vary, a corresponding change is reflected in the generator armature reaction. These changes in ... . governor speed droop setting B. voltage regulator C. balance coil D. phase-balance relay

Last Answer : Answer: B

Description : A fuse will 'blow' if _____________. A. an electric motor is stopped suddenly by opening a switch B. the flow of current to the protection device is reversed C. the electrical current exceeds the rated value of the fuse D. unequal resistors are connected in parallel

Last Answer : Answer: C