A shore power circuit breaker should be closed only _____________. A. when the ship's generators have been directly paralleled to those on shore B. in a shipyard C. if a quick disconnect coupling is used D. when the ship's generators have been removed from the bus

1 Answer

Answer :

Answer: D

Related questions

Description : When shore power is being connected to a ship in dry dock, _____________. A. the ship's generators are paralleled with the shore power to provide continuous power B. proper phase sequence must be ... 450 volts must be supplied from the shore D. exactly 60 Hz must be provided by the terminal

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving fast in the clockwise direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... at any pointer position D. the same as the bus frequency but out of phase with it

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators, and the synchroscope pointer is revolving in the fast direction. This indicates that the frequency of the incoming machine is _____________. A. higher ... the same as the bus frequency and the circuit breaker may be closed at any pointer position

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer is revolving in the slow direction. This indicates that the frequency of the incoming machine is _____________. A. higher than ... same as the bus frequency, and the circuit breaker may be closed at any pointer position

Last Answer : Answer: B

Description : In order to safely carry out repairs to a generator circuit breaker, it must be isolated from the bus. This is accomplished by opening the _____________. A. reverse power relay B. bus disconnect link C. generator bus fuse connections D. power directional relay

Last Answer : Answer: B

Description : An alternator is being paralleled with one on the line. At the INSTANT the circuit breaker is closed, the frequency of the incoming alternator will normally _____________. A. increase B. not change C. decrease D. be exactly 60 hertz

Last Answer : Answer: C

Description : When two AC generators are being paralleled, the breaker should be closed with the synchroscope pointer rotating in the ____________. A. 'slow' direction, just before the 12 o'clock position B. 'fast' ... just before the 12 o'clock position D. 'slow' direction, just after the 12 o'clock position

Last Answer : Answer: C

Description : A bus disconnect link is used to isolate _____________. A. one bus bar from another B. the generator circuit breaker from the bus C. different phases from the equalizer connection D. positive and negative buses from the neutral

Last Answer : Answer: B

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0° prior to closing the circuit breaker. This indicates ___________. A. the frequency of ... be closed after breaker has been reset D. there is an existing cross current between generators

Last Answer : Answer: A

Description : You are attempting to parallel two AC generators and the synchroscope pointer stops at a position other than 0°. If you close the circuit breaker at this moment _____________. A. the incoming ... hazardous condition will be created by the incoming machine being at a higher frequency than the bus

Last Answer : Answer: C

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : An equalizing connection between two compound-wound DC generators when paralleled, serves to _____________. A. reverse the polarity of the incoming generator as the series field weakens B. automatically ... the series field of the incoming generator D. parallel the series fields of the generators

Last Answer : Answer: D

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : When paralleling two AC generators, the frequency (cycles) of the incoming generator, just prior to closing the circuit breaker, should be _____________. A. slightly less than the frequency of the generator on ... C. slightly more than the frequency of the generator on the line D. all of the above

Last Answer : Answer: C

Description : In an emergency, the fastest way to interrupt power and stop the winch shown in the illustration is for the ____________. EL-0102 A. mate to open the disconnect switch at 'L1' and 'L2' B. ... watch engineer to open the winch circuit breaker D. electrician to open the test link at the controller

Last Answer : Answer: B

Description : Transformers are used onboard ships with AC generators to _____________. A. change frequency B. increase power output to modulating frequency controllers C. decrease power output to modulating frequency ... D. permit higher voltage for electric motor operation and low voltage for lighting circuits

Last Answer : Answer: D

Description : Multiple grounds have developed and were initialy indicated by the grounddetecting system as one ground. The FIRST step in locating the grounds is to _____________. A. examine the main bus bars ... no longer indicates any grounds C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : Why is it desirable to operate paralleled AC generators at the same power factor? A. Circulating currents are kept to a minimum. B. Field excitation losses are kept to a minimum. C. Generator ... will have a lesser tendency to hunt. D. Because a power factor increase will decrease kilowatt output.

Last Answer : Answer: A

Description : An alternator will fail to produce line voltage as a result of _____________. A. a closed circuit breaker B. oxidized slip rings C. improperly staggered brushes D. exciter generator failure

Last Answer : Answer: D

Description : When the operating handle of a molded case circuit breaker is in the mid-position, it indicates the circuit breaker is _____________. A. in the 'opened' position B. in the 'closed' position C. tripped D. reset

Last Answer : Answer: C

Description : When paralleling two AC generators, the frequency of the machine coming online, immediately prior to closing its breaker, should be ____________. A. slightly less than the oncoming generator frequency B. the ... bus frequency C. slightly greater than the bus frequency D. the same as the bus voltage

Last Answer : Answer: C

Description : When paralleling two AC generators, the frequency of the incoming machine immediately prior to closing its breaker should be ____________. A. controlled by placing the governor switch in the automatic ... regulator C. slightly greater than the bus frequency D. slightly less than the bus frequency

Last Answer : Answer: C

Description : Prior to closing the breaker when paralleling two AC generators, the recommended practice is to have the frequency of the incoming machine _____________. A. slightly less than the line frequency B. the same as the line frequency C. slightly greater than the line frequency D. all of the above

Last Answer : Answer: C

Description : The division of the reactive KVA load between paralleled AC generators is initiated by the ______________. A. prime mover governors B. voltage regulators C. phase balance relay D. proportioner

Last Answer : Answer: B

Description : When paralleled, AC generators must have the same _________. A. frequency B. number of phases C. phase rotation D. all of the above

Last Answer : Answer: D

Description : When an alternator is to remain idle for even a few days _________________. A. lift the brushes and disconnect the pigtails B. insulate the collector rings with strips of cardboard C. energize the heater circuit D. open the equalizing bus disconnect switch

Last Answer : Answer: C

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : In order to prevent the winch shown in the illustration from turning while troubleshooting the controller circuit, _________________. EL-0102 A. set the dynamic brake by clamping contact 'DB' closed B. set the ... at 'B1' and 'B2' D. open the test link preventing current flow to the armature

Last Answer : Answer: D

Description : When using a megohmmeter to determine which shunt field coil is grounded in a DC machine, you must ____________. A. insulate the field frame from the ship's hull B. disconnect each shunt ... C. use a motor driven high capacity megohmmeter D. remove all main line lead connections before testing

Last Answer : Answer: B

Description : When paralleling two AC generators, the synchroscope selector switch and frequency meter switch should be set up to sense the frequency of the _____________. A. bus B. generator on the line C. oncoming generator D. bus transfer relay

Last Answer : Answer: C

Description : Passenger and merchant ships are constructed at (a) Mazagaon Docks (b) Hindustan Shipyard at Visakhapatnam (c) No place; the Indian docks only make navy ships (d) Goa shipyard

Last Answer : Ans: (b)

Description : Which of the synchroscope illustrations depicts the appropriate direction of rotation and position for closing the circuit breaker when paralleling AC generators? EL-0053 A. A B. B C. C D. D

Last Answer : Answer: D

Description : An AC generator panel is fitted with both synchronizing lamps and a synchroscope. When the synchroscope pointer reaches the noon position, one synchronizing light is bright and the other is dark. This ... sequence is incorrect C. the phase sequence is correct D. the generator breaker may be closed

Last Answer : Answer: B

Description : Two paralleled alternators are operating near rated load. If one trips out mechanically, which of the listed actions should be taken FIRST? A. Restart the tripped machine immediately. B. Strip the board ... circuits. C. Start the emergency generator. D. Transfer all vital loads to the emergency bus.

Last Answer : Answer: B

Description : The part of the shipboard electrical system used to control the distribution of power to the branch circuits, is the _____________. A. bridge control panel B. disconnect links C. governor relay box D. main switchboard

Last Answer : Answer: D

Description : To remove an alternator operating in parallel with another unit from the main electrical bus, you must FIRST _________. A. adjust the power factor on both units B. set the desired voltage on ... C. open the circuit breaker on the outgoing alternator D. remove the load from the outgoing alternator

Last Answer : Answer: D

Description : The graph shown in the illustration represents the speed droop curves of two equal capacity alternators about to be paralleled. When paralleled, the greater portion of the total load above 60% for each unit will be picked up ... unit 'A' B. by unit 'B' C. equally by each unit D. none of the above

Last Answer : Answer: A

Description : The kilowatt load can be adjusted on a paralleled generator by using the _____________. A. field rheostat B. governor control C. automatic voltage regulators D. hand tachometer

Last Answer : Answer: B

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation of the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. type of alternator

Last Answer : Answer: B

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation to the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. number of field poles per alternator

Last Answer : Answer: B

Description : After closing the circuit breaker to place two similar alternators in parallel, the NEXT step is to balance the _____________. A. power factor B. voltage load C. kilowatt load D. ampere load

Last Answer : Answer: C

Description : Before working on an electric cargo winch master switch or controller, you should _____________. A. spray the gasket surface with a solvent B. drain condensate from the box C. open the circuit breaker in the power supply and tag D. heat the switch box to remove any moisture

Last Answer : Answer: C